(N) Operation via communication and its settings
Operation command
Item
Tab. 5-284: Operation commands
The signal within parentheses ( ) is the initial status. The description changes depending on the
setting of Pr. 180 to Pr. 184, Pr. 187 (input terminal function selection) (page 5-439).
The inverter run enable signal is in the initial status for the separated converter type.
JOG operation/automatic restart after instantaneous power failure/start self-holding selection/
reset cannot be controlled over a network, so in the initial status bit8 to bit11 are invalid. To use
bit8 to bit11, change the signal by Pr. 185, Pr. 186, Pr. 188, or Pr. 189 (input terminal function
selection) (page 5-439). (A reset can be executed by the instruction code HFD.)
In RS-485 communication from the PU connector, only the forward rotation command and reverse
rotation command can be used.
5 - 652
Instruc-
Bit
Description
tion code
length
b0:
AU (Terminal 4 input selection)
b1:
Forward rotation command
b2:
Reverse rotation command
b3:
RL (Low-speed operation
command)
HFA
8 bits
b4:
RM (Middle-speed operation
command)
b5:
RH (High-speed operation
command)
b6:
RT (Second function selection)
b7:
MRS (Output stop)
b0:
AU (Terminal 4 input selection)
b1:
Forward rotation command
b2:
Reverse rotation command
b3:
RL (Low-speed operation
command)
b4:
RM (Middle-speed operation
command)
b5:
RH (High-speed operation
command)
b6:
RT (Second function selection)
HF9
16 bits
b7:
MRS (Output stop)
b8:
JOG
(Jog operation selection)
b9:
CS (Selection of automatic
restart after instantaneous
power failure, flying start)
b10: STP (STOP) (Start self-holding
selection)
b11: RES (Inverter reset)
b12 to b15: ⎯
Example
[Example 1] H02 Forward rotation
b7
0
0
0
0
0
0
[Example 2] H00 Stop
b7
0
0
0
0
0
0
[Example 1] H0002 Forward rotation
b15
0
0 0 0 0 0 0 0
0
0 0 0 0 0 1 0
[Example 2] H0800 low speed operation
(When Pr. 189 RES terminal function selection is set to "0")
b15
0
0 0 0 1 0 0 0
0
0 0 0 0 0 0 0
Parameters
b0
1
0
b0
0
0
b0
b0

Hide quick links: