X609 Terminal Strip - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

3.3.3.6

X609 terminal strip

Table 3- 11
Terminal strip X609
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Max. connectable cross-section: 1.5 mm
* Series connection NO contact of pre-charging contactor and bypass contactor (only for frame size GI)
NOTICE
Device failure due to overtemperature caused by incorrect wiring of Active Interface
Modules with frame size HI
In operation, Active Interface Modules, frame sizes HI require a signal on terminals
X609:11 and X609:12 to control the fans. If this signal is not present during operation, the
fans do not rotate and the module is shut down on overtemperature.
• Connect the signals on terminals X609:11 and X609:12 to the Active Interface Modules
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
Designation
P24
P24
M
M
L
L
N
N
Pre-charging contactor–A1
Pre-charging contactor–A2
Bypass contactor–A1
Bypass contactor–A2
Contactor feedback signal 1* Voltage: 230 VAC (195.5 ... 264.5 V)
Contactor feedback signal 2*
2
of frame sizes HI to control the fans.
3.3 Active Interface Modules, air-cooled
Technical data
External 24 V DC supply
Voltage: 24 VDC (20.4 ... 28.5 V)
Current consumption: Max. 0.25 A
Voltage: 230 VAC (195.5 ... 264.5 V)
Current consumption: Max. 10 A
Fan operating currents, see "Technical data"
Voltage: 230 VAC (195.5 ...
264.5 V)
Current consumption:
Max. 4 A
Voltage: 230 VAC (195.5 ...
264.5 V)
Current consumption:
Max. 6 A

 M ax. permissible current: 6 A
Line-side power components
To Active Line Module, X9:5
To Active Line Module, X9:6
To Active Line Module, X9:3
To Active Line Module, X9:4
57