Single Operation - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

DC link components
8.6 Control Supply Module CSM
Note
Observe the connection sequence
If a selectively tripping, AC/DC-sensitive RCCB is used for the drive line-up, the Control
Supply Module must always be connected to the line supply downstream of this circuit
breaker. Otherwise, the residual current operated circuit breaker will trip erroneously if the
direct-current component is asymmetrically drawn in certain operating states.
8.6.4.1

Single operation

Within the drive line-up, the Control Supply Module must be connected to the drive line-up
via the DC link busbars as well as the 24 V busbars. The red 24 V connector from the
accessories pack provided must be inserted under all circumstances. The DIP switch on the
Control supply Module must be set to "single mode" The connection can be established as
shown below.
The supply for other 24 V loads outside the drive line-up using additional Control Supply
Modules, whose outputs are not connected in parallel, must be realized using the 24 V
terminal adapter (do not insert the red 24 V connector).
564
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6