11.5.6.2
Fixing the cables to the rear cabinet panel
Fix the DC link connecting cables directly next to the last component at the rear control
cabinet panel. To do this, use C profile rails and matching cable clamps from the Rittal
company. The distance between the C profile rail and the lower side of the component is
approximately 125 mm.
Appropriately insulate the cable cores at the connection location before mounting.
①
②
③
④
⑤
Figure 11-30 Fixing the DC link connecting cable to the control cabinet panel, dimensions in mm and
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Control cabinet panel
DC link adapter
Cores of the DC link connecting cable
C profile rail from the Rittal company (order number 7831.570 / 7831.571)
Cable clamps for C profile rails from the Rittal company
(inch)
Accessories
11.5 DC link adapter
675