Mitsubishi Electric FR-A820-00046 Instruction Manual page 189

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Basic operation
NOTES
To change the frequency (60 Hz) at the maximum voltage input (initial value 5 V), adjust Pr. 125
"Terminal 2 frequency setting gain frequency".
To change the frequency (0 Hz) at the minimum voltage input (initial value 0 V), adjust the calibra-
tion parameter C2 "Terminal 2 frequency setting bias frequency".
Parameters referred to
Pr. 7
Pr. 8
Pr. 79
Pr. 125
C2 (Pr. 902)
FR-A800
Acceleration time
Deceleration time
Operation mode selection
Terminal 2 frequency setting gain frequency
Terminal 2 frequency setting bias frequency
Basic operation procedure (PU operation)
=>
page 5-241
=>
page 5-241
=>
page 5-271
=>
page 5-418
=>
page 5-418
4 - 19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents