X1 Line Connection - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

4.6.2.2

X1 line connection

Table 4- 40
X1: Line supply connection for Basic Line Modules 20 kW
For ring cable lugs without insulation
1)
Table 4- 41
X1: Line supply connection for Basic Line Modules 40 kW
For ring cable lugs without insulation
1)
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Terminal
Technical data
U1
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
V1
Max. connectable cross-section: 16 mm
W1
Type: Screw terminal 7 (Page 755)
Tightening torque: 1.5 ... 1.7 Nm
PE connection
Threaded hole M5 / 3 Nm
Terminal
Technical data
U1
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
V1
Max. connectable cross-section, 50 mm², end sleeves
W1
Tightening torque, min. 6 Nm
PE connection
Threaded hole M6 / 6 Nm
4.6 Basic Line Modules with internal air cooling
2
1
1)
Line Modules Booksize
233