Monitor Display Selection For Terminals Fm And Am - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.11.3
Monitor display selection for terminals FM and
AM
The monitored statuses can be output as the following items: analog voltage (terminal AM), pulse train (terminal FM).
The signal (monitored item) to be output to terminal FM and terminal AM can be selected.
Pr.
Name
54
FM terminal function
M300
selection
158
AM terminal function
M301
selection
55
Frequency monitoring
M040
reference
56
Current monitoring reference
M041
866
Torque monitoring reference
M042
290
Monitor negative output
M044
selection
291
Pulse train I/O selection
D100

FR-A860-01080 or lower.

FR-A860-01440 or more.

Function assigned to Pr.185 JOG terminal function selection.
(M) Monitor display and monitor output signal
Initial value
Setting range
1 to 3, 5 to 14, 17, 18,
21, 24, 32 to 34, 36,
46, 50, 52, 53, 61, 62,
67, 70, 87 to 90, 92,
1
93, 95, 97, 98
(output
frequency)
1 to 3, 5 to 14, 17, 18,
21, 24, 32 to 34, 36,
46, 50, 52 to 54, 61,
62, 67, 70, 87 to 98
60 Hz
0 to 590 Hz
0 to 500 A

Inverter
Rated current
0 to 3600 A

150%
0 to 400%
0
0 to 7
0
1
10
11
0
20
21
100
Description
Select the monitored item to be output to
the terminal FM.
Select the monitored item to be output to
the terminal AM.
Set the full-scale value when outputting
the frequency monitor value to terminals
FM and AM.
Set the full-scale value when outputting
the output current monitor value to
terminals FM and AM.
Set the full-scale value when outputting
the torque monitor value to terminals FM
and AM.
Set the availability of output with a minus
sign for the terminal AM, the operation
panel display, or monitoring via
communication. (Refer to
page
Pulse train
Pulse train
input
output
(terminal JOG)
(terminal FM)
JOG signal
FM output

Pulse train input
FM output
High-speed pulse
JOG signal
train output

(50% duty)
High-speed pulse
Pulse train input
train output
(50% duty)
High-speed pulse
JOG signal
train output

(ON width fixed)
High-speed pulse
Pulse train input
train output
(ON width fixed)
High-speed pulse
train output
(ON width fixed)
Pulse train input
Output the pulse
train input without
changes.
PARAMETERS
355)
5
GROUP
M
357

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents