Figure 3-15
Dimension drawing of Wideband Line Filter 120 kW for Active Lines Modules, all dimensions in mm and
(inches)
3.7.4.4

Technical data

Table 3- 8
Technical data: Wideband Line Filter for Active Line Modules
Rated power
Supply voltages:
Line voltage
Line frequency
Rated current
Power loss (see power
loss tables (Page 781))
Weight
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
6SL3000
0BE21-6AAx
unit
kW
16
V
3 AC 380 -10 % (-15 % < 1 min) ... 3 AC 480 +10 %
AC
Hz
47 ... 63 Hz
A
30
AC
W
70
kg
8,5
Line connection and line-side power components
0BE23-6AAx
0BE25-5AAx
36
55
67
103
90
110
14,5
15,5
3.7 Line filters
0BE28-0AAx
0BE31-2AAx
80
120
150
225
150
200
26
34,5
75