Note
The cable length between the braking unit and the braking resistor is limited to 15 m.
The following braking resistors are suitable for connecting to the MASTERDRIVES braking
unit:
Table 8- 20
Braking resistors for MASTERDRIVES braking unit
Braking resistor
6SE7031-6ES87-2DC0
6SE7032-7ES87-2DC0
8.4.3.3

Switch S1

Switch S1 on the MASTERDRIVES braking unit is used to set the switch-on threshold. It is
located behind the front panel.
Switch S1 should be set to "high" (factory setting) in order to operate the braking unit on a
SINAMICS S120 drive line-up in booksize format. This means that the switch-on threshold is
at 757 V DC.
For more information, refer to the operating instructions for the MASTERDRIVES braking
unit.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
P
in kW
P
N
20
25
100
42,5
170
8.4 Braking units for 100 kW Basic Line Modules
in kW
P
in kW
max
150
255
DC link components
R in Ω
4
2,35