Connection Bars U, V, W, Pe - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Motor-side power components
10.2 Voltage Protection Module VPM
10.2.3.3

Connection bars U, V, W, PE

The cables to the Motor Module and motor are routed through the cable entry of the Voltage
Protection Module and attached to the connection bars inside the unit.
Table 10- 12 Connections U, V, W, and PE
VPM120
Connection bolt
8 x M6
Cable lug
Crimp-type cable lug M6
Cable cross-
≤ 50 mm
section
Tightening torque
10 Nm
Cable entry
For cables with max. 40 mm ∅
Gland
2 x M50
3)
e.g. from Pflitsch,
order designation: UNI DICHT
EMV 250584117
Locknut M50: GM250PA
There are 2 connection points for each phase and for PE.
1)
There are 4 connection points for each of the phases U, W, and PE, and 2 connection points for phase V.
2)
The glands must be separately ordered.
3)
Note
Cable lengths with cross-sections of > 50 mm
Protection Module or between the Voltage Protection Module and the motor are
implemented using two cables connected in parallel.
604
1)
2
VPM200
8 x M8
1)
Crimp-type cable lug M8
≤ 50 mm
2
25 Nm
4 x M50
e.g. from Pflitsch,
order designation: UNI DICHT
EMV 250584117
Locknut M50: GM250PA
between the Motor Module and the Voltage
2
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
VPM200 Dynamic
14 x M8
2)
Tubular cable lug M8,
90° angled
≤ 50 mm
2
25 Nm
4 x M50
e.g. from Pflitsch,
order designation: UNI DICHT
EMV 250584117
Locknut M50: GM250PA
Booksize Power Units