Mitsubishi Electric FR-A820-00046 Instruction Manual page 1020

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Ethernet communication (FR-A800-E)
Monitor codes
Information about the inverter can be monitored by setting the special monitor selection No. of the
instruction code and monitor code using the remote registers, RWw0 and RWw4 to 7.
● For the monitor code (RWw0), select the first monitor description (RWr0) from the lower 8 bits and
the second monitor description (RWr1) from the upper 8 bits.
Example:
When output current is selected for the first monitor (RWr0) and running speed is selected for the
second monitor (RWr1), the monitor code (RWw0) is H0602.
● When Pr. 544 = "12, 14, or 18", descriptions of monitor codes 3 (RWw4) to 6 (RWw7) can be selected.
Monitor code
H00
H01
H02
H03
...
Tab. 5-407: Codes for selecting monitor items
NOTES
The monitor codes from H01 and up and their contents are the same as those of the RS-485 com-
munication dedicated monitor.
For the details of the monitor code and monitor description, refer to page 5-344.
When the remote registers RWw0 and RWw4 to 7 are used for monitoring, H00 (output frequency),
H01 (output frequency), and H05 (set frequency) always indicate the frequency regardless of the
settings of Pr. 37, Pr. 144, and Pr. 811.
5 - 818
Second monitor
description (first 8 bits)
Output frequency
Output frequency
Output current
Output voltage
...
First, third to sixth monitor
description (last 8 bits)
No monitoring (monitor
value is 0)
Parameters
Increments
0.01 Hz
0.01 Hz
0.01 A/0.1 A