X24 24 V Terminal Adapter; Meaning Of The Leds On The Active Line Module - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Active line modules with cold plate
5.3 Interface description
5.3.6

X24 24 V terminal adapter

Table 5-5
Terminal block X24
Terminal
+
M
The 24 V terminal adapter is supplied as standard
Max. connectable cross-section: 6 mm
Type: Screw terminal 5 (see Appendix A)
5.3.7

Meaning of the LEDs on the Active Line Module

Table 5-6
Meaning of the LEDs on the Line Module
LED
Color
-
Green
Orange
Red
READY
Green
Red
Green/
Orange
or
Red/ Orange
-
Orange
DC LINK
Red
Hazardous DC link voltages may be present at any time regardless of the status of the "DC
link" LED.
The warning information on the components must be carefully observed!
116
Designation
24 V power supply
Ground
2
State
Off
Steady light
Steady light
Steady light
Flashing
2 Hz
Flashing
2 Hz
Off
Steady light
Steady light
WARNING
Technical specifications
24 V DC supply voltage
Electronics ground
Description
Electronics power supply outside the permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Firmware is being downloaded.
Component recognition via LED is activated (p0124).
Note:
Both options depend on the LED status when module
recognition is activated via p0124 = 1.
Electronics power supply outside the permissible
tolerance range.
DC link voltage within permissible tolerance range (only
when ready for operation)
DC link voltage outside the permissible tolerance range
(only when Active Line Module is ready for operation).
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4