Siemens Sinamics S120 Manual page 346

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Line Modules Booksize Compact
5.1 Smart Line Modules Booksize Compact
Danger to life through electric shock as well as fire hazard due to overcurrent protective
devices that trip too late
Overcurrent protective devices that do not trip or trip too late can cause an electric shock or
fire.
• To protect personnel and for fire protection purposes, at the infeed point, the short-
Danger to life through electric shock due to a high DC link voltage
As long as the Line Module is connected to the line supply, the DC link is charged with a
high voltage. Contact with components can result in death or serious injury.
• Isolate the Line Module from the line supply during installation or maintenance work,
Danger to life through electric shock due to the residual charge of the DC link capacitors
Because of the DC link capacitors, a hazardous voltage is present for up to five minutes
after the power supply has been switched off.
Contact with live parts can result in death or serious injury.
• Do not open the protective cover of the DC link until 5 minutes have elapsed.
• Measure the voltage before starting work on the DCP and DCN DC link terminals.
Danger to life through electric shock when the protective cover of the DC link is open
Contact with live parts can result in death or serious injury.
• Only operate the components with closed protective cover.
Danger to life through electric shock due to incorrect connection to the DC link
Incorrect connections can lead to overheating and therefore a risk of fire. There is also a
risk of an electric shock. This can result in serious injury or death.
• Only use adapters (DC link adapters and DC link rectifier adapters) released by
346
WARNING
circuit rating and loop impedance must correspond to the specifications in the
documentation in order for the installed overcurrent protection devices to trip within the
specified time.
DANGER
e.g. via the line contactor or main switch.
DANGER
DANGER
WARNING
Siemens for the connection to the DC link.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6

Advertisement

Table of Contents
loading

Table of Contents