Input Terminal Function Selection - Mitsubishi Electric FR-A820-00046 Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
5.12.8

Input terminal function selection

Use the following parameters to select or change the input terminal functions.
Pr.
178
T700
179
T7001
180
T702
181
T703
182
T704
183
T705
184
T706
185
T707
186
T708
187
T709
188
T710
189
T711
Pr.
699
T740
The initial value is for standard models and IP55 compatible models.
The initial value is for separated converter types.
NOTES
Using the SOURCE/SINK jumper (and the particular connection of the PC/SD terminal as a refer-
ence point), the input terminals can be changed between positive switching (source logic) or neg-
ative switching (sink logic) depending on regional requirements.
Connection diagrams in this Instruction Manual appear with the control logic of the input terminal
as source logic, unless otherwise specified. (For the control logic, refer to page 2-49.)
FR-A800
Name
STF terminal function
selection
STR terminal function
selection
RL terminal function
selection
RM terminal function
selection
RH terminal function
selection
RT terminal function
selection
AU terminal function
selection
JOG terminal function
selection
CS terminal function
selection
MRS terminal function
selection
STOP terminal function
selection
RES terminal function
selection
Name
Input terminal filter
(T) Multi-Function Input Terminal Parameters
Initial
Initial signal
value
60
STF (Forward rotation command)
61
STR (Reverse rotation command)
RL (Low-speed operation
0
command)
RM (Middle-speed operation
1
command)
RH (High-speed operation
2
command)
3
RT (Second function selection)
4
AU (Terminal 4 input selection)
5
JOG (Jog operation selection)
CS (Selection of automatic restart
6
after instantaneous power failure,
flying start)
MRS (Output stop)
24
X10 (Inverter run enable signal)
10
STP (STOP) (Start self-holding
25
selection)
62
RES (Inverter reset)
Initial
Setting range Description
value
Set the time to delay the input terminal
5 to 50 ms
response.
9999
9999
No input terminal filter
Setting range
0 to 20, 22 to 28, 37, 42 to 48,
50 to 53, 57 to 60, 62, 64 to
74, 76, 77 to 80, 87, 92 to 96,
9999
0 to 20, 22 to 28, 37, 42 to 48,
50 to 53, 57 to 59, 61, 62, 64
to 74, 76, 77 to 80, 87, 92 to
96, 9999
0 to 20, 22 to 28, 37, 42 to 48,
50 to 53, 57 to 59, 62, 64 to
74, 76, 77 to 80, 87, 92 to 96,
9999
5 - 439