Ethernet communication (FR-A800-E)
Programming example for fault record reading
The following program reads the fault records of the station 1 inverter to output to D1.
● Faults history No. 1 and 2 reading instruction code: H74 (hexadecimal)
For the error code, refer to page 6-5.
The reply code at the time of instruction code execution is set to D2. (Refer to page 5-821.)
SM1536
SD1536.0
SD1540.0
(0)
M0
X20
(4)
M300
(8)
M301
X100F
(10)
M302
X100F
(17)
(25)
Fig. 5-400:
Programming example 7
Programming example for resetting the inverter at an inverter fault
The following program resets the station 1 inverter at an inverter fault.
SM1536
SD1536.0
SD1540.0
(0)
M0
X101A
X20
(4)
(8)
Fig. 5-401:
Programming example 8
NOTES
The inverter reset with the flag RY1A shown above is enabled at an inverter fault only.
When Pr. 349 "Communication reset selection" = "0", an inverter reset can be made in any opera-
tion mode.
When using the instruction code execution request (RYF) with the instruction code (HFD) and data
(H9696) to reset the inverter, set a value other than "0" in Pr. 340 "Communication startup mode
selection" or change the operation mode to the Network operation mode. (Refer to program
example 2 on page 5-825).
Refer to page 5-633 for operation conditions of inverter reset.
5 - 830
M0
Check the data link status of the station 1.
PLS
M300
SET
M301
Write the faults history No.1 and No.2 read code
MOV
H74
W102
(H74) to RWw2.
Turn ON the instruction code execution request
SET
Y100F
(RY0F).
RST
M301
SET
M302
Read the fault record (RWr3) and the reply
MOV
W3
D1
code (RWr2) to output to D1 and D2 when the
instruction code execution completion (RX0F)
MOV
W2
D2
turns ON.
Turn OFF the instruction code execution request
RST
Y100F
(RY0F).
RST
M302
END
M0
Check the data link status of the station 1.
Turn ON the error reset request flag (RY1A).
Y101A
Turn OFF the error reset request flag (RY1A) when
the error status flag (RX1A) is OFF.
END