Parameters
NOTES
Terminal JOG input specifications (pulse train input or contact input) can be selected with Pr. 291.
When changing the setting value, be careful not to change the terminal JOG input specifications.
(Refer to page 5-292 for pulse train input.)
Connect a meter between the terminals FM and SD after changing the Pr. 291 setting value. When
using the pulse train of FM output (voltage output), be careful that voltage is not added to termi-
nal FM.
A connection cannot be made to the pulse input of a source logic type.
If all parameter clear is performed when selecting the high-speed pulse train output (Pr. 291 = "10,
11, 20, 21, 100"), the terminal FM output can be changed from high-speed pulse train output to
FM output (voltage output), since the Pr. 291 setting value returns to the initial value of "0".
Perform all parameter clear after removing the device connected to the terminal FM.
FM output circuit
Open collector output circuit
5.11.4

Adjusting terminals FM/CA and AM

By using the operation panel or parameter unit, terminals FM, CA and AM can be adjusted (calibrated)
to the full scale.
Pr.
C0 (900)
M310
C1 (901)
M320
C8 (930)
M330
C9 (930)
M331
C10 (931)
M332
C11 (931)
M333
867
M321
869
M334
The parameter number in parentheses ( ) is the one for use with the LCD operation panel and the
parameter unit.
FR-A800
3.3 k
Pr. 291
0, 1
8.2 V
10, 11,
20, 21, 100
Name
FM/CA terminal calibration
AM terminal calibration
Current output bypass signal
Current output bypass current
Current output gain signal
Current output gain current
AM output filter
Current output filter
(M) Monitor display and monitor output signal
Terminal FM
Initial value
Setting range
0%
0 to 100%
0%
0 to 100%
100%
0 to 100%
100%
0 to 100%
0.01 s
0 to 5 s
0.01 s
0 to 5 s
Description
Calibrates the scale of the meter
connected to terminals FM and CA.
Calibrates the scale of the analog
meter connected to terminal AM.
Set the signal value at the minimum
analog current output.
Set the current value at the
minimum analog current output.
Sets the signal value when the
analog current output is at
maximum.
Set the current value at the
maximum analog current output.
Set the terminal AM output filter.
Set the terminal AM output filter.
5 - 365