Parameters
Retry count check (Pr. 69)
● Reading the Pr. 69 value provides the cumulative number of successful restart times made by
retries. The cumulative count in Pr. 69 increases by 1 when a retry is successful. Retry is regarded
as successful when normal operation continues without a fault for the Pr. 68 setting multiplied by
four or longer (3.1 s at the shortest). (When retry is successful, the cumulative number of retry
failures is cleared.)
● Writing "0" in Pr. 69 clears the cumulative count.
Inverter
output
frequency
Retry success count
Y64
Fig. 5-135:
Selecting retry generating faults (Pr. 65)
Using Pr. 65, you can select the fault that will cause a retry. No retry will be made for the fault not in-
dicated. (For the fault details, refer to page 6-10.)
"
" indicates the faults selected for retry.
Retry
generating
fault
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E. BE
E. GF
E.OHT
E.OLT
E.OPT
E.OP3
E. PE
E.MB1
Tab. 5-121: Errors selected for retry
FR-A800
Retry success
Pr. 68 x 4
Pr. 68
(If it is below 3.1s, 3.1s is set.)
0
Retry start
Fault occurrence
ON
Retry success example
Retry success and retry failure example
Pr. 65 setting
0
1
2
3
Pr. 68
Inverter
output
frequency
Time
0
First
Success count + 1
retry
Fault
occurrence
Fault signal
(ALM)
ON
Y64
Retry
generating
4
5
fault
E.MB2
E.MB3
E.MB4
E.MB5
E.MB6
E.MB7
E.OS
E.OSD
E.PTC
E.CDO
E.SER
E.USB
E.ILF
E.PID
E.PCH
E.SOT
E.LCI
(H) Protective function parameter
Pr. 68
Pr. 68
Second
Third
retry
Retry failure
retry
Fault
Fault
occurrence
occurrence
ON
ON
Retry failure example
Pr. 65 setting
0
1
2
3
Time
(E.RET)
ON
I002589E
4
5
5 - 319