(H) Protective function parameter
Frequency [Hz]
STF = ON
Pr. 1480 = 1
Measurement start
Fig. 5-146:
NOTES
Even if the load measurement is not properly completed, the load characteristics fault is detected
based on the load characteristics found by the already-completed portion of the measurement.
During the load characteristics measurement, the load characteristics fault detection is not per-
formed.
During the load characteristics measurement, linear acceleration/deceleration is performed even
if the S-pattern acceleration/deceleration is set.
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
5 - 336
f5 (Pr. 1486)
f4
f3
Load reference 2 recorded
f2
Load reference 1
recorded
f1 (Pr. 1487)
Pr. 1492
Read value of
1
Pr. 1480
STF
Y213
ON
SU signal
SU signal
Example of starting measurement from the stop state
Load reference 4 recorded
Load reference 3 recorded
Pr. 41
Pr. 41
Pr. 41
Pr. 1492
Pr. 1492
Pr. 1492
2
3
ON
ON
ON
ON
Load reference 5 recorded
Pr. 41
Pr. 41
Pr. 1492
4
5
0
ON
ON
ON
Parameters
Operation at the
set frequency
Time
I003027E