Setup Example, Drive-Line-Up, Cold Plate With External Liquid Heat Sink - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Cabinet design and EMC Booksize
12.11 Information on cold plate cooling
12.11.3.2

Setup example, drive-line-up, cold plate with external liquid heat sink

Control cabinet
Fan inside the control cabinet
External liquid heat sink
Figure 12-38 Example: cold plate drive line-up with external liquid cooling
Setup:
● Infeed: Active Line Module 55 kW
● 7 Single Motor Modules
● 3 internal fans at the top of the control cabinet
● 1 common external liquid heat sink (1200 mm x 480 mm)
The heat sinks and fans are not part of the scope of supply.
Recommended suppliers for liquid heat sinks include:
● Company DAU Ges.m.b.H & CO.KG., Ligist (Austria)
● Company Rittal GmbH & Co. KG, Herborn
770
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6