Corrosion Inhibitor Additive (Inhibiting) - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Cooling circuit and coolant properties
13.2 Coolant requirements
NOTICE
Cooling circuit damage caused by seawater
The heat sink material is damaged by seawater.
• Do not use seawater as coolant.
Note
As a general rule, tap water is not suitable for use in the cooling circuit,
although it can be mixed with de-ionized water. Losses must always be replenished with de-
ionized water.
Note
The flow created when the heat sinks are filled results in automatic ventilation, so there is no
need for the devices to be ventilated separately.
The coolant should be checked 3 months after the cooling circuit is filled for the first time
and, subsequently, once a year. If the cooling water becomes cloudy, is colored, or becomes
contaminated by mould spores, the cooling circuit must be cleaned and refilled.
An inspection glass should be provided in the cooling circuit to make it easier to check the
cooling water.
13.2.2

Corrosion Inhibitor Additive (Inhibiting)

Nalco 00GE056 (Nalco company) is recommended as anti-corrosion agent. The
concentration of anti-corrosion agent in the cooling water must be at least 2500 ppm (250
ml/100 liters cooling water).
The water quality must correspond to Chapter Coolant properties (Page 803), or the water
used must be de-ionized.
Note
Corrosion inhibitor does not need to be added if the anti-freeze Antifrogen N is used in the
right concentration (refer to Chapter Anti-Freeze Additive (Page 805))
804
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6

Advertisement

Table of Contents
loading

Table of Contents