Siemens Sinamics S120 Manual page 195

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

External air cooling
Rated power
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Input currents
Rated input current
at AC 400 V:
Input current
at AC 380 V / AC 480 V
at AC 400 V; S6 - 40 %
at AC 400 V; peak current
DC link currents
Rated DC link current
at 600 V:
DC link current:
for 600 V DC; for S6 - 40 %
for 600 V DC; peak current
Current carrying capacity
DC link busbar:
24 V busbar:
Electronics current drawn
at 24 V DC
Total power loss
(including electronics losses, see
Power loss tables (Page 781))
Max. ambient temperature
without derating
with derating
DC link capacitance
Active Line Module
Drive line-up, max.
Power factor
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit current
SCCR
3)
Sound pressure level
Cooling air requirement
Max. permissible heat sink
temperature
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
2)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
3)
Module in the drive system.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
6SL3131–
7TE28–0AAx
kW
80
V
510 ... 720
DC
V
820 ± 2 %
DC
V
360 ± 2 %
DC
A
122
AC
A
128 / 102
AC
A
161
AC
A
200
AC
A
134
DC
A
176
DC
A
218
DC
A
200
DC
A
20
DC
A
1.4
DC
W
1383.6
° C
40
° C
55
μF
2820
μF
20000
cosϕ
1
See Section Overcurrent protection using line fuses and circuit
breakers (Page 51)
kA
65
dB(A)
< 73
m
/h
520
3
73
Rated voltage for rated data 3 AC 380 V
kg
27.66
4.3 Active Line Modules with external air cooling
7TE31-2AAx
120
182
192 / 152
220
267
200
244
292
200
20
1.8
2243.2
40
55
3995
20000
1
65
< 73
520
83
30.74
Line Modules Booksize