Advertisement

Line-side power components
2.3 Active Interface Modules
2.3.3.5

X609 terminal strip

Table 2- 10
X609 terminal strip
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Max. connectable cross-section 1.5 mm
* Series connection NO contact of pre-charge contactor and bypass contactor (only for frame size GI)
CAUTION
Active Interface Modules of frame sizes HI and JI require a signal on terminal X609:11 and
12 to control the fans. If this signal is not present during operation, the fans do not rotate
and the module is shut down on overtemperature.
48
Designation
P24
P24
M
M
L
L
N
N
Pre-charge contactor–A1
Pre-charge contactor–A2
Bypass contactor–A1
Bypass contactor–A2
Contactor feedback 1*
Contactor feedback 2*
2
Technical specifications
Voltage: 24 V DC (20.4 V – 28.5 V)
Power consumption: max. 0.25 A
Voltage: 230 V AC (195.5 V – 264.5 V)
Power consumption: max. 10 A
Fan operating currents, see "Technical data"
Voltage: 230 V AC
(195.5 V – 264.5 V)
Power consumption:
max. 4 A
Voltage: 230 V AC
(195.5 V – 264.5 V)
Power consumption:
max. 6 A
Voltage: 230 V AC (195.5 V – 264.5 V)
Max. permissible current: 6 A
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
To Active Line Module, X9:5
To Active Line Module, X9:6
To Active Line Module, X9:3
To Active Line Module, X9:4
Chassis Liquid Cooled Power Units