Programming example for setting the operation mode
The following explains a program to write various data to the inverter.
The following program changes the operation mode of the station 1 inverter to network operation.
● Operation mode write code: HFB (hexadecimal)
● Network operation set data: H0000 (hexadecimal) (Refer to page 5-757.)
● The reply code (RWr10) to the instruction code execution is set in D2.
(Refer to page 5-756 for the reply code (RWr10).))
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302
X1025
18
24
Fig. 5-375:
Programming example 2
FR-A800
Check the data link status of the station 1.
M0
PLS M300
SET M301
MOV H0FB W110
Write the operation mode write code (HFB)
to RWw10 and the set data (H0000) to RWw11.
MOV H0
W111
Turn ON the instruction code execution request (RY25).
SET Y1025
RST M301
SET M302
Read the reply code (RWr10) to D2 when the instruction code
MOV W10 D2
execution completion (RX25) turns ON.
Turn OFF the instruction code execution request (RY25).
RST Y1025
RST M302
END
CC-Link IE Field Network (FR-A800-GF)