Mitsubishi Electric FR-A820-00046 Instruction Manual page 870

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

(N) Operation via communication and its settings
● Parameters
Pr.
0 to 999
C2 (902)
C3 (902)
125 (903)
C4 (903)
C5 (904)
C6 (904)
126 (905)
C7 (905)
C12 (917)
C13 (917)
C14 (918)
C15 (918)
C16 (919)
C17 (919)
C18 (920)
C19 (920)
C29 (925)
C30 (926)
Tab. 5-303: Parameters (1)
5 - 668
Register Name
For details on parameter names,
41000 to
refer to the parameter list
41999
(page 5-2).
Terminal 2 frequency setting bias
41902
(frequency)
Terminal 2 frequency setting bias
42092
(analog value)
Terminal 2 frequency setting bias
43902
(terminal analog value)
Terminal 2 frequency setting gain
41903
(frequency)
Terminal 2 frequency setting gain
42093
(analog value)
Terminal 2 frequency setting gain
43903
(terminal analog value)
Terminal 4 frequency setting bias
41904
(frequency)
Terminal 4 frequency setting bias
42094
(analog value)
Terminal 4 frequency setting bias
43904
(terminal analog value)
Terminal 4 frequency setting gain
41905
(frequency)
Terminal 4 frequency setting gain
42095
(analog value)
Terminal 4 frequency setting gain
43905
(terminal analog value)
41917
Terminal 1 bias frequency (speed)
42107
Terminal 1 bias (speed)
Terminal 1 bias (speed)
43917
(terminal analog value)
41918
Terminal 1 gain frequency (speed)
42108
Terminal 1 gain (speed)
Terminal 1 gain (speed)
43918
(terminal analog value)
Terminal 1 bias command
41919
(torque)
42109
Terminal 1 bias (torque)
Terminal 1 bias (torque)
43919
(terminal analog value)
Terminal 1 gain command
41920
(torque)
42110
Terminal 1 gain (torque)
Terminal 1 gain (torque)
43920
(terminal analog value)
Motor temperature detection
42115
calibration (analog input)
Motor temperature detection
43925
calibration (analog input)
(terminal analog value)
41926
Terminal 6 bias frequency (speed)
Read/
Remarks
Write
Read/
The parameter number + 41000 is the register
Write
number.
Read/
Write
Read/
Analog value (%) set to C3 (902)
Write
Analog value (%) of voltage (current) applied to
Read
terminal 2
Read/
Write
Read/
Analog value (%) set to C4 (903)
Write
Analog value (%) of voltage (current) applied to
Read
terminal 2
Read/
Write
Read/
Analog value (%) set to C6 (904)
Write
Analog value (%) of current (voltage) applied to
Read
terminal 4
Read/
Write
Read/
Analog value (%) set to C7 (905)
Write
Analog value (%) of current (voltage) applied to
Read
terminal 4
Read/
Write
Read/
Analog value (%) set to C13 (917)
Write
Read
Analog value (%) of voltage applied to terminal 1
Read/
Write
Read/
Analog value (%) set to C15 (918)
Write
Read
Analog value (%) of voltage applied to terminal 1
Read/
Write
Read/
Analog value (%) set to C17 (919)
Write
Read
Analog value (%) of voltage applied to terminal 1
Read/
Write
Read/
Analog value (%) set to C19 (920)
Write
Read
Analog value (%) of voltage applied to terminal 1
Read/
Write
Analog value (%) between terminals TH1 and TH2
Read
of the FR-A8AZ
Read/
Write
Parameters

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents