Notes On Electromagnetic Compatibility (Emc) - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

12.4

Notes on electromagnetic compatibility (EMC)

Requirements to implement the EMC are listed in EN 61000-6-2, EN 61000-6-4, EN 61800-
3, EN 60204-1 and in the Configuration Manual "EMC Installation Guideline" (order number
6FC5297-0AD30-0⃞P⃞). Conformance with the EMC Directive of the EC is ensured by
following the measures described in the Configuration Manual, "EMC installation guideline".
When installing components in cabinets, in order to fulfill the EMC Directive, the following
conditions must be additionally observed:
● Operation on TN and TT line supply systems with grounded neutral point and grounded
● Observance of information about cable shielding and equipotential bonding
● Use of the recommended power and signal cables from Siemens.
● Only use Siemens cables for the DRIVE-CLiQ connections.
Note
Radio service interference due to radio disturbances in residential environments
In a residential environment this product can cause radio disturbances, which may make
interference suppression measures necessary.
This device is not designed for unrestricted operation in the first environment (residential
environment) and may not be used in the first environment without suitable interference
suppression measures.
• Have qualified personnel carry out the installation and commissioning with suitable
Note
Malfunctions when not using original Siemens accessories
Malfunctions can occur if accessories are used that are not original.
• For DRIVE-CLiQ connections only use the DRIVE-CLiQ coupling and DRIVE-CLiQ
Note
Faulty operation of the machine due to incorrect shielding or cables that are too long
The machine can malfunction if the shielding is incorrect or the cables are too long.
• Always follow the correct procedures for the shielding and the specified cable lengths.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
protective conductor as well as to IT line supply systems
interference suppression measures.
cabinet bushing described in Chapter Accessories (Page 617)
Cabinet design and EMC Booksize
12.4 Notes on electromagnetic compatibility (EMC)
695

Advertisement

Table of Contents
loading

Table of Contents