Cabinet design and EMC Booksize
12.8 Connection systems
Table 12- 26 Possible installations of the shield plate
Shield plate supplied for the motor connector
Lateral alignment of the shield plate
Mount the shield plate with the recesses facing upwards. Otherwise the shield plate will not be able to be tightened. It is
then no longer guaranteed that the shield plate is mounted so that there is a reliable electrical connection.
The shield plate can be mounted at various angles at the motor connector using two screws
(M4) that are provided (tightening torque: 1.8 Nm).
Note
In order to guarantee that the cable shield is connected through a large surface area, the
motor power cable is attached with a steel hose clamp at the shield plate.
752
Correct
Frontal alignment of the shield plate
Lateral alignment of the shield plate
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Incorrect
Booksize Power Units