Current-Carrying Capacity And Derating Factors For Power Cables And Signal Cables - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Cabinet design and EMC Booksize
12.8 Connection systems
12.8.3
Current-carrying capacity and derating factors for power cables and signal
cables
The current carrying capacity of PVC/PUR-insulated copper cables is specified for routing
types B1, B2 and C under continuous operating conditions in the table below with reference
to an ambient air temperature of 40° C. For other ambient temperatures, the values must be
corrected by the factors listed in the "Derating factors for deviating ambient temperatures"
table.
Routing types
B1
B2
C
Table 12- 18 Current carrying capacity according to EN 60204-1 for 40° C ambient temperature
Cross-section
mm
Signal cables
0,20
0,50
0,75
Power cables
0,75
1,00
1,50
2,50
4
6
10
16
25
35
50
70
95
120
740
Cables in conduits or cable ducts
Multi-conductor cables in conduits or cable ducts
Cables along walls, without conduits or cable ducts
2
Current carrying capacity, effective; AC 50/60 Hz or DC
For routing type
B1
B2
A
A
4,3
7,5
9
8,6
8,5
10,3
10,1
13,5
13,1
18,3
17,4
24
23
31
30
44
40
59
54
77
70
96
86
117
103
149
130
180
165
208
179
C
A
4,4
7,5
9,5
9,8
11,7
15,2
21
28
36
50
66
84
104
125
160
194
225