Mitsubishi Electric FR-A820-00046 Instruction Manual page 674

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

(C) Motor constant parameters
Pr.
90
C120
92
C122
93
C123
859
C126
706
C130
1412
C135
711
C131
712
C132
717
C182
721
C185
725
C133
450
C200
453
C201
454
C202
51
C203
456
C204
457
C205
5 - 472
Name
Motor constant (R1)
Motor constant (L1)/
d-axis inductance (Ld)
Motor constant (L2)/
q-axis inductance (Lq)
Torque current/
Rated PM motor current
Induced voltage constant
(phi f)
Motor induced voltage
constant (phi f) exponent
Motor Ld decay ratio
Motor Lq decay ratio
Starting resistance tuning
compensation
Starting magnetic pole
position detection pulse
width
Motor protection current
level
Second applied motor
Second motor capacity
Number of second motor
poles
Second electronic thermal O/
L relay
Rated second motor voltage
Rated second motor
frequency
Initial
Setting range
value
0 to 50 Ω, 9999
9999
0 to 400 mΩ, 9999
0 to 500 mH, 9999
9999
0 to 50 mH, 9999
0 to 500 mH, 9999
9999
0 to 50 mH, 9999
0 to 500 A, 9999
9999
0 to 3600 A, 9999
0 to 5000 mV/(rad/s)
9999
9999
0 to 2
9999
9999
9999
0 to 100%, 9999
9999
0 to 100%, 9999
9999
0 to 200%, 9999
0 to 6000 μs,
9999
10000 to 16000 μs, 9999
100 to 500%
9999
9999
0, 1, 3 to 6, 13 to 16, 20, 23, 24,
30, 33, 34, 40, 43, 44, 50, 53, 54,
70, 73, 74, 330, 333, 334, 8090,
9999
8093, 8094, 9090, 9093, 9094
9999
0.4 to 55 kW
9999
0 to 3600 kW
9999
2, 4, 6, 8, 10, 12
9999
9999
0 to 500 A
0 to 3600 A
9999
9999
200/400
0 to 1000 V
V
10 to 400 Hz
9999
9999
Parameters
Description
Tuning data
(The value measured by offline auto
tuning is automatically set.)
9999: Uses the MM-CF constant for
the IPM motor MM-CF, and the
inverter internal data for a PM motor
other than MM-CF.
Set this parameter according to the
PM motor specifications.
The value calculated by the motor
constant parameter setting is used.
Set the exponent n when the
induced voltage constant phi f
n
(Pr. 706) is multiplied by 10
.
No exponent setting
Tuning data
(The value measured by offline auto
tuning is automatically set.)
9999: Uses the MM-CF constant for
the IPM motor MM-CF, and the
inverter internal data for a PM motor
other than MM-CF.
Set the maximum current (OCT) level
of the motor.
Uses the MM-CF constant for the IPM
motor MM-CF, and 200% for a PM
motor other than MM-CF.
Set this parameter when using the
second motor.
(the same specifications as Pr. 71).
The function is disabled.
Set the capacity of the second motor.
V/F control
Set the number of poles of the
second motor.
V/F control
Set the rated current of the second
motor.
Second electronic thermal O/L relay
disabled.
Set the rated voltage (V) of the
second motor.
Set the rated frequency (Hz) of the
second motor.
The MM-CF constant is used when
the IPM motor MM-CF is selected for
the second motor, and the inverter
internal data is used when a PM
motor other than MM-CF is selected.
Use the correct setting according to
the motor specification.