Parameters
Logic reversing of inverter run enable signal (X10 signal, Pr. 599)
● Use Pr. 599 "X10 terminal input selection" to select the X10 signal input specification between
normally open (NO contact) and normally closed (NC contact). With the normally closed (NC
contact) input specification, the inverter output is shut off by turning OFF (opening) the X10
signal.
● Changing the inverter logic (NO/NC contact) with the Pr. 599 setting is required according to the
logic of the inverter operation enable signal sent from the option unit.
● The response time of the X10 signal is within 2 ms.
Output frequency
X10 signal (Pr. 599 = 0)
X10 signal (Pr. 599 = 1)
● Relationship between Pr. 599 and the inverter operation enable signal of each option unit
Pr.599 setting
0
(Initial value of standard models
and IP55 compatible models)
1
(Initial value of separated
converter types)
Tab. 5-325: Selecting NO/NC contact for X10 signal
NOTES
If the X10 signal is unassigned while Pr. 30 = "2" (FR-HC2/FR-CV connection) or "10 or 11" (DC feed-
ing mode 1), the MRS signal can be used as the X10 signal. At this time, logic setting for the signal
will follow Pr. 17 "MRS input selection".
MRS signal is enabled from any of the communication or external input, but when using the MRS
signal as Inverter run enable signal (X10), it can be used as input from external.
When FR-HC or MT-HC is connected, set Pr. 599 = "0 (initial value)".
When the terminal assignment is changed with Pr. 178 to Pr. 189 (input terminal function selec-
tion), wiring may be mistaken due to different terminal name and signal contents, or may affect
other functions. Set parameters after confirming the function of each terminal.
FR-A800
Fig. 5-355:
Motor coasts to stop
X10 signal
Time
ON
OFF
Corresponding signal of the option unit
FR-HC2
FR-CV
RDY
(negative logic)
RDYB
(initial setting)
RDY
RDYA
(positive logic)
(G) Control parameters
Operation according to the X10
signal status
FR-CC2
X10-ON: Inverter output shutoff
RDB
(NO contact)
X10-OFF: Inverter output shutoff
RDA
(NC contact)
I002755E