Line connection and line-side power components
3.11 Line connection variants
3.11.3

Operation of the line connection components via a transformer

3.11.3.1

Safety instructions for line connection components

NOTICE
Destruction or damage to additional loads as a result of undesirable line harmonics
Line harmonics can occur if line filters that differ from those listed in this Manual are used.
These can disturb or damage other loads connected to the line supply.
• Only use line filters that are listed in this Manual.
NOTICE
Destruction or damage to additional loads as a result of incorrect connection
When incorrectly connecting the line filter, other loads can be destroyed or damaged.
• Connect additional loads upstream of the SINAMICS line filter (if required, via a
NOTICE
Damage and faults of devices connected to the Line Module as a result of overcurrent
protective devices that do not trip
Overcurrent protective devices that do not trip can result in faults at the SINAMICS Line
Modules. It can also result in faults and damage to other devices that are connected at the
same point of the line supply as the Line Module.
• In order to avoid material damage, the short-circuit power must correspond to what is
Note
If, for Line Modules, a transformer is used, this does not replace the external line reactor.
140
separate line filter).
specified in the documentation. This then ensures that the installed overcurrent
protective devices will trip.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6