Danger to life through electric shock if the cutout in the protective cover has been broken
out
If the 24 V terminal adapter or the DC link infeed adapter is removed, and you touch live
parts this will result in death or severe injury.
• Replace the protective cover with the broken out cutouts by a new protective cover.
Note
The 24 V terminal adapter should always be installed to the left of the component located at
the far left, because if it is positioned anywhere else there may not be enough space for the
red 24 V jumpers.
If necessary, the 24 V terminal adapter can also be located at the right for 50 mm and
100 mm modules.
12.6.4

Attaching the motor cable

The Motor Modules are ideal for the operation of Siemens motors.
NOTICE
Damage to the components caused by switching overvoltages when third-party motors are
used
If the brake is controlled using the brake connection of the Motor Module, overvoltages can
result when the brake is switched off. These overvoltages can damage connected
components.
• To prevent switching overvoltages, deploy a free-wheeling diode for third-party motors.
Note
Connections with free-wheeling diodes extend the switching times of the brakes.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
WARNING
Cabinet design and EMC Booksize
12.6 Electrical connection
717