Bias And Gain For Torque (Magnetic Flux) And Set Voltage (Current) - Mitsubishi Electric FR-A820-00046 Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

(T) Multi-Function Input Terminal Parameters
5.12.6

Bias and gain for torque (magnetic flux) and set voltage (current)

Sensorless
Sensorless Vector
Sensorless
The magnitude (slope) of the torque can be set as desired in relation to the torque setting signal (0 to
5 V DC, 0 to 10 V DC, or 4 to 20 mA).
Use Pr. 73 "Analog input selection" or Pr. 267 "Terminal 4 input selection" to switch among input 0 to
5 V DC, 0 to 10 V, and 4 to 20 mA. (Refer to page 5-406.)
Pr.
C16 (919)
T110
C17 (919)
T111
C18 (920)
T112
C19 (920)
T113
C38 (932)
T410
C39 (932)
T411
C40 (933)
T412
C41 (933)
T413
241
M043
The parameter number in parentheses is the one for use with the LCD operation panel and the
parameter unit.
Changing the function of analog input terminal
The initial value for terminal 1 used as analog input is set to speed setting auxiliary (speed limit aux-
iliary), and terminal 4 is set to speed command (speed control). To use the analog input terminal as
torque command, torque limit, or magnetic flux command, set Pr. 868 "Terminal 1 function assign-
ment", Pr. 858 "Terminal 4 function assignment" to change the function. (Refer to page 5-411.)
The magnetic flux command is valid under vector control only.
5 - 426
Vector
Vector
PM
PM
PM
Name
Terminal 1 bias command (torque)
Terminal 1 bias (torque)
Terminal 1 gain command (torque)
Terminal 1 gain (torque)
Terminal 4 bias command (torque)
Terminal 4 bias (torque)
Terminal 4 gain command (torque)
Terminal 4 gain (torque)
Analog input display unit switchover
Initial
Setting
Description
value
range
Set the torque (magnetic flux) of the bias side of
0%
0 to 400%
terminal 1 input.
Set the converted % on bias side voltage of
0%
0 to 300%
terminal 1 input.
Set the torque (magnetic flux) of the gain
150% 0 to 400%
(maximum) of terminal 1 input.
Set the converted % on the gain side voltage of
100% 0 to 300%
terminal 1 input.
Set the torque (magnetic flux) of the bias side of
0%
0 to 400%
terminal 4 input.
Set the converted % on the bias side current
20%
0 to 300%
(voltage) of terminal 4 input.
Set the torque (magnetic flux) of the gain
150% 0 to 400%
(maximum) of terminal 4 input.
Set the converted % on gain side current
100% 0 to 300%
(voltage) of terminal 4 input.
0
% display
0
V/mA
1
display
Parameters
Select the unit for analog input
display.