Note
If the cooling air requirement is not covered by the filtered fan, the components cannot
output their specified power.
The filters with filter fan must be regularly checked for dirt and cleaned if necessary.
4.3.7

Technical data

Table 4- 22
Technical data for Active Line Modules with external air cooling, part 1
External air cooling
Rated power
Infeed
Rated power (S1)
1)
Infeed power (S6 - 40 %)
Peak infeed power
1)
Regenerative feedback
Continuous regenerative power
Peak regenerative power
Supply voltages
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Input currents
Rated input current:
for AC 400 V
Input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 - 40 %
for AC 400 V; peak current
DC link currents
Rated DC link current:
for 600 V
DC link current:
for 600 V DC; for S6 - 40 %
for 600 V DC; peak current
Current carrying capacity
DC link busbars
Reinforced DC link busbars
24 V DC busbars
Electronics current drawn
at 24 V DC
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
6SL3131–
kW
kW (P
)
n
kW (P
)
1)
s6
kW (P
)
max
kW
kW
V
ACrms
Hz
V
DC
V
DC
V
DC
V
DC
A
AC
A
AC
A
AC
A
AC
A
DC
A
DC
A
DC
A
DC
A
DC
A
DC
A
DC
4.3 Active Line Modules with external air cooling
7TE21–6AAx
7TE23–6AAx
16
36
16
36
21
47
35
70
16
36
35
70
3 AC 380 ... 480 ± 10 % (15 % < 1 min)
47 ... 63 Hz
24 (20.4 ... 28.8)
510 ... 720
820 ± 2 %
360 ± 2 %
25
55
26 / 21
58 /46
32
71
54
107
27
60
35
79
59
117
100
200
150
--
20
20
0,95
1,5
Line Modules Booksize
7TE25–5AAx
7TE25–5AA3
+ Active
Interface
Module
55
55
55
55
71
71
91
110
55
55
91
110
84
84
88 / 70
88 /70
108
108
139
168
92
92
121
121
152
176
200
200
--
--
20
20
1,9
1,9
193