Mitsubishi Electric FR-A820-00046 Instruction Manual page 743

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
For the differential line driver, set the terminating resistor selection switch to the ON position (initial
status) to use. (Refer to page 2-73.)
Note that the terminating resistor switch should be set to the OFF position when sharing the same
encoder with another unit (NC, etc.) or when the terminating resistor is connected to another unit.
For the complementary, set the switch to the OFF position.
For terminal compatibility between the FR-A8TP and the FR-JCBL/FR-V7CBL, refer to the Instruction
Manual of the FR-A8TP.
A separate power supply of 5 V/12 V/15 V is necessary according to the encoder power specifica-
tion. When the encoder output is the differential line driver type, only 5 V can be input. If using the
24 V power supply of the FR-A8TP, 24 V power can be supplied from terminal PG24. Make the
voltage of the external power supply same as the encoder output voltage, and connect the
external power supply between PG and SD.
The encoder and the power supply can be shared under orientation control, encoder feedback
control, or vector control.
When a stop position command is input from outside, a plug-in option FR-A8AX is required. Refer
to page 5-527 for the external stop position command.
To enable terminal OH, set Pr. 876 "Thermal protector input" = "1 (initial value)". Terminal OH is
initially set to negative logic (SINK). Use the switch SW5A on the option unit FR-A8TP to change to
the shown positive logic (SOURCE).
FR-A800
(A) Application parameters
5 - 541

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents