GE UR Series B30 Instruction Manual
GE UR Series B30 Instruction Manual

GE UR Series B30 Instruction Manual

Bus differential system
Hide thumbs Also See for UR Series B30:
Table of Contents

Advertisement

Title Page
GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-0109-W2*
B30 Bus Differential System
UR Series Instruction Manual
B30 revision: 5.9x
Manual P/N: 1601-0109-W2 (GEK-113371A)
E83849
LISTED
IND.CONT. EQ.
52TL
GE Multilin's Quality Management
System is registered to
ISO9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE UR Series B30

  • Page 1 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1 System is registered to ISO9001:2008 Tel: +1 905 927 7070 Fax: +1 905 927 5098 QMI # 005094 UL # A3775 Internet: http://www.GEDigitalEnergy.com...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3: Table Of Contents

    APPROVALS ....................2-18 2.2.14 MAINTENANCE ....................2-18 3. HARDWARE 3.1 DESCRIPTION 3.1.1 PANEL CUTOUT ....................3-1 3.1.2 MODULE WITHDRAWAL AND INSERTION ............. 3-7 3.1.3 REAR TERMINAL LAYOUT................3-8 3.2 WIRING 3.2.1 TYPICAL WIRING.................... 3-10 GE Multilin B30 Bus Differential System...
  • Page 4 OSCILLOGRAPHY ...................5-42 5.2.9 USER-PROGRAMMABLE LEDS ..............5-44 5.2.10 USER-PROGRAMMABLE SELF TESTS ............5-48 5.2.11 CONTROL PUSHBUTTONS ................5-49 5.2.12 USER-PROGRAMMABLE PUSHBUTTONS............5-50 5.2.13 FLEX STATE PARAMETERS ................5-56 5.2.14 USER-DEFINABLE DISPLAYS ................5-56 5.2.15 DIRECT INPUTS AND OUTPUTS..............5-59 5.2.16 TELEPROTECTION ..................5-66 B30 Bus Differential System GE Multilin...
  • Page 5 5.9 TRANSDUCER INPUTS AND OUTPUTS 5.9.1 DCMA INPUTS ....................5-183 5.9.2 RTD INPUTS....................5-184 5.9.3 DCMA OUTPUTS ..................5-186 5.10 TESTING 5.10.1 TEST MODE ....................5-189 5.10.2 FORCE CONTACT INPUTS ................5-190 5.10.3 FORCE CONTACT OUTPUTS ..............5-191 GE Multilin B30 Bus Differential System...
  • Page 6 8.1.3 LOCAL PASSWORDS..................8-2 8.1.4 REMOTE PASSWORDS ..................8-3 8.1.5 ACCESS SUPERVISION ...................8-4 8.1.6 DUAL PERMISSION SECURITY ACCESS............8-4 8.2 SETTINGS SECURITY 8.2.1 SETTINGS TEMPLATES ...................8-6 8.2.2 SECURING AND LOCKING FLEXLOGIC™ EQUATIONS ......8-10 8.2.3 SETTINGS FILE TRACEABILITY..............8-12 B30 Bus Differential System GE Multilin...
  • Page 7 10.6 ENHANCING RELAY PERFORMANCE 10.6.1 USING SETTING GROUPS................10-12 11. MAINTENANCE 11.1 UNINSTALL AND CLEAR FILES AND DATA 11.1.1 UNINSTALL AND CLEAR FILES AND DATA..........11-1 11.2 REPAIRS 11.2.1 REPAIRS ......................11-2 11.3 STORAGE 11.3.1 STORAGE......................11-3 GE Multilin B30 Bus Differential System...
  • Page 8 OVERVIEW ....................... C-8 C.4.2 GSSE CONFIGURATION.................. C-8 C.4.3 FIXED GOOSE ....................C-8 C.4.4 CONFIGURABLE GOOSE ................C-8 C.4.5 ETHERNET MAC ADDRESS FOR GSSE/GOOSE ........C-10 C.4.6 GSSE ID AND GOOSE ID SETTINGS ............C-11 viii B30 Bus Differential System GE Multilin...
  • Page 9 ANALOG INPUTS ....................E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY ..................F-1 F.1.2 CHANGES TO THE B30 MANUAL..............F-2 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ............... F-11 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY ................F-14 INDEX GE Multilin B30 Bus Differential System...
  • Page 10 TABLE OF CONTENTS B30 Bus Differential System GE Multilin...
  • Page 11 (Cd), ólom (Pb) vagy higany (Hg) tartalomra utaló betűjelzés. A hulladék akkumulátor leadható a termék forgalmazójánál új akkumulátor vásárlásakor, vagy a kijelölt elektronikai hulladékudvarokban. További információ a www.recyclethis.info oldalon. GE Multilin B30 Bus Differential System...
  • Page 12 Batteriet är märkt med denna symbol, vilket kan innebära att det innehåller kadmium (Cd), bly (Pb) eller kvicksilver (Hg). För korrekt återvinning skall batteriet returneras till leverantören eller till en därför avsedd deponering. För mer information, se: www.recyclethis.info. B30 Bus Differential System GE Multilin...
  • Page 13 North America 905-294-6222 Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 GE Multilin B30 Bus Differential System xiii...
  • Page 14 0.1 BATTERY DISPOSAL 0 BATTERY DISPOSAL B30 Bus Differential System GE Multilin...
  • Page 15: Getting Started

    • Mounting screws For product information, instruction manual updates, and the latest software updates, please visit the GE Digital Energy website. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Multilin immediately. NOTE...
  • Page 16: Ur Overview

    This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. B30 Bus Differential System...
  • Page 17: Hardware Architecture

    (dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. GE Multilin B30 Bus Differential System...
  • Page 18: Ur Software Architecture

    5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic™ section in chapter 5. B30 Bus Differential System GE Multilin...
  • Page 19: Enervista Ur Setup Software

    After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD. Insert the GE EnerVista CD into your CD-ROM drive.
  • Page 20 EnerVista UR Setup to the Windows start menu. Click Finish to end the installation. The UR-series device will be added to the list of installed IEDs in the EnerVista Launchpad window, as shown below. B30 Bus Differential System GE Multilin...
  • Page 21: Configuring The B30 For Software Access

    RS232 port. A computer with an RS232 port and a serial cable is required. To use the RS485 port at the back of the relay, a GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 22 UR device must be on the same subnet. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 23: Using The Quick Connect Feature

    Before starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 port with a straight-through 9-pin to 9-pin RS232 cable. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 24 White/green White/orange Blue Blue White/blue White/blue Green Orange White/brown White/brown Brown Brown 842799A1.CDR FIGURE 1–6: ETHERNET CROSS-OVER CABLE PIN LAYOUT Now, assign the computer an IP address compatible with the relay’s IP address. 1-10 B30 Bus Differential System GE Multilin...
  • Page 25 Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Click on the “Use the following IP address” box. GE Multilin B30 Bus Differential System 1-11...
  • Page 26 Verify the physical connection between the B30 and the laptop computer, and double-check the programmed IP address in    setting, then repeat step 2 in the above procedure. PRODUCT SETUP COMMUNICATIONS NETWORK IP ADDRESS If the following sequence of messages appears when entering the command: C:\WINNT>ping 1.1.1.1 1-12 B30 Bus Differential System GE Multilin...
  • Page 27 If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the B30 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 28 The EnerVista UR Setup software will then proceed to configure all settings and order code options in the Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to identify and interrogate, in seconds, all UR-series devices in a particular location. 1-14 B30 Bus Differential System GE Multilin...
  • Page 29: Connecting To The B30 Relay

    View the B30 event record. • View the last recorded oscillography record. • View the status of all B30 inputs and outputs. • View all of the B30 metering values. • View the B30 protection summary. GE Multilin B30 Bus Differential System 1-15...
  • Page 30: Ur Hardware

    FIGURE 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the B30 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the B30 rear communications port.
  • Page 31: Using The Relay

    LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message    SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed GE Multilin B30 Bus Differential System 1-17...
  • Page 32: Relay Passwords

    Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level passwords. NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. 1-18 B30 Bus Differential System GE Multilin...
  • Page 33: Commissioning

    View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements. If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for prompt service. GE Multilin...
  • Page 34 1.5 USING THE RELAY 1 GETTING STARTED 1-20 B30 Bus Differential System GE Multilin...
  • Page 35: Product Description

    Ground time overcurrent 50BF Breaker failure Neutral time overcurrent Ground instantaneous overcurrent Phase time overcurrent Neutral instantaneous overcurrent Neutral overvoltage Phase instantaneous overcurrent Auxiliary overvoltage 50/74 CT trouble Restrained bus differential 50/87 Unrestrained bus differential GE Multilin B30 Bus Differential System...
  • Page 36 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION Figure 2–1: SINGLE LINE DIAGRAM B30 Bus Differential System GE Multilin...
  • Page 37: Ordering

    The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules (regu- lar CT/VT modules or the HardFiber modules). The order code options are described in the following sub-sections. GE Multilin B30 Bus Differential System...
  • Page 38 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels B30 Bus Differential System GE Multilin...
  • Page 39 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels GE Multilin B30 Bus Differential System...
  • Page 40 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels B30 Bus Differential System GE Multilin...
  • Page 41 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels GE Multilin B30 Bus Differential System...
  • Page 42: Replacement Modules

    4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs B30 Bus Differential System GE Multilin...
  • Page 43 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs GE Multilin B30 Bus Differential System...
  • Page 44: Specifications

    0.000 to 3.000 pu in steps of 0.001 Inverse; IEC (and BS) A/B/C and Short Dropout level: 97 to 98% of pickup Inverse; GE IAC Inverse, Short/Very/ Level accuracy: ±0.5% of reading from 10 to 208 V Extremely Inverse; I t;...
  • Page 45: User-Programmable Elements

    LEDs on Test sequence 2: all LEDs off, one LED at a time on for 1 s Test sequence 3: all LEDs on, one LED at a time off for 1 s GE Multilin B30 Bus Differential System 2-11...
  • Page 46: Monitoring

    I = 0.1 to 0.25 pu: ±0.05 Hz I > 0.25 pu: ±0.02 Hz (when current signal is used for RMS VOLTAGE frequency measurement) Accuracy: ±0.5% of reading from 10 to 208 V 2-12 B30 Bus Differential System GE Multilin...
  • Page 47: Inputs

    Auto-burnish impulse current: 50 to 70 mA Default states on loss of comms.: On, Off, Latest/Off, Latest/On Duration of auto-burnish impulse: 25 to 50 ms Ring configuration: Data rate: 64 or 128 kbps CRC: 32-bit GE Multilin B30 Bus Differential System 2-13...
  • Page 48: Power Supply

    15 to 250 V DC Operate time: < 0.6 ms Trickle current: approx. 1 to 2.5 mA Internal Limiting Resistor: 100 Ω, 2 W FORM-A CURRENT MONITOR Threshold current: approx. 80 to 100 mA 2-14 B30 Bus Differential System GE Multilin...
  • Page 49: Communications

    15 dB Maximum input –7.6 dBm –14 dBm –7 dBm power Typical distance 1.65 km 2 km 15 km Duplex full/half full/half full/half Redundancy The UR-2S and UR-2T only support 100 Mb multimode GE Multilin B30 Bus Differential System 2-15...
  • Page 50: Inter-Relay Communications

    – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Noise: 0 dB Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6days). 2-16 B30 Bus Differential System GE Multilin...
  • Page 51: Type Tests

    20 V/m, 80 MHz to 1 GHz Safety UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2.2.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin B30 Bus Differential System 2-17...
  • Page 52: Approvals

    Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to NOTE avoid deterioration of electrolytic capacitors. 2-18 B30 Bus Differential System GE Multilin...
  • Page 53: Hardware

    RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. 11.016” [279,81 mm] 9.687” [246,05 mm] 17.56” [446,02 mm] 7.460” [189,48 mm] 6.995” 6.960” [177,67 mm] [176,78 mm] 19.040” [483,62 mm] 842807A1.CDR Figure 3–1: B30 HORIZONTAL DIMENSIONS (ENHANCED PANEL) GE Multilin B30 Bus Differential System...
  • Page 54 The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent equipment. B30 Bus Differential System GE Multilin...
  • Page 55 The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. Figure 3–4: B30 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin B30 Bus Differential System...
  • Page 56 Figure 3–5: B30 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For side mounting B30 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Digital Energy website: • GEK-113180: UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...
  • Page 57 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: B30 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin B30 Bus Differential System...
  • Page 58 3.1 DESCRIPTION 3 HARDWARE Figure 3–7: B30 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL) B30 Bus Differential System GE Multilin...
  • Page 59: Module Withdrawal And Insertion

    Before performing this action, control power must be removed from the relay. Record the original loca- tion of the module to ensure that the same or replacement module is inserted into the correct slot. Modules with current input provide automatic shorting of external CT circuits. GE Multilin B30 Bus Differential System...
  • Page 60: Rear Terminal Layout

    Inst. Manual: Contact Outputs: Standard Pilot Duty / 250V AC 7.5A MAZB98000029 Serial Number: 360V A Resistive / 125V DC Break Firmware: GE Multilin 4A @ L/R = 40mS / 300W 2006/01/05 Mfg. Date: Technical Support: Made in Tel: (905) 294-6222 http://www.GEmultilin.com...
  • Page 61 3 HARDWARE 3.1 DESCRIPTION Figure 3–11: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin B30 Bus Differential System...
  • Page 62: Wiring

    3.2 WIRING 3 HARDWARE 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–12: TYPICAL WIRING DIAGRAM 3-10 B30 Bus Differential System GE Multilin...
  • Page 63: Dielectric Strength

    An LED on the front of the control power module shows the status of the power supply: LED INDICATION POWER SUPPLY CONTINUOUS ON ON / OFF CYCLING Failure Failure GE Multilin B30 Bus Differential System 3-11...
  • Page 64: Ct/Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair cabling on the zero-sequence CT is recommended. 3-12 B30 Bus Differential System GE Multilin...
  • Page 65 Substitute the tilde “~” symbol with the slot position of the module in the following figure. NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–15: CT/VT MODULE WIRING GE Multilin B30 Bus Differential System 3-13...
  • Page 66: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The B30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 67 Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent dam- age of the output contact (in situations when the element initiating the contact output is bouncing, at values in the region of the pickup value). GE Multilin B30 Bus Differential System 3-15...
  • Page 68 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-16 B30 Bus Differential System GE Multilin...
  • Page 69 Not Used ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin B30 Bus Differential System 3-17...
  • Page 70 3.2 WIRING 3 HARDWARE Figure 3–17: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-18 B30 Bus Differential System GE Multilin...
  • Page 71 3 HARDWARE 3.2 WIRING Figure 3–18: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output con- nections. GE Multilin B30 Bus Differential System 3-19...
  • Page 72 Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-20 B30 Bus Differential System GE Multilin...
  • Page 73 CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–21: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope. NOTE GE Multilin B30 Bus Differential System 3-21...
  • Page 74: Transducer Inputs And Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–22: TRANSDUCER INPUT/OUTPUT MODULE WIRING The following figure show how to connect RTDs. 3-22 B30 Bus Differential System GE Multilin...
  • Page 75 3 HARDWARE 3.2 WIRING Figure 3–23: RTD CONNECTIONS GE Multilin B30 Bus Differential System 3-23...
  • Page 76: Rs232 Faceplate Port

    10Base-F or 10Base-T (obsolete) RS485 Redundant 10Base-F or 10Base-T (obsolete) RS485 100Base-FX or 10/100Base-T RS485 Redundant 100Base-FX or 10/100Base-T RS485 100Base-FX (obsolete) RS485 Redundant 100Base-FX (obsolete) RS485 10/100Base-T RS485 Six-port managed Ethernet switch RS485 3-24 B30 Bus Differential System GE Multilin...
  • Page 77 Installation of the 10/100Base-T Ethernet cable at the same time as the CH1 and/or CH2 100Base-F fiber cables does not affect the communication over the CH1 or CH2 fiber ports. Figure 3–25: CPU MODULE COMMUNICATIONS WIRING (MODULE APPLICABLE DEPENDS ON ORDER CODE) GE Multilin B30 Bus Differential System 3-25...
  • Page 78 To ensure maximum reliability, all equipment should have similar transient protection devices installed. Both ends of the RS485 circuit should also be terminated with an impedance as shown below. Figure 3–26: RS485 SERIAL CONNECTION 3-26 B30 Bus Differential System GE Multilin...
  • Page 79: Irig-B

    (AM). Third party equipment is available for generating the IRIG-B signal; this equipment can use a GPS satellite system to obtain the time reference so that devices at different geographic locations can be syn- chronized. Figure 3–27: OPTIONS FOR IRIG-B CONNECTION GE Multilin B30 Bus Differential System 3-27...
  • Page 80 UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down. Figure 3–28: IRIG-B REPEATER Using an amplitude modulated receiver causes errors up to 1 ms in event time-stamping. NOTE 3-28 B30 Bus Differential System GE Multilin...
  • Page 81: Direct Input And Output Communications

    1 to channel 2 on UR2, the setting should be “Enabled” on UR2. This DIRECT I/O CHANNEL CROSSOVER forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1. GE Multilin B30 Bus Differential System 3-29...
  • Page 82 1300 nm, multi-mode, LED, 2 channels 1300 nm, single-mode, ELED, 2 channels 1300 nm, single-mode, LASER, 2 channels Channel 1: RS422, channel: 820 nm, multi-mode, LED Channel 1: RS422, channel 2: 1300 nm, multi-mode, LED 3-30 B30 Bus Differential System GE Multilin...
  • Page 83: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module. Module: 72/ 7D 73/ 7K Connection Location: Slot X Slot X 831720A3.CDR 1 Channel 2 Channels Figure 3–33: LASER FIBER MODULES GE Multilin B30 Bus Differential System 3-31...
  • Page 84: Interface

    Before performing this action, control power must be removed from the relay. The original location of the module should be recorded to help ensure that the same or replacement module is inserted into the correct slot. 3-32 B30 Bus Differential System GE Multilin...
  • Page 85 Internal Timing Mode: The system clock is generated internally. Therefore, the G.703 timing selection should be in the internal timing mode for back-to-back (UR-to-UR) connections. For back-to-back connections, set for octet timing (S1 = OFF) and timing mode to internal timing (S5 = ON and S6 = OFF). GE Multilin B30 Bus Differential System 3-33...
  • Page 86 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–38: G.703 DUAL LOOPBACK MODE 3-34 B30 Bus Differential System GE Multilin...
  • Page 87: Rs422 Interface

    1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. GE Multilin B30 Bus Differential System...
  • Page 88 Figure 3–42: CLOCK AND DATA TRANSITIONS d) RECEIVE TIMING The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data. NRZI-MARK is an edge-type, invertible, self-clocking code. 3-36 B30 Bus Differential System GE Multilin...
  • Page 89: Rs422 And Fiber Interface

    When using a laser interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver. Shield Tx – G.703 Rx – channel 1 Tx + Rx + Surge Fiber channel 2 842778A1.CDR Figure 3–44: G.703 AND FIBER INTERFACE CONNECTION GE Multilin B30 Bus Differential System 3-37...
  • Page 90: Ieee C37.94 Interface

    IEEE C37.94 standard, as shown below. In 2008, GE Digital Energy released revised modules 76 and 77 for C37.94 communication to enable multi-ended fault location functionality with firmware 5.60 release and higher. All modules 76 and 77 shipped since the change support this feature and are fully backward compatible with firmware releases below 5.60.
  • Page 91 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. GE Multilin B30 Bus Differential System...
  • Page 92 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE Figure 3–45: IEEE C37.94 TIMING SELECTION SWITCH SETTING 3-40 B30 Bus Differential System GE Multilin...
  • Page 93: C37.94Sm Interface

    It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below. In 2008, GE Digital Energy released revised modules 2A and 2B for C37.94SM communication to enable multi-ended fault location functionality with firmware 5.60 release and higher. All modules 2A and 2B shipped since the change support this feature and are fully backward compatible with firmware releases below 5.60.
  • Page 94 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. 3-42 B30 Bus Differential System GE Multilin...
  • Page 95 3 HARDWARE 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS Figure 3–46: C37.94SM TIMING SELECTION SWITCH SETTING GE Multilin B30 Bus Differential System 3-43...
  • Page 96 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3-44 B30 Bus Differential System GE Multilin...
  • Page 97: Human Interfaces

    Factory default values are supplied and can be restored after any changes. The following communications settings are not transferred to the B30 with settings files. Modbus Slave Address Modbus TCP Port Number RS485 COM1 Baud Rate RS485 COM1 Parity COM1 Minimum Response Time GE Multilin B30 Bus Differential System...
  • Page 98 The firmware of a B30 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”. B30 Bus Differential System GE Multilin...
  • Page 99: Enervista Ur Setup Main Window

    Settings list control bar window. Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar. 10. Quick action hot links. GE Multilin B30 Bus Differential System...
  • Page 100 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW B30 Bus Differential System GE Multilin...
  • Page 101: Extended Enervista Ur Setup Features

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. GE Multilin B30 Bus Differential System...
  • Page 102 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. B30 Bus Differential System GE Multilin...
  • Page 103 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND GE Multilin B30 Bus Differential System...
  • Page 104 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. B30 Bus Differential System GE Multilin...
  • Page 105: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. GE Multilin B30 Bus Differential System...
  • Page 106 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. 4-10 B30 Bus Differential System GE Multilin...
  • Page 107: Settings File Traceability

    UR-series device to determine if security SENT BACK TO ENERVISTA AND has been compromised. ADDED TO SETTINGS FILE. 842864A1.CDR Figure 4–11: SETTINGS FILE TRACEABILITY MECHANISM With respect to the above diagram, the traceability feature is used as follows. GE Multilin B30 Bus Differential System 4-11...
  • Page 108 Figure 4–12: DEVICE DEFINITION SHOWING TRACEABILITY DATA This information is also available in printed settings file reports as shown in the example below. Traceability data in settings report 842862A1.CDR Figure 4–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA 4-12 B30 Bus Differential System GE Multilin...
  • Page 109 If the user converts an existing settings file to another revision, then any existing traceability information is removed from the settings file. • If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings file. GE Multilin B30 Bus Differential System 4-13...
  • Page 110: Faceplate Interface

    The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over the faceplate which must be removed in order to access the keypad panel. The following figure shows the horizontal arrangement of the faceplate panels. Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS 4-14 B30 Bus Differential System GE Multilin...
  • Page 111: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. GE Multilin B30 Bus Differential System 4-15...
  • Page 112 LED indicator or target message, once the condition has been cleared (these latched conditions can also be reset via the   menu). The RS232 port is intended for connection SETTINGS INPUT/OUTPUTS RESETTING to a portable PC. keys are used by the breaker control feature. USER 4-16 B30 Bus Differential System GE Multilin...
  • Page 113 User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. GE Multilin B30 Bus Differential System 4-17...
  • Page 114: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational. • The B30 settings have been saved to a settings file. • The B30 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed. •...
  • Page 115 Remove the B30 label insert tool from the package and bend the tabs as described in the following procedures. These tabs will be used for removal of the default and custom LED labels. It is important that the tool be used EXACTLY as shown below, with the printed side containing the GE part number facing the user.
  • Page 116 Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay. Slide the label tool under the LED label until the tabs snap out as shown below. This will attach the label tool to the LED label. 4-20 B30 Bus Differential System GE Multilin...
  • Page 117 Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown below. Make sure the bent tab is pointing away from the relay. GE Multilin B30 Bus Differential System 4-21...
  • Page 118 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. 4-22 B30 Bus Differential System GE Multilin...
  • Page 119: Display

    If the mode is selected as three-pole, a single input tracks the breaker open or closed posi- tion. If the mode is selected as one-pole, all three breaker pole states must be input to the relay. These inputs must be in agreement to indicate the position of the breaker. GE Multilin B30 Bus Differential System 4-23...
  • Page 120: Menus

    Each press of the MENU key advances through the following main heading pages: • Actual values. • Settings. • Commands. • Targets. • User displays (when enabled). 4-24 B30 Bus Differential System GE Multilin...
  • Page 121: Changing Settings

    TIME: 1.0 s 4.3.8 CHANGING SETTINGS a) ENTERING NUMERICAL DATA Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define what values are acceptable for a setting. GE Multilin B30 Bus Differential System 4-25...
  • Page 122 For example: to enter the text, “Breaker #1”. Press the decimal to enter text edit mode. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position. 4-26 B30 Bus Differential System GE Multilin...
  • Page 123 To enter the initial setting (or command) password, proceed as follows: Press the MENU key until the header flashes momentarily and the message appears on the SETTINGS PRODUCT SETUP display. GE Multilin B30 Bus Differential System 4-27...
  • Page 124 FlexLogic™ operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings pass- DENIED word. These default settings can be changed in EnerVista under Settings > Product Setup > Security. 4-28 B30 Bus Differential System GE Multilin...
  • Page 125: Overview

    See page 5-67.   SETTINGS  AC INPUTS See page 5-69.  SYSTEM SETUP   POWER SYSTEM See page 5-70.   SIGNAL SOURCES See page 5-71.   BREAKERS See page 5-74.  GE Multilin B30 Bus Differential System...
  • Page 126  DIGITAL COUNTERS See page 5-154.   MONITORING See page 5-156.  ELEMENTS  SETTINGS  CONTACT INPUTS See page 5-165.  INPUTS / OUTPUTS   VIRTUAL INPUTS See page 5-167.  B30 Bus Differential System GE Multilin...
  • Page 127   SETTINGS TEST MODE See page 5-189.  TESTING FUNCTION: Disabled TEST MODE FORCING: See page 5-189.  FORCE CONTACT See page 5-190.  INPUTS  FORCE CONTACT See page 5-191.  OUTPUTS GE Multilin B30 Bus Differential System...
  • Page 128: Introduction To Elements

    PICKUP setting: For simple elements, this setting is used to program the level of the measured parameter above or below which the pickup state is established. In more complex elements, a set of settings may be provided to define the range of the measured parameters which will cause the element to pickup. B30 Bus Differential System GE Multilin...
  • Page 129: Introduction To Ac Sources

    The same considerations apply to transformer winding 2. The protection elements require access to the net current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2. GE Multilin B30 Bus Differential System...
  • Page 130 INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 < bank 1 > < bank 3 > < bank 5 > < bank 2 > < bank 4 > < bank 6 > B30 Bus Differential System GE Multilin...
  • Page 131 Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display them in the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1, F5, M1, M5, U1, and U5. GE Multilin B30 Bus Differential System...
  • Page 132: Product Setup

    (via the setting and command level access timeout settings). The remote setting and command ses- sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout. B30 Bus Differential System GE Multilin...
  • Page 133 ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both com- mands and settings. NOTE If a remote connection is established, local passcodes are not visible. NOTE GE Multilin B30 Bus Differential System...
  • Page 134  SUPERVISION  TIMEOUTS Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min 5-10 B30 Bus Differential System GE Multilin...
  • Page 135 If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain setting access, then the message is displayed on the front panel. UNAUTHORIZED ACCESS GE Multilin B30 Bus Differential System 5-11...
  • Page 136 If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. 5-12 B30 Bus Differential System GE Multilin...
  • Page 137: Display Properties

    The B30 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical GE Multilin B30 Bus Differential System...
  • Page 138: Clear Relay Records

    Set the properties for user-programmable pushbutton 1 by making the following changes in the  SETTINGS PRODUCT   menu: SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 “Self-reset” PUSHBUTTON 1 FUNCTION: “0.20 s” PUSHBTN 1 DROP-OUT TIME: 5-14 B30 Bus Differential System GE Multilin...
  • Page 139: Communications

    RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that these parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any of GE Multilin B30 Bus Differential System...
  • Page 140 Generally, each device added to the link should use the next higher address starting at 1. When using Modbus TCP/IP, the client must use the programmed value in the Unit Identifier field. See Appendix B for MODBUS SLAVE ADDRESS more information on the Modbus protocol. 5-16 B30 Bus Differential System GE Multilin...
  • Page 141 DNP CURRENT DEFAULT MESSAGE DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP VOLTAGE DEFAULT MESSAGE DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP POWER DEFAULT MESSAGE DEADBAND: 30000 GE Multilin B30 Bus Differential System 5-17...
  • Page 142 FRONT PANEL - RS232, NETWORK - TCP,  NETWORK NETWORK - UDP Range: NONE, COM1 - RS485, COM2 - RS485, DNP CHANNEL 2 PORT: MESSAGE FRONT PANEL - RS232, NETWORK - TCP, COM2 - RS485 NETWORK - UDP 5-18 B30 Bus Differential System GE Multilin...
  • Page 143 B30, the default deadbands will be in effect. The B30 relay does not support power metering. As such, the DNP POWER SCALE FACTOR DNP POWER DEFAULT settings are not applicable. DEADBAND NOTE GE Multilin B30 Bus Differential System 5-19...
  • Page 144 256 points. The value for each point is user-programmable and can be configured by assigning FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points. 5-20 B30 Bus Differential System GE Multilin...
  • Page 145 IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point NOTE are ignored. Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the B30 is restarted. NOTE GE Multilin B30 Bus Differential System 5-21...
  • Page 146    PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION  GSSE / GOOSE  TRANSMISSION  CONFIGURATION   RECEPTION MESSAGE  The main transmission menu is shown below: 5-22 B30 Bus Differential System GE Multilin...
  • Page 147 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In B30 releases previous to 5.0x, this name string was repre- sented by the setting. RELAY NAME GE Multilin B30 Bus Differential System 5-23...
  • Page 148 ID for each GOOSE sending device. This value can be left at its default if the feature is not required. Both the GOOSE VLAN settings are required by IEC 61850. PRIORITY GOOSE ETYPE APPID 5-24 B30 Bus Differential System GE Multilin...
  • Page 149 The aggressive scheme is only supported in fast type 1A GOOSE messages (GOOSEOut 1 and GOOSEOut 2). For slow GOOSE messages (GOOSEOut 3 to GOOSEOut 8) the aggressive scheme is the same as the medium scheme. GE Multilin B30 Bus Differential System...
  • Page 150 Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. 5-26 B30 Bus Differential System GE Multilin...
  • Page 151 Configure the GOOSE service settings by making the following changes in the  INPUTS/OUTPUTS REMOTE DEVICES  settings menu: REMOTE DEVICE 1 – to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”. REMOTE DEVICE 1 ID GE Multilin B30 Bus Differential System 5-27...
  • Page 152 The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™ operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con- taining the defined dataset. 5-28 B30 Bus Differential System GE Multilin...
  • Page 153 Range: up to 80 alphanumeric characters LOCATION: Location MESSAGE Range: 1 to 65535 in steps of 1 IEC/MMS TCP PORT MESSAGE NUMBER: Range: Disabled, Enabled INCLUDE NON-IEC MESSAGE DATA: Enabled Range: Disabled, Enabled SERVER SCANNING: MESSAGE Disabled GE Multilin B30 Bus Differential System 5-29...
  • Page 154 PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL MMXU DEADBANDS  MMXU DEADBANDS  MMXU1 DEADBANDS    MMXU2 DEADBANDS MESSAGE   MMXU3 DEADBANDS MESSAGE   MMXU4 DEADBANDS MESSAGE  5-30 B30 Bus Differential System GE Multilin...
  • Page 155 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the B30 virtual inputs. GE Multilin B30 Bus Differential System 5-31...
  • Page 156 ANALOG IN 1 MIN ANALOG IN 1 MAX numbers. Because of the large range of these settings, not all values can be stored. Some values may be rounded NOTE to the closest possible floating point number. 5-32 B30 Bus Differential System GE Multilin...
  • Page 157 LLN0 if a user needs some (but not all) data from already existing GGIO1, GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset. GE Multilin B30 Bus Differential System...
  • Page 158 XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1. 5-34 B30 Bus Differential System GE Multilin...
  • Page 159 IP address of the B30 into the “Address” box on the web browser. Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of those protocols. NOTE GE Multilin B30 Bus Differential System 5-35...
  • Page 160 60870-5-104 data change buffers, no more than two masters should actively communicate with the B30 at one time. Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of those protocols. NOTE 5-36 B30 Bus Differential System GE Multilin...
  • Page 161 B30 then listens to SNTP messages sent to the “all ones” broadcast address for the subnet. The B30 waits up to eighteen minutes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error. The UR-series relays do not support the multicast or anycast SNTP functionality. GE Multilin B30 Bus Differential System 5-37...
  • Page 162 MESSAGE (Modbus register address range) Fast exchanges (50 to 1000 ms) are generally used in control schemes. The B30 has one fast exchange (exchange 1) and two slow exchanges (exchange 2 and 3). 5-38 B30 Bus Differential System GE Multilin...
  • Page 163 Modbus address with no data, or 0. That is, if the first three settings contain valid Modbus addresses and the fourth is 0, the produced EGD exchange will contain three data items. GE Multilin B30 Bus Differential System...
  • Page 164: Modbus User Map

    Range: Sunday to Saturday (all days of the week) DST STOP DAY: MESSAGE Sunday Range: First, Second, Third, Fourth, Last DST STOP DAY MESSAGE INSTANCE: First Range: 0:00 to 23:00 DST STOP HOUR: MESSAGE 2:00 5-40 B30 Bus Differential System GE Multilin...
  • Page 165: User-Programmable Fault Report

    The relay includes two user-programmable fault reports to enable capture of two types of trips (for example, trip from ther- mal protection with the report configured to include temperatures, and short-circuit trip with the report configured to include voltages and currents). Both reports feed the same report file queue. GE Multilin B30 Bus Differential System 5-41...
  • Page 166: Oscillography

    See the  ACTUAL VALUES  menu to view the number of cycles captured per record. The following table provides sam- RECORDS OSCILLOGRAPHY ple configurations with corresponding cycles/record. 5-42 B30 Bus Differential System GE Multilin...
  • Page 167 FlexLogic™ operand state recorded in an oscillography trace. The length of DIGITAL 1(63) CHANNEL each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. Upon startup, the relay will automatically prepare the parameter list. GE Multilin B30 Bus Differential System 5-43...
  • Page 168: User-Programmable Leds

     TRIP & ALARM LEDS MESSAGE See page 5–47.   USER-PROGRAMMABLE MESSAGE See page 5–47.  LED  USER-PROGRAMMABLE MESSAGE  LED  USER-PROGRAMMABLE MESSAGE  LED ↓  USER-PROGRAMMABLE MESSAGE  LED 48 5-44 B30 Bus Differential System GE Multilin...
  • Page 169 The test responds to the position and rising edges of the control input defined by the set- LED TEST CONTROL ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. GE Multilin B30 Bus Differential System 5-45...
  • Page 170 2. Once stage 2 has started, the pushbutton can be released. When stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. 5-46 B30 Bus Differential System GE Multilin...
  • Page 171 LED 19 operand LED 8 operand LED 20 operand LED 9 operand LED 21 operand LED 10 operand LED 22 operand LED 11 operand LED 23 operand LED 12 operand LED 24 operand GE Multilin B30 Bus Differential System 5-47...
  • Page 172: User-Programmable Self Tests

    Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. self-test is not applicable to the B30 device. ETHERNET SWITCH FAIL FUNCTION NOTE 5-48 B30 Bus Differential System GE Multilin...
  • Page 173: Control Pushbuttons

    An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key must be released before the next one can be pressed. GE Multilin B30 Bus Differential System 5-49...
  • Page 174: User-Programmable Pushbuttons

    PUSHBTN 1 DROP-OUT MESSAGE TIME: 0.00 s Range: FlexLogic™ operand PUSHBTN 1 LED CTL: MESSAGE Range: Disabled, Normal, High Priority PUSHBTN 1 MESSAGE: MESSAGE Disabled Range: Disabled, Enabled PUSHBUTTON 1 MESSAGE EVENTS: Disabled 5-50 B30 Bus Differential System GE Multilin...
  • Page 175 The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the set- PUSHBTN 1 RESET ting or by directly pressing the associated active front panel pushbutton. GE Multilin B30 Bus Differential System 5-51...
  • Page 176 This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer. 5-52 B30 Bus Differential System GE Multilin...
  • Page 177 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. GE Multilin B30 Bus Differential System 5-53...
  • Page 178 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–9: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) 5-54 B30 Bus Differential System GE Multilin...
  • Page 179 User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via NOTE EnerVista UR Setup with the Maintenance > Enable Pushbutton command. GE Multilin B30 Bus Differential System 5-55...
  • Page 180: Flex State Parameters

    • USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi- gate the programmed displays. 5-56 B30 Bus Differential System GE Multilin...
  • Page 181 (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this conversion). GE Multilin B30 Bus Differential System 5-57...
  • Page 182 If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items NOTE are different. 5-58 B30 Bus Differential System GE Multilin...
  • Page 183: Direct Inputs And Outputs

    “Yes”), all direct output messages should be received back. If not, the direct input/output ring CH2 RING CONFIGURATION break self-test is triggered. The self-test error is signaled by the FlexLogic™ operand. DIRECT RING BREAK GE Multilin B30 Bus Differential System 5-59...
  • Page 184 The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged. 5-60 B30 Bus Differential System GE Multilin...
  • Page 185 UR IED 1 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–12: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. GE Multilin B30 Bus Differential System 5-61...
  • Page 186 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. 5-62 B30 Bus Differential System GE Multilin...
  • Page 187 Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below. GE Multilin B30 Bus Differential System...
  • Page 188 FlexLogic™ operand is set. When the total message counter reaches the user-defined maximum specified by the set- CRC ALARM CH1 MESSAGE COUNT ting, both the counters reset and the monitoring process is restarted. 5-64 B30 Bus Differential System GE Multilin...
  • Page 189 The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration. The total number of unreturned input and output messages is available as the   ACTUAL VALUES STATUS DIRECT  actual value. INPUTS UNRETURNED MSG COUNT CH1 GE Multilin B30 Bus Differential System 5-65...
  • Page 190: Teleprotection

    On two- terminals two-channel systems, the same is transmitted over LOCAL RELAY ID NUMBER both channels; as such, only the has to be programmed on the receiving end. TERMINAL 1 ID NUMBER 5-66 B30 Bus Differential System GE Multilin...
  • Page 191: Installation

    This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the IEC 61850 protocol. GE Multilin B30 Bus Differential System 5-67...
  • Page 192: Remote Resources Configuration

    Configure shared inputs and outputs as required for the application's functionality. Shared inputs and outputs are dis- tinct binary channels that provide high-speed protection quality signaling between relays through a Brick. For additional information on how to configure a relay with a process bus module, please refer to GE publication number GEK-113500: HardFiber System Instruction Manual.
  • Page 193: System Setup

    1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). GE Multilin B30 Bus Differential System 5-69...
  • Page 194: Power System

    ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be con- nected to system phases A, B, and C for correct operation. 5-70 B30 Bus Differential System GE Multilin...
  • Page 195: Signal Sources

    CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type, ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered, including specifying which CTs will be summed together. GE Multilin B30 Bus Differential System 5-71...
  • Page 196 The following figure shows the arrangement of sources used to provide the functions required in this application, and the CT/VT inputs that are used to provide the data. Figure 5–18: EXAMPLE USE OF SOURCES 5-72 B30 Bus Differential System GE Multilin...
  • Page 197 5 SETTINGS 5.4 SYSTEM SETUP Y LV D HV SRC 1 SRC 2 SRC 3 Phase CT F1+F5 None Ground CT None None Phase VT None None Aux VT None None GE Multilin B30 Bus Differential System 5-73...
  • Page 198: Breakers

    Range: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic™ operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled 5-74 B30 Bus Differential System GE Multilin...
  • Page 199 MANUAL CLOSE RECAL1 TIME: This setting specifies the interval required to maintain setting changes in effect after an operator has initiated a manual close command to operate a circuit breaker. • BREAKER 1 OUT OF SV: Selects an operand indicating that breaker 1 is out-of-service. GE Multilin B30 Bus Differential System 5-75...
  • Page 200 5 SETTINGS Figure 5–19: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the B30 is in “Programmed” mode and not in the local control mode. NOTE 5-76 B30 Bus Differential System GE Multilin...
  • Page 201 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–20: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) GE Multilin B30 Bus Differential System 5-77...
  • Page 202: Disconnect Switches

    1. • SWITCH 1 MODE: This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch. 5-78 B30 Bus Differential System GE Multilin...
  • Page 203 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the B30 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin B30 Bus Differential System 5-79...
  • Page 204 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–21: DISCONNECT SWITCH SCHEME LOGIC 5-80 B30 Bus Differential System GE Multilin...
  • Page 205: Flexcurves

    1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin- ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu. GE Multilin B30 Bus Differential System...
  • Page 206 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE 5-82 B30 Bus Differential System GE Multilin...
  • Page 207 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the B30 are displayed in the following graphs. GE Multilin B30 Bus Differential System 5-83...
  • Page 208 CURRENT (multiple of pickup) 842723A1.CDR Figure 5–25: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–26: RECLOSER CURVES GE113, GE120, GE138 AND GE142 5-84 B30 Bus Differential System GE Multilin...
  • Page 209 Figure 5–27: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–28: RECLOSER CURVES GE131, GE141, GE152, AND GE200 GE Multilin B30 Bus Differential System 5-85...
  • Page 210 Figure 5–29: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–30: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 5-86 B30 Bus Differential System GE Multilin...
  • Page 211 Figure 5–31: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–32: RECLOSER CURVES GE119, GE135, AND GE202 GE Multilin B30 Bus Differential System 5-87...
  • Page 212: Bus

    If a given circuit cannot be connected to any other bus section different than the protected one, the FlexLogic™ constant "On" is recommended for the status signal. 5-88 B30 Bus Differential System GE Multilin...
  • Page 213: Flexlogic

    Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic™ minimizes the requirement for auxiliary components and wiring while making more complex schemes possible. GE Multilin B30 Bus Differential System 5-89...
  • Page 214 The virtual input is presently in the ON state Virtual Output Virt Op 1 On The virtual output is presently in the set state (i.e. evaluation of the equation which produces this virtual output results in a "1") 5-90 B30 Bus Differential System GE Multilin...
  • Page 215 Breaker failure 1 timer 3 is operated BKR FAIL 1 TRIP OP Breaker failure 1 trip is operated BKR FAIL 2 to 6 Same set of operands as shown for BKR FAIL 1 GE Multilin B30 Bus Differential System 5-91...
  • Page 216 Digital counter 1 output is ‘equal to’ comparison value Counter 1 LO Digital counter 1 output is ‘less than’ comparison value Counter 2 to 8 Same set of operands as shown for Counter 1 5-92 B30 Bus Differential System GE Multilin...
  • Page 217 Phase B of phase time overcurrent 1 has dropped out PHASE TOC1 DPO C Phase C of phase time overcurrent 1 has dropped out PHASE TOC2 to 6 Same set of operands as shown for PHASE TOC1 GE Multilin B30 Bus Differential System 5-93...
  • Page 218 Teleprotection ↓ ↓ inputs/outputs TELEPRO INPUT 1-16 On Flag is set, Logic =1 TELEPRO INPUT 2-1 On Flag is set, Logic =1 ↓ ↓ TELEPRO INPUT 2-16 On Flag is set, Logic =1 5-94 B30 Bus Differential System GE Multilin...
  • Page 219 Asserted when the front panel PHASE B LED is on LED PHASE C Asserted when the front panel PHASE C LED is on LED NEUTRAL/GROUND Asserted when the front panel NEUTRAL/GROUND LED is on GE Multilin B30 Bus Differential System 5-95...
  • Page 220 (identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in the FlexLogic™ operands table above. 5-96 B30 Bus Differential System GE Multilin...
  • Page 221 Assigns previous FlexLogic™ operand to virtual The virtual output is set by the preceding ↓ virtual output 1. parameter output = Virt Op 96 ↓ Assigns previous FlexLogic™ operand to virtual output 96. GE Multilin B30 Bus Differential System 5-97...
  • Page 222: Flexlogic™ Rules

    Inspect each operator between the initial operands and final virtual outputs to determine if the output from the operator is used as an input to more than one following operator. If so, the operator output must be assigned as a virtual output. 5-98 B30 Bus Differential System GE Multilin...
  • Page 223 It is also recommended to list operator inputs from bottom to top. For demonstration, the final output will be arbitrarily identified as parameter 99, GE Multilin B30 Bus Differential System...
  • Page 224 AND (2) FLEXLOGIC ENTRY n: =Virt Op 3 827030A2.VSD Figure 5–39: FLEXLOGIC™ EQUATION FOR VIRTUAL OUTPUT 3 Repeating the process described for virtual output 3, select the FlexLogic™ parameters for Virtual Output 4. 5-100 B30 Bus Differential System GE Multilin...
  • Page 225 It is now possible to check that the selection of parameters will produce the required logic by converting the set of parame- ters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 4 dia- gram as a check. GE Multilin B30 Bus Differential System 5-101...
  • Page 226 In the expression above, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of feedback, in this case, used to create a seal-in effect with the latch, and is correct. 5-102 B30 Bus Differential System GE Multilin...
  • Page 227: Flexlogic™ Equation Editor

    TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". • TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0". GE Multilin B30 Bus Differential System 5-103...
  • Page 228: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. 5-104 B30 Bus Differential System GE Multilin...
  • Page 229 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS GE Multilin B30 Bus Differential System 5-105...
  • Page 230 DIRECTION = Under; FLEXELEMENT INPUT MODE = Signed; FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Absolute; FlexElement 1 OpSig 842706A2.CDR Figure 5–43: FLEXELEMENT™ INPUT MODE SETTING 5-106 B30 Bus Differential System GE Multilin...
  • Page 231 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. GE Multilin B30 Bus Differential System 5-107...
  • Page 232: Non-Volatile Latches

    LATCH N LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–44: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC 5-108 B30 Bus Differential System GE Multilin...
  • Page 233: Grouped Elements

    Each of the six setting group menus is identical. Setting Group 1 (the default active group) automatically becomes active if no other group is active (see Section 5.7.3: Setting Groups on page 5–144 for further details). GE Multilin B30 Bus Differential System...
  • Page 234 The biased bus differential function has a dual-slope operating characteristic (see figure below) operating in conjunction with saturation detection and a directional comparison principle (refer to the Bus zone 1 differential scheme logic figure in this section). 5-110 B30 Bus Differential System GE Multilin...
  • Page 235 BUS ZONE 1 DIFF LOW BPNT: This setting defines the lower breakpoint of the dual-slope operating characteristic. The percentage bias applied for the restraining current from zero to the value specified as is given by the LOW BPNT GE Multilin B30 Bus Differential System 5-111...
  • Page 236 BUS ZONE 1 DIFF SEAL-IN: This setting defines the drop-out time of the seal-in timer applied to the Flex- BUS 1 OP Logic™ operand. More information on the bus zone differential settings can be found in the Application of settings chapter. 5-112 B30 Bus Differential System GE Multilin...
  • Page 237 5 SETTINGS 5.6 GROUPED ELEMENTS re s tra in in g re s tra in in g Figure 5–46: BUS ZONE 1 DIFFERENTIAL SCHEME LOGIC GE Multilin B30 Bus Differential System 5-113...
  • Page 238: Phase Current

      PHASE IOC3 MESSAGE See page 5–122.   PHASE IOC4 MESSAGE See page 5–122.   PHASE IOC5 MESSAGE See page 5–122.   PHASE IOC6 MESSAGE See page 5–122.  5-114 B30 Bus Differential System GE Multilin...
  • Page 239 5.6 GROUPED ELEMENTS b) INVERSE TOC CURVE CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 240 5.041 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 5-116 B30 Bus Differential System GE Multilin...
  • Page 241 0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 GE Multilin B30 Bus Differential System 5-117...
  • Page 242 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–16: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 243 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The B30 uses the FlexCurve™ feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve™ sec- tion in this chapter for additional details. GE Multilin B30 Bus Differential System 5-119...
  • Page 244 (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see the figure below); the pickup level is calculated as ‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. 5-120 B30 Bus Differential System GE Multilin...
  • Page 245 PHASE TOC1 C DPO Multiplier-Phase C PHASE TOC1 C OP SETTING PHASE TOC1 PKP PHASE TOC1 VOLT RESTRAINT: PHASE TOC1 OP Enabled PHASE TOC1 DPO 827072A4.CDR Figure 5–48: PHASE TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin B30 Bus Differential System 5-121...
  • Page 246 The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing curves are shown below for form-A contacts in a 60 Hz system. 5-122 B30 Bus Differential System GE Multilin...
  • Page 247 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–49: PHASE INSTANTANEOUS OVERCURRENT TIMING CURVES Figure 5–50: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC GE Multilin B30 Bus Differential System 5-123...
  • Page 248: Neutral Current

    SETTING RESET: NEUTRAL TOC1 PKP NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–51: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC 5-124 B30 Bus Differential System GE Multilin...
  • Page 249 NEUTRAL IOC1 PICKUP: RESET DELAY : SETTING NEUTRAL IOC1 DPO NEUTRAL IOC1 OP 3( _0 - K _1 ) PICKUP NEUTRAL IOC1 BLOCK: Off=0 SETTING NEUTRAL IOC1 SOURCE: 827035A4.CDR Figure 5–52: NEUTRAL IOC1 SCHEME LOGIC GE Multilin B30 Bus Differential System 5-125...
  • Page 250: Ground Current

    ETT NG RESET: GROUND TOC1 PKP GROUND TOC1 IG ≥ PICKUP GROUND TOC1 DPO SOURCE: GROUND TOC1 OP ETT NG GROUND TOC1 BLOCK: 827036A3.VSD Off = 0 Figure 5–53: GROUND TOC1 SCHEME LOGIC 5-126 B30 Bus Differential System GE Multilin...
  • Page 251 ETT NG DELAY: GROUND IOC1 GROUND IOC1 RESET ETT NG PICKUP: DELAY: GROUND IOC1 SOURCE: IG ≥ PICKUP ETT NG GROUND IOC1 BLOCK: 827037A4.VSD Off = 0 Figure 5–54: GROUND IOC1 SCHEME LOGIC GE Multilin B30 Bus Differential System 5-127...
  • Page 252: Breaker Failure

    Range: 0.001 to 30.000 pu in steps of 0.001 BF1 N AMP HISET MESSAGE PICKUP: 1.050 pu Range: 0.001 to 30.000 pu in steps of 0.001 BF1 PH AMP LOSET MESSAGE PICKUP: 1.050 pu 5-128 B30 Bus Differential System GE Multilin...
  • Page 253 This can also occur in breaker-and-a-half or ring bus configurations where the first breaker closes into a fault; the protection trips and attempts to initiate breaker failure for the second breaker, which is in the process of closing, but does not yet have current flowing through it. GE Multilin B30 Bus Differential System 5-129...
  • Page 254 BREAKER FAILURE TIMER No. 2 (±1/8 cycle) INITIATE (1/8 cycle) BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle) BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle) FAULT cycles OCCURS 827083A6.CDR Figure 5–55: BREAKER FAILURE MAIN PATH SEQUENCE 5-130 B30 Bus Differential System GE Multilin...
  • Page 255 BF1 TIMER 3 PICKUP DELAY: Timer 3 is set to the same interval as timer 2, plus an increased safety margin. Because this path is intended to operate only for low level faults, the delay can be in the order of 300 to 500 ms. GE Multilin B30 Bus Differential System...
  • Page 256 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be given via output operand BKR FAIL 1 TRIP OP 5-132 B30 Bus Differential System GE Multilin...
  • Page 257 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–57: SINGLE-POLE BREAKER FAILURE, INITIATE GE Multilin B30 Bus Differential System 5-133...
  • Page 258 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–58: SINGLE-POLE BREAKER FAILURE, TIMERS 5-134 B30 Bus Differential System GE Multilin...
  • Page 259 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–59: THREE-POLE BREAKER FAILURE, INITIATE GE Multilin B30 Bus Differential System 5-135...
  • Page 260 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–60: THREE-POLE BREAKER FAILURE, TIMERS 5-136 B30 Bus Differential System GE Multilin...
  • Page 261: Voltage Elements

     ------------------ –   pickup where: T = operating time D = undervoltage delay setting (D = 0.00 operates instantaneously) V = secondary voltage applied to the relay = pickup level pickup GE Multilin B30 Bus Differential System 5-137...
  • Page 262 This can be applied for bus configurations of up to five feeders with the voltage signal available. If applied, use the undervoltage function to supervise the main differential output with an AND gate in the FlexLogic™ equation before driving the output contact. 5-138 B30 Bus Differential System GE Multilin...
  • Page 263 Source VT = Wye FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP FLEXLOGIC OPERAND PHASE UV1 DPO 827039AB.CDR Figure 5–62: PHASE UNDERVOLTAGE1 SCHEME LOGIC GE Multilin B30 Bus Differential System 5-139...
  • Page 264 “Definite time”. The source assigned to this element must be configured for a phase VT. NEUTRAL OV1 CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–63: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC 5-140 B30 Bus Differential System GE Multilin...
  • Page 265 AUX OV1 RESET Off=0 DELAY : FLEXLOGIC OPERANDS < Vx Pickup AUX OV1 OP SETTING AUX OV1 DPO AUX OV1 SIGNAL AUX OV1 PKP SOURCE: AUXILIARY VOLT (Vx) 827836A2.CDR Figure 5–64: AUXILIARY OVERVOLTAGE SCHEME LOGIC GE Multilin B30 Bus Differential System 5-141...
  • Page 266: Control Elements

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-142 B30 Bus Differential System GE Multilin...
  • Page 267 TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–66: TRIP BUS LOGIC GE Multilin B30 Bus Differential System 5-143...
  • Page 268: Setting Groups

    The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 5-144 B30 Bus Differential System GE Multilin...
  • Page 269: Selector Switch

    Range: FlexLogic™ operand SELECTOR 1 3BIT ACK: MESSAGE Range: Restore, Synchronize, Sync/Restore SELECTOR 1 POWER-UP MESSAGE MODE: Restore Range: Self-reset, Latched, Disabled SELECTOR 1 TARGETS: MESSAGE Self-reset Range: Disabled, Enabled SELECTOR 1 EVENTS: MESSAGE Disabled GE Multilin B30 Bus Differential System 5-145...
  • Page 270 • SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest 5-146 B30 Bus Differential System GE Multilin...
  • Page 271 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. GE Multilin B30 Bus Differential System 5-147...
  • Page 272 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–68: TIME-OUT MODE 5-148 B30 Bus Differential System GE Multilin...
  • Page 273 Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 GE Multilin B30 Bus Differential System 5-149...
  • Page 274 3-bit acknowledge SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–70: SELECTOR SWITCH LOGIC 5-150 B30 Bus Differential System GE Multilin...
  • Page 275: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. GE Multilin B30 Bus Differential System 5-151...
  • Page 276 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–72: TRIP CIRCUIT EXAMPLE 1 5-152 B30 Bus Differential System GE Multilin...
  • Page 277 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–73: TRIP CIRCUIT EXAMPLE 2 GE Multilin B30 Bus Differential System 5-153...
  • Page 278: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are blocked. 5-154 B30 Bus Differential System GE Multilin...
  • Page 279 COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–74: DIGITAL COUNTER SCHEME LOGIC GE Multilin B30 Bus Differential System 5-155...
  • Page 280: Monitoring Elements

    See page 5–157.  FLASHOVER 2  CT TROUBLE ZONE 1 MESSAGE See page 5–160.   CT TROUBLE ZONE 2 MESSAGE See page 5–160.   THERMAL OVERLOAD MESSAGE See page 5–162.  PROTECTION 5-156 B30 Bus Differential System GE Multilin...
  • Page 281 Voltage drop measured from either side of the breaker during the flashover period, Voltage difference drop, and Measured flashover current through the breaker. Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across the breaker. GE Multilin B30 Bus Differential System 5-157...
  • Page 282 This application does not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than setting. However, monitoring the breaker contact will ensure scheme stability. BRK 1 FLSHOVR DIFF V PKP 5-158 B30 Bus Differential System GE Multilin...
  • Page 283 Depending on the flashover protection application, the flashover current can vary from levels of the charging current when the line is de-energized (all line breakers open), to well above the maximum line (feeder) load (line/feeder con- nected to load). GE Multilin B30 Bus Differential System 5-159...
  • Page 284 CT TROUBLE ZONE 1 DELAY setting, CT Trouble is declared for the given phase by setting the appropriate FlexLogic™ output operand. 5-160 B30 Bus Differential System GE Multilin...
  • Page 285 CT TROUBLE 1 OP B SETTING BUS ZONE 1F SOURCE: | Icd1 | > PICKUP CT TROUBLE 1 OP C 836722A2.CDR SETTING BUS ZONE 1F STATUS: Off = 0 Figure 5–76: CT TROUBLE SCHEME LOGIC GE Multilin B30 Bus Differential System 5-161...
  • Page 286 I = measured overload RMS current. • = measured load RMS current before overload occurs. • k= IEC 255-8 k-factor applied to I , defining maximum permissible current above nominal current. • = protected element base (nominal) current. 5-162 B30 Bus Differential System GE Multilin...
  • Page 287 , element starts increasing the thermal energy: t Δ -------------- - (EQ 5.17) – op In When current is less than the dropout level, I > 0.97 × k × I , the element starts decreasing the thermal energy: GE Multilin B30 Bus Differential System 5-163...
  • Page 288 30 minutes Busbar 60 minutes 20 minutes Underground cable 20 to 60 minutes 60 minutes The logic for the thermal overload protection element is shown below. Figure 5–78: THERMAL OVERLOAD PROTECTION SCHEME LOGIC 5-164 B30 Bus Differential System GE Multilin...
  • Page 289: Inputs And Outputs

    The update is performed at the beginning of the protection pass so all protection and control functions, as well as FlexLogic™ equations, are fed with the updated states of the contact inputs. GE Multilin B30 Bus Differential System...
  • Page 290 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5-166 B30 Bus Differential System GE Multilin...
  • Page 291: Virtual Inputs

    SETTING “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–80: VIRTUAL INPUTS SCHEME LOGIC GE Multilin B30 Bus Differential System 5-167...
  • Page 292: Contact Outputs

    L-Cont Op 1 Range: FlexLogic™ operand OUTPUT H1a OPERATE: MESSAGE Range: FlexLogic™ operand OUTPUT H1a RESET: MESSAGE Range: Operate-dominant, Reset-dominant OUTPUT H1a TYPE: MESSAGE Operate-dominant Range: Disabled, Enabled OUTPUT H1a EVENTS: MESSAGE Disabled 5-168 B30 Bus Differential System GE Multilin...
  • Page 293 Application Example 3: A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement this functionality as described below: GE Multilin B30 Bus Differential System 5-169...
  • Page 294: Virtual Outputs

    FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: 5-170 B30 Bus Differential System GE Multilin...
  • Page 295: Remote Devices

    SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE    setting. CONFIGURATION TRANSMISSION GSSE GSSE ID In B30 releases previous to 5.0x, these name strings were represented by the setting. RELAY NAME GE Multilin B30 Bus Differential System 5-171...
  • Page 296: Remote Inputs

    (see the Remote devices section). The setting selects the specific bits of the REMOTE DEVICE (16) ID REMOTE IN 1 ITEM GSSE/GOOSE message required. 5-172 B30 Bus Differential System GE Multilin...
  • Page 297: Remote Double-Point Status Inputs

    REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUTPUTS DNA- 1(32) BIT PAIR Range: FlexLogic™ operand  REMOTE OUTPUTS DNA- 1 OPERAND:  DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled GE Multilin B30 Bus Differential System 5-173...
  • Page 298: Resetting

    RESET OP to identify the source of the command. The setting RESET OP (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) shown above selects the operand that will create the operand. RESET OP (OPERAND) 5-174 B30 Bus Differential System GE Multilin...
  • Page 299: Direct Inputs And Outputs

    FlexLogic™ operand that determines the state of this direct output. c) APPLICATION EXAMPLES The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. GE Multilin B30 Bus Differential System 5-175...
  • Page 300 DIRECT INPUT 7 DEFAULT STATE : "3" DIRECT INPUT 8 DEVICE ID : "3" DIRECT INPUT 8 BIT NUMBER : select "On" for security, select "Off" for dependability DIRECT INPUT 8 DEFAULT STATE 5-176 B30 Bus Differential System GE Multilin...
  • Page 301 "3" (effectively, this is a message from IED 1) DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: GE Multilin B30 Bus Differential System 5-177...
  • Page 302 In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct inputs 5 and 6 should be ANDed in FlexLogic™ and the resulting operand configured as the permission to trip ( HYB POTT setting). 5-178 B30 Bus Differential System GE Multilin...
  • Page 303: Teleprotection Inputs And Outputs

    The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/On” and logic 0 for “Latest/Off”. GE Multilin B30 Bus Differential System 5-179...
  • Page 304 (On 3-terminal system or 2-terminal (same for 1-2...1-16) SETTING with redundant channel) FLEXLOGIC OPERAND TELEPROT OUTPUT 2-1: (same for 2-2...2-16) Fail TELEPRO INPUT 2-1 On Off (Flexlogic Operand) (same for 1-2...1-16) 842750A2.CDR Figure 5–86: TELEPROTECTION INPUT/OUTPUT PROCESSING 5-180 B30 Bus Differential System GE Multilin...
  • Page 305: Iec 61850 Goose Analogs

    +IN and –IN inputs. FREQUENCY = 1 Hz BASE PHASE ANGLE ϕ = 360 degrees (see the UR angle referencing convention) BASE POWER FACTOR = 1.00 BASE RTDs BASE = 100°C GE Multilin B30 Bus Differential System 5-181...
  • Page 306: Iec 61850 Goose Integers

    “Default Value”, then the value of the GOOSE uinteger input is defined by the setting. UINTEGER 1 DEFAULT The GOOSE integer input FlexInteger™ values are available for use in other B30 functions that use FlexInteger™ values. 5-182 B30 Bus Differential System GE Multilin...
  • Page 307: Transducer Inputs And Outputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT H1 MIN VALUE DCMA INPUT H1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin B30 Bus Differential System 5-183...
  • Page 308: Rtd Inputs

    1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-184 B30 Bus Differential System GE Multilin...
  • Page 309 15.61 168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 GE Multilin B30 Bus Differential System 5-185...
  • Page 310: Dcma Outputs

    – MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. DRIVING SIGNAL MIN VAL MAX VAL 842739A1.CDR Figure 5–87: DCMA OUTPUT CHARACTERISTIC 5-186 B30 Bus Differential System GE Multilin...
  • Page 311 ------------------ - 161.66 kV, 254.03 kV (EQ 5.24) The base unit for voltage (refer to the FlexElements section in this chapter for additional details) is: 0.0664 kV 6024 × 400 kV (EQ 5.25) BASE GE Multilin B30 Bus Differential System 5-187...
  • Page 312 ± 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-188 B30 Bus Differential System GE Multilin...
  • Page 313: Testing

    The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED indicator, and by the critical fail relay, as shown in the following table. GE Multilin B30 Bus Differential System...
  • Page 314: Force Contact Inputs

    Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as “Dis- abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled. 5-190 B30 Bus Differential System GE Multilin...
  • Page 315: Force Contact Outputs

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin B30 Bus Differential System 5-191...
  • Page 316 5.10 TESTING 5 SETTINGS 5-192 B30 Bus Differential System GE Multilin...
  • Page 317: Actual Values

     STATUS  TELEPROT CH TESTS See page 6-9.   ACTUAL VALUES  BUS See page 6-12.  METERING   SOURCE SRC 1 See page 6-12.   SOURCE SRC 2  GE Multilin B30 Bus Differential System...
  • Page 318  FAULT REPORTS  EVENT RECORDS See page 6-17.   OSCILLOGRAPHY See page 6-17.   ACTUAL VALUES  MODEL INFORMATION See page 6-19.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-19.  B30 Bus Differential System GE Multilin...
  • Page 319: Contact Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin B30 Bus Differential System...
  • Page 320: Remote Double-Point Status Inputs

    The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of the display indicates the logic state of the contact output. B30 Bus Differential System GE Multilin...
  • Page 321: Virtual Outputs

    DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented. GE Multilin B30 Bus Differential System...
  • Page 322: Digital Counters

    STATUS ETHERNET Range: Fail, OK  ETHERNET ETHERNET PRI LINK  STATUS: OK Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: OK These values indicate the status of the primary and secondary Ethernet links. B30 Bus Differential System GE Multilin...
  • Page 323: Direct Inputs

     STATUS STATUS: Offline Range: Offline, Online DIRECT DEVICE 2 MESSAGE STATUS: Offline ↓ Range: Offline, Online DIRECT DEVICE 16 MESSAGE STATUS: Offline These actual values represent the state of direct devices 1 through 16. GE Multilin B30 Bus Differential System...
  • Page 324: Iec 61850 Goose Integers

     SIGNATURE: SLOW EXCHANGE 1 MESSAGE DATA LENGTH: These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size for the slow EGD exchanges are displayed. B30 Bus Differential System GE Multilin...
  • Page 325: Teleprotection Channel Tests

    “FAIL” message will be displayed. The “N/A” value appears if the local relay ID is set to a default value of “0”, the chan- nel is failed, or if the teleprotection inputs/outputs are not enabled. GE Multilin B30 Bus Differential System...
  • Page 326: Metering Conventions

    ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. 6-10 B30 Bus Differential System GE Multilin...
  • Page 327 SYSTEM SETUP POWER SYSTEM FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure. SYSTEM VOLTAGES SYMMETRICAL COMPONENTS WYE VTs DELTA VTs 827844A1.CDR Figure 6–2: MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS GE Multilin B30 Bus Differential System 6-11...
  • Page 328: Bus Zone

    Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignments for this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and power val- ues will be unavailable. 6-12 B30 Bus Differential System GE Multilin...
  • Page 329 The metered ground current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was programmed by the user for the associated source (see   SETTINGS SYSTEM SETUP SIGNAL SOURCES GE Multilin B30 Bus Differential System 6-13...
  • Page 330 The metered auxiliary voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was programmed by the user for the associated source (see   SETTINGS SYSTEM SETUP SIGNAL SOURCES 6-14 B30 Bus Differential System GE Multilin...
  • Page 331: Tracking Frequency

    × I SOURCE POWER = maximum value of V for the +IN and –IN inputs BASE BASE BASE SOURCE VOLTAGE = maximum nominal primary RMS value of the +IN and –IN inputs BASE GE Multilin B30 Bus Differential System 6-15...
  • Page 332: Iec 61580 Goose Analog Values

    RTD INPUT xx  -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value. 6-16 B30 Bus Differential System GE Multilin...
  • Page 333: Records

    This menu allows the user to view the number of triggers involved and number of oscillography traces available. The value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog- CYCLES PER RECORD raphy section of chapter 5 for additional details. GE Multilin B30 Bus Differential System 6-17...
  • Page 334 6 ACTUAL VALUES A trigger can be forced here at any time by setting “Yes” to the command. Refer to the  FORCE TRIGGER? COMMANDS menu for information on clearing the oscillography records. CLEAR RECORDS 6-18 B30 Bus Differential System GE Multilin...
  • Page 335: Product Information

    6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION   PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE multilin order code format;  MODEL INFORMATION ORDER CODE LINE 1: example order code shown  B30-E00-HCL-F8H-H6A Range: standard GE multilin order code format...
  • Page 336 6.5 PRODUCT INFORMATION 6 ACTUAL VALUES 6-20 B30 Bus Differential System GE Multilin...
  • Page 337: Commands And

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin B30 Bus Differential System...
  • Page 338: Relay Maintenance

    UPDATE command causes the relay to scan the backplane for the hardware modules and update the order code to ORDER CODE match. If an update occurs, the following message is shown. UPDATING... PLEASE WAIT B30 Bus Differential System GE Multilin...
  • Page 339 For example, it may be desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self- checking variables are reset to their initial state and diagnostics will restart from scratch. GE Multilin B30 Bus Differential System...
  • Page 340: Targets Menu

    The critical fail relay on the power supply module is de-energized. • All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. B30 Bus Differential System GE Multilin...
  • Page 341 Most of the minor self-test errors can be disabled. Refer to the settings in the User-programmable self-tests section in the Settings chapter for additional details. MODULE FAILURE___: Contact Factory (xxx) • Latched target message: Yes. • Description of problem: Module hardware failure detected. GE Multilin B30 Bus Differential System...
  • Page 342 How often the test is performed: The battery is monitored every five seconds. The error message displays after 60 sec- onds if the problem persists • What to do: Return the power supply module to GE Digital Energy for battery replacement. MAINTENANCE ALERT: Direct I/O Ring Break •...
  • Page 343 What to do: Check direct input and output configuration and wiring. REMOTE DEVICE FAIL: COMM Path Incomplete • Latched target message: No. • Description of problem: One or more GOOSE devices are not responding. GE Multilin B30 Bus Differential System...
  • Page 344 Description of problem: Abnormal restart from modules being removed or inserted while the B30 is powered-up, when there is an abnormal DC supply, or as a result of internal relay failure. • How often the test is performed: Event driven. • What to do: Contact the factory. B30 Bus Differential System GE Multilin...
  • Page 345: Security

    • ACCESS REM CMND ON: Asserted when remote command access is enabled. The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated every five seconds. GE Multilin B30 Bus Differential System...
  • Page 346: Password Security Menu

    ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both com- mands and settings. NOTE If a remote connection is established, local passcodes are not visible. NOTE B30 Bus Differential System GE Multilin...
  • Page 347: Remote Passwords

    If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password value. If you establish a local connection to the relay (serial), you cannot view remote passcodes. NOTE GE Multilin B30 Bus Differential System...
  • Page 348: Access Supervision

    Range: selected FlexLogic™ operands (see below)  DUAL PERMISSION LOCAL SETTING AUTH:  SECURITY ACCESS Range: FlexLogic™ operand REMOTE SETTING AUTH: MESSAGE Range: 5 to 480 minutes in steps of 1 ACCESS AUTH MESSAGE TIMEOUT: 30 min. B30 Bus Differential System GE Multilin...
  • Page 349 If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin B30 Bus Differential System...
  • Page 350: Settings Security

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. B30 Bus Differential System GE Multilin...
  • Page 351 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin B30 Bus Differential System...
  • Page 352 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND B30 Bus Differential System GE Multilin...
  • Page 353 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin B30 Bus Differential System...
  • Page 354: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. 8-10 B30 Bus Differential System GE Multilin...
  • Page 355 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin B30 Bus Differential System 8-11...
  • Page 356: Settings File Traceability

    UR-series device to determine if security SENT BACK TO ENERVISTA AND has been compromised. ADDED TO SETTINGS FILE. 842864A1.CDR Figure 8–11: SETTINGS FILE TRACEABILITY MECHANISM With respect to the above diagram, the traceability feature is used as follows. 8-12 B30 Bus Differential System GE Multilin...
  • Page 357 Figure 8–12: DEVICE DEFINITION SHOWING TRACEABILITY DATA This information is also available in printed settings file reports as shown in the example below. Traceability data in settings report 842862A1.CDR Figure 8–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA GE Multilin B30 Bus Differential System 8-13...
  • Page 358 If the user converts an existing settings file to another revision, then any existing traceability information is removed from the settings file. • If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings file. 8-14 B30 Bus Differential System GE Multilin...
  • Page 359: Enervista Security Management System

    Select the Security > User Management menu item to open the user management configuration window. Enter a username in the User field. The username must be between 4 and 20 characters in length. GE Multilin B30 Bus Differential System 8-15...
  • Page 360: Modifying User Privileges

    The EnerVista security management system must be enabled. The following procedure describes how to modify user privileges. Select the Security > User Management menu item to open the user management configuration window. Locate the username in the User field. 8-16 B30 Bus Differential System GE Multilin...
  • Page 361 When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights. Click OK to save the changes to user to the security management system. GE Multilin B30 Bus Differential System 8-17...
  • Page 362 8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8-18 B30 Bus Differential System GE Multilin...
  • Page 363: Theory Of Operation

    The output logic (Block 11) combines the differential, directional and saturation flags into the biased differential operation flag. The applied logic enhances performance of the relay while keeping an excellent balance between dependability/speed and security. Refer to Section 8.6: Output Logic and Examples for details. GE Multilin B30 Bus Differential System...
  • Page 364: Dynamic Bus Replica Mechanism

    FlexLogic™ for contact discrepancy filtering or extra security. The pair “SRC 1 - Cont Ip 1 On” defines the input to the Bus Zone 1. Figure 9–2: DYNAMIC BUS REPLICA MECHANISM B30 Bus Differential System GE Multilin...
  • Page 365: Ct Ratio Matching

    1A source is 2000 A : (600:5) : 5A/pu = 3.33 pu. The pu current of the 1B source is 1000 A : (500:1) : 1A/pu = 2.00 pu. The pu differential current is (1000A + 2000A) : 1000A = 3.00 pu. GE Multilin B30 Bus Differential System...
  • Page 366: Differential Principle

    , and HIGH SLOPE HIGH BPNT • a smooth transition from the bias of between the breakpoints. LOW SLOPE HIGH SLOPE B30 Bus Differential System GE Multilin...
  • Page 367: Differential And Restraining Currents

    ) should be set not higher than HIGH BPNT 5000A : 1000A = 5 pu (1000A is the base unit; see page 8–2 for the example). The same approach applies to the setting of the lower breakpoint, LOW BPNT GE Multilin B30 Bus Differential System...
  • Page 368: Enhanced Security

    The first level includes slopes and breakpoints of the characteristic with regard to the amount of the bias. The second level includes control over the split between the first and second regions of the characteristic. B30 Bus Differential System GE Multilin...
  • Page 369: Directional Principle

    The B30 implementation calculates the maximum angle for the considered currents and compares it against a fixed thresh- old of 90°. The flag indicating whether the directional protection principle is satisfied is available as the FlexLogic™ oper- BUS 1(2) DIR GE Multilin B30 Bus Differential System...
  • Page 370: Saturation Detector

    The differential- restraining trajectory The differential out of the differential characteristic characteristic for a entered certain period of time EXTERNAL FAULT and CT SATURATION SAT := 1 836729A1.CDR Figure 9–8: SATURATION DETECTOR STATE MACHINE B30 Bus Differential System GE Multilin...
  • Page 371: Output Logic And Examples

    CT saturation, the B30 remains stable. Figure 8-11 presents the same signals but for the case of an internal fault. The B30 trips in 10 ms (fast form-C output con- tact). GE Multilin B30 Bus Differential System...
  • Page 372 9.6 OUTPUT LOGIC AND EXAMPLES 9 THEORY OF OPERATION Figure 9–10: EXTERNAL FAULT EXAMPLE 9-10 B30 Bus Differential System GE Multilin...
  • Page 373 9 THEORY OF OPERATION 9.6 OUTPUT LOGIC AND EXAMPLES Figure 9–11: INTERNAL FAULT EXAMPLE GE Multilin B30 Bus Differential System 9-11...
  • Page 374 9.6 OUTPUT LOGIC AND EXAMPLES 9 THEORY OF OPERATION 9-12 B30 Bus Differential System GE Multilin...
  • Page 375: Application Of Settings

    S-1 through S-6; circuit C-5 can be connected to either bus via breakers B-5 and B-6. NORTH BUS CT-7 CT-1 CT-5 CT-2 CT-3 CT-4 CT-6 CT-8 SOUTH BUS 836731A2.CDR Figure 10–1: SAMPLE BUS CONFIGURATION GE Multilin B30 Bus Differential System 10-1...
  • Page 376 Table 10–2: BASIC CT DATA RATIO (Ω) LEADS (M) CTSEC CT-1 600:5 0.34 CT-2 600:5 0.34 CT-3 1200:5 0.64 CT-4 1000:5 0.54 CT-5, CT-6 1000:5 0.54 CT-7, CT-8 1200:5 0.64 836732A4.CDR Figure 10–2: APPROXIMATE CT MAGNETIZING CHARACTERISTICS 10-2 B30 Bus Differential System GE Multilin...
  • Page 377: Zoning And Dynamic Bus Replica

    NORTH BUS CT-1 CT-7 CT-2 CT-4 CT-3 CT-5 CT-6 CT-8 SOUTH BUS 836733A1.CDR Figure 10–3: NORTH BUS ZONE GE Multilin B30 Bus Differential System 10-3...
  • Page 378: South Bus Zone

    The trip signal should be routed directly to the B-6 and B-7 breakers while it should be supervised by the status of S-2, S-4 and S-6 for the B-2, B-3 and B-4 breakers, respectively. NORTH BUS CT-1 CT-7 CT-2 CT-4 CT-3 CT-5 CT-6 CT-8 SOUTH BUS 836734A1.CDR Figure 10–4: SOUTH BUS ZONE 10-4 B30 Bus Differential System GE Multilin...
  • Page 379: Biased Characteristic Breakpoints

    155.84 31.17 6.23 CT-4 1.75 137.30 22.88 4.58 CT-5, CT-6 1.63 147.42 24.57 4.91 CT-7, CT-8 1.85 155.84 31.17 6.23 The third and fourth columns of the above table have the following significance. GE Multilin B30 Bus Differential System 10-5...
  • Page 380: Low Breakpoint

    A combination of very high residual magnetism and a DC component with a long time constant may saturate a given CT even with the AC current below the suggested value of the lower breakpoint. The relay copes with this threat by using a 2- out-of-2 operating mode for low differential currents. 10-6 B30 Bus Differential System GE Multilin...
  • Page 381 CT voltage at 10 A exciting current obtained from the CT excitation curve CT limiting factor K is defined by the following equation: S_LIM × ------------- - (EQ 10.7) S…LIM × GE Multilin B30 Bus Differential System 10-7...
  • Page 382: Slopes And High Set Threshold

    Practically, CT time-to-saturate can be obtained by either of the following methods: • Method 1 — Download the "CT Time-to-Saturate Estimator.xlsm" spreadsheet from the GE Multilin web site, located under Support > Support Documents > B30 Bus Differential System. Enter the required system and CT parameters to obtain the CT time-to-saturate.
  • Page 383: External Faults On C-1

    The saturation does not occur before 23.68 ms and is detected by the Sat- uration Detector. Table 10–6: CALCULATIONS FOR THE EXTERNAL FAULTS ON C-3 (KA) (A SEC) (MS) (MS) FAULT FAULT SATURATION SATURATION CT-1 0.00 GE Multilin B30 Bus Differential System 10-9...
  • Page 384: External Faults On C-4

    Table 10–8: EXTERNAL FAULT CALCULATIONS ON C-5 (KA) (A SEC) (MS) (MS) FAULT FAULT SATURATION SATURATION CT-1 0.00 CT-2 0.00 CT-3 25.00 CT-4 25.00 26.37 CT-5 11.0 55.00 9.45 CT-7, CT-8 11.0 45.83 11.54 10-10 B30 Bus Differential System GE Multilin...
  • Page 385: Bus Differential Settings

    2 has been adopted. The highest internal fault current is 14kA, or 11.67 pu giving a good chance to clear a number of faults by the unbiased differential operation. GE Multilin B30 Bus Differential System 10-11...
  • Page 386: Enhancing Relay Performance

    CTs in any particular bus configuration. 10-12 B30 Bus Differential System GE Multilin...
  • Page 387: Maintenance

    Other files can be in standard formats, such as COMTRADE or .csv. You cannot erase directly the flash memory, but all records and settings in that memory can be deleted. Do this using the   command. SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS GE Multilin B30 Bus Differential System 11-1...
  • Page 388: Repairs

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Digital Energy service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gedigitalenergy.com/multilin/support/ret_proc.htm...
  • Page 389: Storage

    Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. GE Multilin B30 Bus Differential System 11-3...
  • Page 390: Disposal

    European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules as outlined earlier, dismantle the unit, and recycle the metal when possible. 11-4 B30 Bus Differential System GE Multilin...
  • Page 391: Parameter Lists

    Source 2 ground current angle 6233 SRC 2 I_0 Mag Amps Source 2 zero-sequence current magnitude 6235 SRC 2 I_0 Angle Degrees Source 2 zero-sequence current angle 6236 SRC 2 I_1 Mag Amps Source 2 positive-sequence current magnitude GE Multilin B30 Bus Differential System...
  • Page 392 Source 4 zero-sequence current magnitude 6363 SRC 4 I_0 Angle Degrees Source 4 zero-sequence current angle 6364 SRC 4 I_1 Mag Amps Source 4 positive-sequence current magnitude 6366 SRC 4 I_1 Angle Degrees Source 4 positive-sequence current angle B30 Bus Differential System GE Multilin...
  • Page 393 Source 6 zero-sequence current angle 6492 SRC 6 I_1 Mag Amps Source 6 positive-sequence current magnitude 6494 SRC 6 I_1 Angle Degrees Source 6 positive-sequence current angle 6495 SRC 6 I_2 Mag Amps Source 6 negative-sequence current magnitude GE Multilin B30 Bus Differential System...
  • Page 394 SRC 2 Vbc Mag Volts Source 2 phase BC voltage magnitude 6746 SRC 2 Vbc Angle Degrees Source 2 phase BC voltage angle 6747 SRC 2 Vca Mag Volts Source 2 phase CA voltage magnitude B30 Bus Differential System GE Multilin...
  • Page 395 SRC 4 Vcg Mag Volts Source 4 phase CG voltage magnitude 6862 SRC 4 Vcg Angle Degrees Source 4 phase CG voltage angle 6863 SRC 4 Vab RMS Volts Source 4 phase AB voltage RMS GE Multilin B30 Bus Differential System...
  • Page 396 SRC 6 Vag RMS Volts Source 6 phase AG voltage RMS 6978 SRC 6 Vbg RMS Volts Source 6 phase BG voltage RMS 6980 SRC 6 Vcg RMS Volts Source 6 phase CG voltage RMS B30 Bus Differential System GE Multilin...
  • Page 397 Oscillography number of triggers 13504 DCmA Inputs 1 Value DCmA input 1 actual value 13506 DCmA Inputs 2 Value DCmA input 2 actual value 13508 DCmA Inputs 3 Value DCmA input 3 actual value GE Multilin B30 Bus Differential System...
  • Page 398 RTD input 23 actual value 13575 RTD Inputs 24 Value RTD input 24 actual value 13576 RTD Inputs 25 Value RTD input 25 actual value 13577 RTD Inputs 26 Value RTD input 26 actual value B30 Bus Differential System GE Multilin...
  • Page 399 IEC 61850 GOOSE analog input 12 45608 GOOSE Analog In 13 IEC 61850 GOOSE analog input 13 45610 GOOSE Analog In 14 IEC 61850 GOOSE analog input 14 45612 GOOSE Analog In 15 IEC 61850 GOOSE analog input 15 GE Multilin B30 Bus Differential System...
  • Page 400: Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 A-10 B30 Bus Differential System GE Multilin...
  • Page 401: Modbus Communications

    See the Supported Function Codes section for complete details. An exception response from the slave is indi- cated by setting the high order bit of the function code in the response packet. See the Exception Responses section for further details. GE Multilin B30 Bus Differential System...
  • Page 402: Modbus Rtu Crc-16 Algorithm

    This algorithm requires the characteristic polynomial to be reverse bit ordered. The most significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder. A C programming language implementation of the CRC algorithm will be provided upon request. B30 Bus Differential System GE Multilin...
  • Page 403 No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC GE Multilin B30 Bus Differential System...
  • Page 404: Modbus Function Codes

    1 to 127 though only a small subset is generally needed. The relay supports some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail. FUNCTION CODE MODBUS DEFINITION GE MULTILIN DEFINITION Read holding registers Read actual values or settings Read holding registers...
  • Page 405: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high GE Multilin B30 Bus Differential System...
  • Page 406: Store Multiple Settings (Function Code 10H

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte B30 Bus Differential System GE Multilin...
  • Page 407: File Transfers

    Cleared Date to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT GE Multilin B30 Bus Differential System...
  • Page 408 EVTnnn.TXT (replace nnn with the desired starting record number) To read from a specific record to another specific record, use the following filename: EVT.TXT xxxxx yyyyy (replace xxxxx with the starting record number and yyyyy with the ending record number) B30 Bus Differential System GE Multilin...
  • Page 409: Memory Mapping

    0 (Off) 0412 Virtual Input 19 State 0 to 1 F108 0 (Off) 0413 Virtual Input 20 State 0 to 1 F108 0 (Off) 0414 Virtual Input 21 State 0 to 1 F108 0 (Off) GE Multilin B30 Bus Differential System...
  • Page 410 Digital Counter 1 Frozen Time Stamp us (microsecond 0 to 4294967295 F003 part of time stamp) 0808 ...Repeated for Digital Counter 2 0810 ...Repeated for Digital Counter 3 0818 ...Repeated for Digital Counter 4 0820 ...Repeated for Digital Counter 5 B-10 B30 Bus Differential System GE Multilin...
  • Page 411 0 to 65535 F500 1603 Field Shared Input States 0 to 65535 F500 1604 Field Shared Input Channel States 0 to 65535 F500 1605 Field Shared Input Test States 0 to 65535 F500 GE Multilin B30 Bus Differential System B-11...
  • Page 412 Source 1 Negative Sequence Current Angle -359.9 to 0 degrees F002 1822 Source 1 Differential Ground Current Magnitude 0 to 999999.999 0.001 F060 1824 Source 1 Differential Ground Current Angle -359.9 to 0 degrees F002 B-12 B30 Bus Differential System GE Multilin...
  • Page 413 21A9 Breaker Flashover 1 Status Closed A 0 to 65535 F300 21AA Breaker Flashover 1 Status Closed B 0 to 65535 F300 21AB Breaker Flashover 1 Status Closed C 0 to 65535 F300 GE Multilin B30 Bus Differential System B-13...
  • Page 414 IEC 61850 GGIO5 uinteger Input 8 Operand F612 26B8 IEC 61850 GGIO5 uinteger Input 9 Operand F612 26B9 IEC 61850 GGIO5 uinteger Input 10 Operand F612 26BA IEC 61850 GGIO5 uinteger Input 11 Operand F612 B-14 B30 Bus Differential System GE Multilin...
  • Page 415 Fault Report 1 Prefault Trigger 0 to 65535 F300 3093 Fault Report Analog Channel 1 (32 items) 0 to 65536 F600 30B3 Fault Report 1 Reserved (5 items) F001 30B8 ...Repeated for Fault Report 2 GE Multilin B30 Bus Differential System B-15...
  • Page 416 -32768 to 32767 °C F002 34FD RTD Input 14 Value -32768 to 32767 °C F002 34FE RTD Input 15 Value -32768 to 32767 °C F002 34FF RTD Input 16 Value -32768 to 32767 °C F002 B-16 B30 Bus Differential System GE Multilin...
  • Page 417 Field Unit Process Card Ports (Read/Write Setting) 3878 Field Unit 1 Process Card Port 0 to 7 F244 6 (H1a) 3879 Field Unit 2 Process Card Port 0 to 7 F244 4 (H2a) GE Multilin B30 Bus Differential System B-17...
  • Page 418 ...Repeated for Field Contact Input 16 39B0 ...Repeated for Field Contact Input 17 39BB ...Repeated for Field Contact Input 18 39C6 ...Repeated for Field Contact Input 19 39D1 ...Repeated for Field Contact Input 20 B-18 B30 Bus Differential System GE Multilin...
  • Page 419 ...Repeated for Field Contact Output 7 3D2A ...Repeated for Field Contact Output 8 Field Unit Latching Outputs (Read/Write Setting) (8 modules) 3D60 Field Latching Output 1 ID 0 to 1 F205 "FLO Ux /LO" GE Multilin B30 Bus Differential System B-19...
  • Page 420 Field Unit Transducer 1 Max Value -9999.999 to 9999.999 0.001 F004 100000 3EDC Field Unit Transducer 1 Units F206 (none) 3EDF ...Repeated for Field Unit Transducer 2 3EEE ...Repeated for Field Unit Transducer 3 B-20 B30 Bus Differential System GE Multilin...
  • Page 421 0.1 to 1 F001 Communications (Read/Write Setting) 407D COM2 Selection 0 to 3 F601 0 (RS485) 407E COM1 Minimum Response Time 0 to 1000 F001 407F COM2 Minimum Response Time 0 to 1000 F001 GE Multilin B30 Bus Differential System B-21...
  • Page 422 40EA IEC 60870-5-104 Energy Default Threshold 0 to 100000000 F003 30000 40EC IEC 60870-5-104 Power Default Threshold 0 to 100000000 F003 30000 40EE IEC 60870-5-104 Other Default Threshold 0 to 100000000 F003 30000 B-22 B30 Bus Differential System GE Multilin...
  • Page 423 Daylight Savings Time (DST) Stop Day Instance 0 to 4 F239 0 (First) 41B1 Daylight Savings Time (DST) Stop Hour 0 to 23 F001 Oscillography (Read/Write Setting) 41C0 Oscillography Number of Records 1 to 64 F001 GE Multilin B30 Bus Differential System B-23...
  • Page 424 ...Repeated for User-Programmable LED 38 42CC ...Repeated for User-Programmable LED 39 42CE ...Repeated for User-Programmable LED 40 42D0 ...Repeated for User-Programmable LED 41 42D2 ...Repeated for User-Programmable LED 42 42D4 ...Repeated for User-Programmable LED 43 B-24 B30 Bus Differential System GE Multilin...
  • Page 425 ...Repeated for Source 2 458E ...Repeated for Source 3 4595 ...Repeated for Source 4 459C ...Repeated for Source 5 45A3 ...Repeated for Source 6 Power System (Read/Write Setting) 4600 Nominal Frequency 25 to 60 F001 GE Multilin B30 Bus Differential System B-25...
  • Page 426 ...Repeated for User-Definable Display 10 4D40 ...Repeated for User-Definable Display 11 4D60 ...Repeated for User-Definable Display 12 4D80 ...Repeated for User-Definable Display 13 4DA0 ...Repeated for User-Definable Display 14 4DC0 ...Repeated for User-Definable Display 15 B-26 B30 Bus Differential System GE Multilin...
  • Page 427 0 (100 ohm Platinum) 5413 ...Repeated for RTD Input 2 5426 ...Repeated for RTD Input 3 5439 ...Repeated for RTD Input 4 544C ...Repeated for RTD Input 5 545F ...Repeated for RTD Input 6 GE Multilin B30 Bus Differential System B-27...
  • Page 428 ...Repeated for FlexLogic™ Timer 3 5818 ...Repeated for FlexLogic™ Timer 4 5820 ...Repeated for FlexLogic™ Timer 5 5828 ...Repeated for FlexLogic™ Timer 6 5830 ...Repeated for FlexLogic™ Timer 7 5838 ...Repeated for FlexLogic™ Timer 8 B-28 B30 Bus Differential System GE Multilin...
  • Page 429 F300 5A08 Phase Instantaneous Overcurrent 1 Target 0 to 2 F109 0 (Self-reset) 5A09 Phase Instantaneous Overcurrent 1 Events 0 to 1 F102 0 (Disabled) 5A0A Reserved (6 items) 0 to 1 F001 GE Multilin B30 Bus Differential System B-29...
  • Page 430 ...Repeated for Ground Time Overcurrent 2 5D20 ...Repeated for Ground Time Overcurrent 3 5D30 ...Repeated for Ground Time Overcurrent 4 5D40 ...Repeated for Ground Time Overcurrent 5 5D50 ...Repeated for Ground Time Overcurrent 6 B-30 B30 Bus Differential System GE Multilin...
  • Page 431 CT Trouble (Read/Write Setting) (4 modules) 65A0 CT Trouble 1 Function 0 to 1 F102 0 (Disabled) 65A1 CT Trouble 1 Pickup 0.02 to 2 0.001 F001 65A2 CT Trouble 1 Delay 1 to 60 F001 GE Multilin B30 Bus Differential System B-31...
  • Page 432 ...Repeated for DCmA Inputs 23 7528 ...Repeated for DCmA Inputs 24 Disconnect (Breaker) Switch (Read/Write Setting) (24 modules) 7540 Disconnect Switch 1 Function 0 to 1 F102 0 (Disabled) 7541 Disconnect Switch 1 Name F206 “SW 1" B-32 B30 Bus Differential System GE Multilin...
  • Page 433 0 to 1 F102 0 (Disabled) 7743 Reserved (2 items) F001 7745 Repeated for Thermal Protection 2 Ohm Inputs (Read/Write Setting) (2 modules) 7840 Ohm Inputs 1 Function 0 to 1 F102 0 (Disabled) GE Multilin B30 Bus Differential System B-33...
  • Page 434 0 (SRC 1) 7F32 Auxiliary Overvoltage 1 Pickup 0 to 3 0.001 F001 7F33 Auxiliary Overvoltage 1 Pickup Delay 0 to 600 0.01 F001 7F34 Auxiliary Overvoltage 1 Reset Delay 0 to 600 0.01 F001 B-34 B30 Bus Differential System GE Multilin...
  • Page 435 Breaker Failure 1 Use Timer 1 0 to 1 F126 1 (Yes) 860A Breaker Failure 1 Timer 1 Pickup 0 to 65.535 0.001 F001 860B Breaker Failure 1 Use Timer 2 0 to 1 F126 1 (Yes) GE Multilin B30 Bus Differential System B-35...
  • Page 436 ...Repeated for Digital Element 11 8ADC ...Repeated for Digital Element 12 8AF0 ...Repeated for Digital Element 13 8B04 ...Repeated for Digital Element 14 8B18 ...Repeated for Digital Element 15 8B2C ...Repeated for Digital Element 16 B-36 B30 Bus Differential System GE Multilin...
  • Page 437 0 to 65535 F300 8E12 Trip Bus 1 Input 15 0 to 65535 F300 8E13 Trip Bus 1 Input 16 0 to 65535 F300 8E14 Trip Bus 1 Latching 0 to 1 F102 0 (Disabled) GE Multilin B30 Bus Differential System B-37...
  • Page 438 ...Repeated for DCmA Output 12 9348 ...Repeated for DCmA Output 13 934E ...Repeated for DCmA Output 14 9354 ...Repeated for DCmA Output 15 935A ...Repeated for DCmA Output 16 9360 ...Repeated for DCmA Output 17 B-38 B30 Bus Differential System GE Multilin...
  • Page 439 ...Repeated for IEC61850 GOOSE uinteger 7 9925 ...Repeated for IEC61850 GOOSE uinteger 8 9928 ...Repeated for IEC61850 GOOSE uinteger 9 992B ...Repeated for IEC61850 GOOSE uinteger 10 992E ...Repeated for IEC61850 GOOSE uinteger 11 GE Multilin B30 Bus Differential System B-39...
  • Page 440 F300 A289 Selector 1 Bit Mode 0 to 1 F083 0 (Time-out) A28A Selector 1 Bit Acknowledge 0 to 65535 F300 A28B Selector 1 Power Up Mode 0 to 2 F084 0 (Restore) B-40 B30 Bus Differential System GE Multilin...
  • Page 441 ...Repeated for Digital Counter 2 A840 ...Repeated for Digital Counter 3 A860 ...Repeated for Digital Counter 4 A880 ...Repeated for Digital Counter 5 A8A0 ...Repeated for Digital Counter 6 A8C0 ...Repeated for Digital Counter 7 GE Multilin B30 Bus Differential System B-41...
  • Page 442 0 to 65534 F206 (none) AB33 IEC 61850 Logical Node PIOCx Name Prefix (72 items) 0 to 65534 F206 (none) AC0B IEC 61850 Logical Node PTOCx Name Prefix (24 items) 0 to 65534 F206 (none) B-42 B30 Bus Differential System GE Multilin...
  • Page 443 ...Repeated for IEC 61850 GGIO4 Analog Input 2 AF1E ...Repeated for IEC 61850 GGIO4 Analog Input 3 AF25 ...Repeated for IEC 61850 GGIO4 Analog Input 4 AF2C ...Repeated for IEC 61850 GGIO4 Analog Input 5 GE Multilin B30 Bus Differential System B-43...
  • Page 444 IEC 61850 MMXU TotPF Deadband 1 0.001 to 100 0.001 F003 10000 B0C8 IEC 61850 MMXU Hz Deadband 1 0.001 to 100 0.001 F003 10000 B0CA IEC 61850 MMXU PPV.phsAB Deadband 1 0.001 to 100 0.001 F003 10000 B-44 B30 Bus Differential System GE Multilin...
  • Page 445 ...Repeated for Received Analog 21 B23A ...Repeated for Received Analog 22 B23C ...Repeated for Received Analog 23 B23E ...Repeated for Received Analog 24 B240 ...Repeated for Received Analog 25 B242 ...Repeated for Received Analog 26 GE Multilin B30 Bus Differential System B-45...
  • Page 446 BB06 Contact Input 1 Events 0 to 1 F102 0 (Disabled) BB07 Contact Input 1 Debounce Time 0 to 16 F001 BB08 ...Repeated for Contact Input 2 BB10 ...Repeated for Contact Input 3 B-46 B30 Bus Differential System GE Multilin...
  • Page 447 ...Repeated for Contact Input 52 BCA0 ...Repeated for Contact Input 53 BCA8 ...Repeated for Contact Input 54 BCB0 ...Repeated for Contact Input 55 BCB8 ...Repeated for Contact Input 56 BCC0 ...Repeated for Contact Input 57 GE Multilin B30 Bus Differential System B-47...
  • Page 448 ...Repeated for Virtual Input 3 BE54 ...Repeated for Virtual Input 4 BE60 ...Repeated for Virtual Input 5 BE6C ...Repeated for Virtual Input 6 BE78 ...Repeated for Virtual Input 7 BE84 ...Repeated for Virtual Input 8 B-48 B30 Bus Differential System GE Multilin...
  • Page 449 ...Repeated for Virtual Input 57 C0DC ...Repeated for Virtual Input 58 C0E8 ...Repeated for Virtual Input 59 C0F4 ...Repeated for Virtual Input 60 C100 ...Repeated for Virtual Input 61 C10C ...Repeated for Virtual Input 62 GE Multilin B30 Bus Differential System B-49...
  • Page 450 ...Repeated for Virtual Output 44 C290 ...Repeated for Virtual Output 45 C298 ...Repeated for Virtual Output 46 C2A0 ...Repeated for Virtual Output 47 C2A8 ...Repeated for Virtual Output 48 C2B0 ...Repeated for Virtual Output 49 B-50 B30 Bus Differential System GE Multilin...
  • Page 451 Force VFD and LED 0 to 1 F126 0 (No) C432 Test Mode Initiate 0 to 65535 F300 Clear Commands (Read/Write) C433 Clear All Relay Records Command 0 to 1 F126 0 (No) GE Multilin B30 Bus Differential System B-51...
  • Page 452 ...Repeated for Contact Output 39 C614 ...Repeated for Contact Output 40 C620 ...Repeated for Contact Output 41 C62C ...Repeated for Contact Output 42 C638 ...Repeated for Contact Output 43 C644 ...Repeated for Contact Output 44 B-52 B30 Bus Differential System GE Multilin...
  • Page 453 F001 C891 Direct Input 1 Number 0 to 96 F001 C892 Direct Input 1 Default State 0 to 3 F086 0 (Off) C893 Direct Input 1 Events 0 to 1 F102 0 (Disabled) GE Multilin B30 Bus Differential System B-53...
  • Page 454 ...Repeated for Direct Output 16 CA30 ...Repeated for Direct Output 17 CA32 ...Repeated for Direct Output 18 CA34 ...Repeated for Direct Output 19 CA36 ...Repeated for Direct Output 20 CA38 ...Repeated for Direct Output 21 B-54 B30 Bus Differential System GE Multilin...
  • Page 455 ...Repeated for Device 6 CBD8 ...Repeated for Device 7 CBFC ...Repeated for Device 8 CC20 ...Repeated for Device 9 CC44 ...Repeated for Device 10 CC68 ...Repeated for Device 11 CC8C ...Repeated for Device 12 GE Multilin B30 Bus Differential System B-55...
  • Page 456 ...Repeated for Remote Output 5 D234 ...Repeated for Remote Output 6 D238 ...Repeated for Remote Output 7 D23C ...Repeated for Remote Output 8 D240 ...Repeated for Remote Output 9 D244 ...Repeated for Remote Output 10 B-56 B30 Bus Differential System GE Multilin...
  • Page 457 ...Repeated for Remote Output 24 D300 ...Repeated for Remote Output 25 D304 ...Repeated for Remote Output 26 D308 ...Repeated for Remote Output 27 D30C ...Repeated for Remote Output 28 D310 ...Repeated for Remote Output 29 GE Multilin B30 Bus Differential System B-57...
  • Page 458 IEC 61850 GGIO2.CF.SPCSO47.ctlModel Value 0 to 2 F001 D34F IEC 61850 GGIO2.CF.SPCSO48.ctlModel Value 0 to 2 F001 D350 IEC 61850 GGIO2.CF.SPCSO49.ctlModel Value 0 to 2 F001 D351 IEC 61850 GGIO2.CF.SPCSO50.ctlModel Value 0 to 2 F001 B-58 B30 Bus Differential System GE Multilin...
  • Page 459 Reserved (6 items) F205 (none) Setting File Template (Read Only Non-Volatile) ED07 Last Settings Change Date 0 to 4294967295 F050 Settings File Template (Read/Write Setting) ED09 Template Bitmask (750 items) 0 to 65535 F001 GE Multilin B30 Bus Differential System B-59...
  • Page 460: Data Formats

    First 16 bits are Hours/Minutes (HH:MM:xx.xxx). ENUMERATION: DISABLED/ENABLED Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm. 0 = Disabled, 1 = Enabled Minutes: 0 to 59 in steps of 1. Last 16 bits are Seconds (xx:xx:.SS.SSS): 0=00.000s, 1=00.001,...,59999=59.999s). B-60 B30 Bus Differential System GE Multilin...
  • Page 461 19.00 F113 0.84 2.70 5.70 19.50 ENUMERATION: PARITY 0.86 2.80 5.80 20.00 0 = None, 1 = Odd, 2 = Even F122 ENUMERATION: ELEMENT INPUT SIGNAL TYPE 0 = Phasor, 1 = RMS GE Multilin B30 Bus Differential System B-61...
  • Page 462 Digital Counter 1 Phase Undervoltage 3 Digital Counter 2 Auxiliary Overvoltage 1 Digital Counter 3 Auxiliary Overvoltage 2 Digital Counter 4 Auxiliary Overvoltage 3 Digital Counter 5 Neutral Overvoltage 1 Digital Counter 6 B-62 B30 Bus Differential System GE Multilin...
  • Page 463 RTD Input 45 Digital Element 47 RTD Input 46 Digital Element 48 RTD Input 47 Trip Bus 1 RTD Input 48 Trip Bus 2 User-Programmable Pushbutton 1 Trip Bus 3 User-Programmable Pushbutton 2 GE Multilin B30 Bus Differential System B-63...
  • Page 464 Thermal overload protection 2 Voltage Monitor FlexLogic Error Token Equipment Mismatch F126 Process Bus Failure ENUMERATION: NO/YES CHOICE Unit Not Programmed 0 = No, 1 = Yes System Exception Latching Output Discrepancy Ethernet Switch Fail B-64 B30 Bus Differential System GE Multilin...
  • Page 465 ENUMERATION: FORCED CONTACT INPUT STATE 4 = Group 4, 5 = Group 5, 6 = Group 6 0 = Disabled, 1 = Open, 2 = Closed F155 ENUMERATION: REMOTE DEVICE STATE 0 = Offline, 1 = Online GE Multilin B30 Bus Differential System B-65...
  • Page 466 GooseIn 2 GooseIn 3 F167 GooseIn 4 ENUMERATION: SIGNAL SOURCE 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6 B-66 B30 Bus Differential System GE Multilin...
  • Page 467 User-programmable key 15 TEXT32: 32-CHARACTER ASCII TEXT Enter User-programmable key 16 F220 F192 ENUMERATION: PUSHBUTTON MESSAGE PRIORITY ENUMERATION: ETHERNET OPERATION MODE Value Priority 0 = Half-Duplex, 1 = Full-Duplex Disabled Normal High Priority GE Multilin B30 Bus Differential System B-67...
  • Page 468 MMXU3.MX.TotPF.mag.f MMXU1.MX.W.phsA.cVal.mag.f MMXU3.MX.Hz.mag.f MMXU1.MX.W.phsB.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU1.MX.W.phsC.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU1.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU1.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU1.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU1.MX.VA.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU1.MX.VA.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU1.MX.PF.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU1.MX.PF.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU2.MX.TotW.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU2.MX.TotVAr.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU2.MX.TotVA.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU2.MX.TotPF.mag.f MMXU3.MX.A.phsB.cVal.mag.f B-68 B30 Bus Differential System GE Multilin...
  • Page 469 MMXU5.MX.PF.phsB.cVal.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU5.MX.PF.phsC.cVal.mag.f MMXU4.MX.A.phsC.cVal.mag.f MMXU6.MX.TotW.mag.f MMXU4.MX.A.phsC.cVal.ang.f MMXU6.MX.TotVAr.mag.f MMXU4.MX.A.neut.cVal.mag.f MMXU6.MX.TotVA.mag.f MMXU4.MX.A.neut.cVal.ang.f MMXU6.MX.TotPF.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU6.MX.Hz.mag.f MMXU4.MX.W.phsB.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GE Multilin B30 Bus Differential System B-69...
  • Page 470 IEC 61850 GOOSE Rx dataset GGIO4.MX.AnIn17.mag.f item GGIO4.MX.AnIn18.mag.f None GGIO4.MX.AnIn19.mag.f GGIO3.ST.Ind1.q GGIO4.MX.AnIn20.mag.f GGIO3.ST.Ind1.stVal GGIO4.MX.AnIn21.mag.f GGIO3.ST.Ind2.q GGIO4.MX.AnIn22.mag.f GGIO3.ST.Ind2.stVal GGIO4.MX.AnIn23.mag.f ↓ ↓ GGIO4.MX.AnIn24.mag.f GGIO1.ST.Ind64q GGIO4.MX.AnIn25.mag.f GGIO1.ST.Ind64.stVal GGIO4.MX.AnIn26.mag.f GGIO3.MX.AnIn1.mag.f GGIO4.MX.AnIn27.mag.f GGIO3.MX.AnIn2.mag.f GGIO4.MX.AnIn28.mag.f GGIO3.MX.AnIn3.mag.f GGIO4.MX.AnIn29.mag.f GGIO3.MX.AnIn4.mag.f GGIO4.MX.AnIn30.mag.f GGIO3.MX.AnIn5.mag.f GGIO4.MX.AnIn31.mag.f B-70 B30 Bus Differential System GE Multilin...
  • Page 471 Wednesday GGIO3.ST.UIntIn4.stVal Thursday GGIO3.ST.UIntIn5.q Friday GGIO3.ST.UIntIn5.stVal Saturday GGIO3.ST.UIntIn6.q GGIO3.ST.UIntIn6.stVal GGIO3.ST.UIntIn7.q F239 GGIO3.ST.UIntIn7.stVal ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS TIME START DAY INSTANCE GGIO3.ST.UIntIn8.q GGIO3.ST.UIntIn8.stVal Value Instance GGIO3.ST.UIntIn9.q First GGIO3.ST.UIntIn9.stVal Second GGIO3.ST.UIntIn10.q Third GGIO3.ST.UIntIn10.stVal GE Multilin B30 Bus Differential System B-71...
  • Page 472 U1/DC2 U1/DC3 U2/DC1 F247 ENUMERATION: BRICK AC BANK ORIGIN U8/DC3 Value Description None F256 U1/AC1..3 ENUMERATION: BRICK ORIGIN/DESTINATION U1/AC5..7 U2/AC1..3 Value Description U2/AC5..7 None U3/AC1..3 U3/AC5..7 U4/AC1..3 U4/AC5..7 U5/AC1..3 U5/AC5..7 U6/AC1..3 B-72 B30 Bus Differential System GE Multilin...
  • Page 473 IDs. The operate bit for element ID [46] NAND (2 to 16 inputs) X is bit [X mod 16] in register [X/16]. [48] TIMER (1 to 32) GE Multilin B30 Bus Differential System B-73...
  • Page 474 Only certain values can be used as FlexAn- Bitmask Default variation alogs (basically all metering quantities used in protection). F601 ENUMERATION: COM2 PORT USAGE Enumeration COM2 port usage RS485 RRTD GPM-F RRTD & GPM-F B-74 B30 Bus Differential System GE Multilin...
  • Page 475 IEC 61850 report dataset items PIOC12.ST.Op.general None PIOC13.ST.Str.general PDIF1.ST.Str.general PIOC13.ST.Op.general PDIF1.ST.Op.general PIOC14.ST.Str.general PDIF2.ST.Str.general PIOC14.ST.Op.general PDIF2.ST.Op.general PIOC15.ST.Str.general PDIF3.ST.Str.general PIOC15.ST.Op.general PDIF3.ST.Op.general PIOC16.ST.Str.general PDIF4.ST.Str.general PIOC16.ST.Op.general PDIF4.ST.Op.general PIOC17.ST.Str.general PDIS1.ST.Str.general PIOC17.ST.Op.general PDIS1.ST.Op.general PIOC18.ST.Str.general PDIS2.ST.Str.general PIOC18.ST.Op.general PDIS2.ST.Op.general PIOC19.ST.Str.general PDIS3.ST.Str.general PIOC19.ST.Op.general GE Multilin B30 Bus Differential System B-75...
  • Page 476 PIOC64.ST.Op.general PIOC38.ST.Op.general PIOC65.ST.Str.general PIOC39.ST.Str.general PIOC65.ST.Op.general PIOC39.ST.Op.general PIOC66.ST.Str.general PIOC40.ST.Str.general PIOC66.ST.Op.general PIOC40.ST.Op.general PIOC67.ST.Str.general PIOC41.ST.Str.general PIOC67.ST.Op.general PIOC41.ST.Op.general PIOC68.ST.Str.general PIOC42.ST.Str.general PIOC68.ST.Op.general PIOC42.ST.Op.general PIOC69.ST.Str.general PIOC43.ST.Str.general PIOC69.ST.Op.general PIOC43.ST.Op.general PIOC70.ST.Str.general PIOC44.ST.Str.general PIOC70.ST.Op.general PIOC44.ST.Op.general PIOC71.ST.Str.general PIOC45.ST.Str.general PIOC71.ST.Op.general PIOC45.ST.Op.general PIOC72.ST.Str.general PIOC46.ST.Str.general PIOC72.ST.Op.general B-76 B30 Bus Differential System GE Multilin...
  • Page 477 PTUV5.ST.Op.general PTOC19.ST.Op.general PTUV6.ST.Str.general PTOC20.ST.Str.general PTUV6.ST.Op.general PTOC20.ST.Op.general PTUV7.ST.Str.general PTOC21.ST.Str.general PTUV7.ST.Op.general PTOC21.ST.Op.general PTUV8.ST.Str.general PTOC22.ST.Str.general PTUV8.ST.Op.general PTOC22.ST.Op.general PTUV9.ST.Str.general PTOC23.ST.Str.general PTUV9.ST.Op.general PTOC23.ST.Op.general PTUV10.ST.Str.general PTOC24.ST.Str.general PTUV10.ST.Op.general PTOC24.ST.Op.general PTUV11.ST.Str.general PTOV1.ST.Str.general PTUV11.ST.Op.general PTOV1.ST.Op.general PTUV12.ST.Str.general PTOV2.ST.Str.general PTUV12.ST.Op.general PTOV2.ST.Op.general PTUV13.ST.Str.general PTOV3.ST.Str.general PTUV13.ST.Op.general GE Multilin B30 Bus Differential System B-77...
  • Page 478 CSWI11.ST.Pos.stVal RBRF19.ST.OpIn.general CSWI12.ST.Loc.stVal RBRF20.ST.OpEx.general CSWI12.ST.Pos.stVal RBRF20.ST.OpIn.general CSWI13.ST.Loc.stVal RBRF21.ST.OpEx.general CSWI13.ST.Pos.stVal RBRF21.ST.OpIn.general CSWI14.ST.Loc.stVal RBRF22.ST.OpEx.general CSWI14.ST.Pos.stVal RBRF22.ST.OpIn.general CSWI15.ST.Loc.stVal RBRF23.ST.OpEx.general CSWI15.ST.Pos.stVal RBRF23.ST.OpIn.general CSWI16.ST.Loc.stVal RBRF24.ST.OpEx.general CSWI16.ST.Pos.stVal RBRF24.ST.OpIn.general CSWI17.ST.Loc.stVal RFLO1.MX.FltDiskm.mag.f CSWI17.ST.Pos.stVal RFLO2.MX.FltDiskm.mag.f CSWI18.ST.Loc.stVal RFLO3.MX.FltDiskm.mag.f CSWI18.ST.Pos.stVal RFLO4.MX.FltDiskm.mag.f CSWI19.ST.Loc.stVal RFLO5.MX.FltDiskm.mag.f CSWI19.ST.Pos.stVal B-78 B30 Bus Differential System GE Multilin...
  • Page 479 GGIO1.ST.Ind68.stVal GGIO1.ST.Ind16.stVal GGIO1.ST.Ind69.stVal GGIO1.ST.Ind17.stVal GGIO1.ST.Ind70.stVal GGIO1.ST.Ind18.stVal GGIO1.ST.Ind71.stVal GGIO1.ST.Ind19.stVal GGIO1.ST.Ind72.stVal GGIO1.ST.Ind20.stVal GGIO1.ST.Ind73.stVal GGIO1.ST.Ind21.stVal GGIO1.ST.Ind74.stVal GGIO1.ST.Ind22.stVal GGIO1.ST.Ind75.stVal GGIO1.ST.Ind23.stVal GGIO1.ST.Ind76.stVal GGIO1.ST.Ind24.stVal GGIO1.ST.Ind77.stVal GGIO1.ST.Ind25.stVal GGIO1.ST.Ind78.stVal GGIO1.ST.Ind26.stVal GGIO1.ST.Ind79.stVal GGIO1.ST.Ind27.stVal GGIO1.ST.Ind80.stVal GGIO1.ST.Ind28.stVal GGIO1.ST.Ind81.stVal GGIO1.ST.Ind29.stVal GGIO1.ST.Ind82.stVal GGIO1.ST.Ind30.stVal GGIO1.ST.Ind83.stVal GGIO1.ST.Ind31.stVal GGIO1.ST.Ind84.stVal GE Multilin B30 Bus Differential System B-79...
  • Page 480 MMXU2.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind122.stVal MMXU2.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind123.stVal MMXU2.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind124.stVal MMXU2.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind125.stVal MMXU2.MX.PhV.phsA.cVal.ang.f GGIO1.ST.Ind126.stVal MMXU2.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind127.stVal MMXU2.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind128.stVal MMXU2.MX.PhV.phsC.cVal.mag.f MMXU1.MX.TotW.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU1.MX.TotVAr.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU1.MX.TotVA.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU1.MX.TotPF.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU1.MX.Hz.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU1.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU1.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.A.phsC.cVal.ang.f MMXU1.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU1.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.A.neut.cVal.ang.f B-80 B30 Bus Differential System GE Multilin...
  • Page 481 MMXU5.MX.TotPF.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU3.MX.W.phsB.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU4.MX.TotVA.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU4.MX.TotPF.mag.f MMXU5.MX.A.phsB.cVal.mag.f GE Multilin B30 Bus Differential System B-81...
  • Page 482 XSWI2.ST.Pos.stVal MMXU6.MX.A.phsB.cVal.ang.f XSWI3.ST.Loc.stVal MMXU6.MX.A.phsC.cVal.mag.f XSWI3.ST.Pos.stVal MMXU6.MX.A.phsC.cVal.ang.f XSWI4.ST.Loc.stVal MMXU6.MX.A.neut.cVal.mag.f XSWI4.ST.Pos.stVal MMXU6.MX.A.neut.cVal.ang.f XSWI5.ST.Loc.stVal MMXU6.MX.W.phsA.cVal.mag.f XSWI5.ST.Pos.stVal MMXU6.MX.W.phsB.cVal.mag.f XSWI6.ST.Loc.stVal MMXU6.MX.W.phsC.cVal.mag.f XSWI6.ST.Pos.stVal MMXU6.MX.VAr.phsA.cVal.mag.f XSWI7.ST.Loc.stVal MMXU6.MX.VAr.phsB.cVal.mag.f XSWI7.ST.Pos.stVal MMXU6.MX.VAr.phsC.cVal.mag.f XSWI8.ST.Loc.stVal MMXU6.MX.VA.phsA.cVal.mag.f XSWI8.ST.Pos.stVal MMXU6.MX.VA.phsB.cVal.mag.f XSWI9.ST.Loc.stVal MMXU6.MX.VA.phsC.cVal.mag.f XSWI9.ST.Pos.stVal MMXU6.MX.PF.phsA.cVal.mag.f XSWI10.ST.Loc.stVal MMXU6.MX.PF.phsB.cVal.mag.f XSWI10.ST.Pos.stVal B-82 B30 Bus Differential System GE Multilin...
  • Page 483 GGIO1.ST.Ind24.q GGIO1.ST.Ind24.stVal GGIO1.ST.Ind25.q F616 GGIO1.ST.Ind25.stVal ENUMERATION: IEC 61850 GOOSE DATASET ITEMS GGIO1.ST.Ind26.q Enumeration GOOSE dataset items GGIO1.ST.Ind26.stVal None GGIO1.ST.Ind27.q GGIO1.ST.Ind1.q GGIO1.ST.Ind27.stVal GGIO1.ST.Ind1.stVal GGIO1.ST.Ind28.q GGIO1.ST.Ind2.q GGIO1.ST.Ind28.stVal GGIO1.ST.Ind2.stVal GGIO1.ST.Ind29.q GGIO1.ST.Ind3.q GGIO1.ST.Ind29.stVal GGIO1.ST.Ind3.stVal GGIO1.ST.Ind30.q GGIO1.ST.Ind4.q GGIO1.ST.Ind30.stVal GE Multilin B30 Bus Differential System B-83...
  • Page 484 GGIO1.ST.Ind75.stVal GGIO1.ST.Ind49.stVal GGIO1.ST.Ind76.q GGIO1.ST.Ind50.q GGIO1.ST.Ind76.stVal GGIO1.ST.Ind50.stVal GGIO1.ST.Ind77.q GGIO1.ST.Ind51.q GGIO1.ST.Ind77.stVal GGIO1.ST.Ind51.stVal GGIO1.ST.Ind78.q GGIO1.ST.Ind52.q GGIO1.ST.Ind78.stVal GGIO1.ST.Ind52.stVal GGIO1.ST.Ind79.q GGIO1.ST.Ind53.q GGIO1.ST.Ind79.stVal GGIO1.ST.Ind53.stVal GGIO1.ST.Ind80.q GGIO1.ST.Ind54.q GGIO1.ST.Ind80.stVal GGIO1.ST.Ind54.stVal GGIO1.ST.Ind81.q GGIO1.ST.Ind55.q GGIO1.ST.Ind81.stVal GGIO1.ST.Ind55.stVal GGIO1.ST.Ind82.q GGIO1.ST.Ind56.q GGIO1.ST.Ind82.stVal GGIO1.ST.Ind56.stVal GGIO1.ST.Ind83.q GGIO1.ST.Ind57.q GGIO1.ST.Ind83.stVal B-84 B30 Bus Differential System GE Multilin...
  • Page 485 GGIO1.ST.Ind128.stVal GGIO1.ST.Ind102.stVal MMXU1.MX.TotW.mag.f GGIO1.ST.Ind103.q MMXU1.MX.TotVAr.mag.f GGIO1.ST.Ind103.stVal MMXU1.MX.TotVA.mag.f GGIO1.ST.Ind104.q MMXU1.MX.TotPF.mag.f GGIO1.ST.Ind104.stVal MMXU1.MX.Hz.mag.f GGIO1.ST.Ind105.q MMXU1.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind105.stVal MMXU1.MX.PPV.phsAB.cVal.ang.f GGIO1.ST.Ind106.q MMXU1.MX.PPV.phsBC.cVal.mag.f GGIO1.ST.Ind106.stVal MMXU1.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind107.q MMXU1.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind107.stVal MMXU1.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind108.q MMXU1.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind108.stVal MMXU1.MX.PhV.phsA.cVal.ang.f GGIO1.ST.Ind109.q MMXU1.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind109.stVal MMXU1.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind110.q MMXU1.MX.PhV.phsC.cVal.mag.f GE Multilin B30 Bus Differential System B-85...
  • Page 486 MMXU3.MX.VA.phsA.cVal.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU2.MX.A.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU4.MX.TotVA.mag.f MMXU2.MX.A.neut.cVal.ang.f MMXU4.MX.TotPF.mag.f MMXU2.MX.W.phsA.cVal.mag.f MMXU4.MX.Hz.mag.f MMXU2.MX.W.phsB.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.VAr.phsA.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.VAr.phsB.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.VAr.phsC.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.VA.phsA.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.ang.f B-86 B30 Bus Differential System GE Multilin...
  • Page 487 MMXU6.MX.W.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU6.MX.W.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU6.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU6.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU6.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU6.MX.VA.phsA.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU6.MX.VA.phsB.cVal.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU6.MX.VA.phsC.cVal.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU6.MX.PF.phsA.cVal.mag.f MMXU5.MX.A.phsB.cVal.mag.f MMXU6.MX.PF.phsB.cVal.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU6.MX.PF.phsC.cVal.mag.f MMXU5.MX.A.phsC.cVal.mag.f GGIO4.MX.AnIn1.mag.f MMXU5.MX.A.phsC.cVal.ang.f GGIO4.MX.AnIn2.mag.f MMXU5.MX.A.neut.cVal.mag.f GGIO4.MX.AnIn3.mag.f MMXU5.MX.A.neut.cVal.ang.f GGIO4.MX.AnIn4.mag.f MMXU5.MX.W.phsA.cVal.mag.f GGIO4.MX.AnIn5.mag.f MMXU5.MX.W.phsB.cVal.mag.f GGIO4.MX.AnIn6.mag.f GE Multilin B30 Bus Differential System B-87...
  • Page 488 PIOC2.ST.Op.general GGIO5.ST.UIntIn6.stVal PIOC3.ST.Str.general GGIO5.ST.UIntIn7.q PIOC3.ST.Op.general GGIO5.ST.UIntIn7.stVal PIOC4.ST.Str.general GGIO5.ST.UIntIn8.q PIOC4.ST.Op.general GGIO5.ST.UIntIn8.stVal PIOC5.ST.Str.general GGIO5.ST.UIntIn9.q PIOC5.ST.Op.general GGIO5.ST.UIntIn9.stVal PIOC6.ST.Str.general GGIO5.ST.UIntIn10.q PIOC6.ST.Op.general GGIO5.ST.UIntIn10.stVal PIOC7.ST.Str.general GGIO5.ST.UIntIn11.q PIOC7.ST.Op.general GGIO5.ST.UIntIn11.stVal PIOC8.ST.Str.general GGIO5.ST.UIntIn12.q PIOC8.ST.Op.general GGIO5.ST.UIntIn12.stVal PIOC9.ST.Str.general GGIO5.ST.UIntIn13.q PIOC9.ST.Op.general GGIO5.ST.UIntIn13.stVal PIOC10.ST.Str.general GGIO5.ST.UIntIn14.q PIOC10.ST.Op.general B-88 B30 Bus Differential System GE Multilin...
  • Page 489 PIOC55.ST.Op.general PIOC29.ST.Op.general PIOC56.ST.Str.general PIOC30.ST.Str.general PIOC56.ST.Op.general PIOC30.ST.Op.general PIOC57.ST.Str.general PIOC31.ST.Str.general PIOC57.ST.Op.general PIOC31.ST.Op.general PIOC58.ST.Str.general PIOC32.ST.Str.general PIOC58.ST.Op.general PIOC32.ST.Op.general PIOC59.ST.Str.general PIOC33.ST.Str.general PIOC59.ST.Op.general PIOC33.ST.Op.general PIOC60.ST.Str.general PIOC34.ST.Str.general PIOC60.ST.Op.general PIOC34.ST.Op.general PIOC61.ST.Str.general PIOC35.ST.Str.general PIOC61.ST.Op.general PIOC35.ST.Op.general PIOC62.ST.Str.general PIOC36.ST.Str.general PIOC62.ST.Op.general PIOC36.ST.Op.general PIOC63.ST.Str.general PIOC37.ST.Str.general PIOC63.ST.Op.general GE Multilin B30 Bus Differential System B-89...
  • Page 490 PTRC2.ST.Op.general PTOC10.ST.Op.general PTRC3.ST.Tr.general PTOC11.ST.Str.general PTRC3.ST.Op.general PTOC11.ST.Op.general PTRC4.ST.Tr.general PTOC12.ST.Str.general PTRC4.ST.Op.general PTOC12.ST.Op.general PTRC5.ST.Tr.general PTOC13.ST.Str.general PTRC5.ST.Op.general PTOC13.ST.Op.general PTRC6.ST.Tr.general PTOC14.ST.Str.general PTRC6.ST.Op.general PTOC14.ST.Op.general PTUV1.ST.Str.general PTOC15.ST.Str.general PTUV1.ST.Op.general PTOC15.ST.Op.general PTUV2.ST.Str.general PTOC16.ST.Str.general PTUV2.ST.Op.general PTOC16.ST.Op.general PTUV3.ST.Str.general PTOC17.ST.Str.general PTUV3.ST.Op.general PTOC17.ST.Op.general PTUV4.ST.Str.general PTOC18.ST.Str.general PTUV4.ST.Op.general B-90 B30 Bus Differential System GE Multilin...
  • Page 491 CSWI2.ST.Pos.stVal RBRF10.ST.OpIn.general CSWI3.ST.Loc.stVal RBRF11.ST.OpEx.general CSWI3.ST.Pos.stVal RBRF11.ST.OpIn.general CSWI4.ST.Loc.stVal RBRF12.ST.OpEx.general CSWI4.ST.Pos.stVal RBRF12.ST.OpIn.general CSWI5.ST.Loc.stVal RBRF13.ST.OpEx.general CSWI5.ST.Pos.stVal RBRF13.ST.OpIn.general CSWI6.ST.Loc.stVal RBRF14.ST.OpEx.general CSWI6.ST.Pos.stVal RBRF14.ST.OpIn.general CSWI7.ST.Loc.stVal RBRF15.ST.OpEx.general CSWI7.ST.Pos.stVal RBRF15.ST.OpIn.general CSWI8.ST.Loc.stVal RBRF16.ST.OpEx.general CSWI8.ST.Pos.stVal RBRF16.ST.OpIn.general CSWI9.ST.Loc.stVal RBRF17.ST.OpEx.general CSWI9.ST.Pos.stVal RBRF17.ST.OpIn.general CSWI10.ST.Loc.stVal RBRF18.ST.OpEx.general CSWI10.ST.Pos.stVal GE Multilin B30 Bus Differential System B-91...
  • Page 492 CSWI30.ST.Loc.stVal 1000 XCBR2.ST.Pos.stVal CSWI30.ST.Pos.stVal 1001 XCBR3.ST.Loc.stVal XSWI1.ST.Loc.stVal 1002 XCBR3.ST.Pos.stVal XSWI1.ST.Pos.stVal 1003 XCBR4.ST.Loc.stVal XSWI2.ST.Loc.stVal 1004 XCBR4.ST.Pos.stVal XSWI2.ST.Pos.stVal 1005 XCBR5.ST.Loc.stVal XSWI3.ST.Loc.stVal 1006 XCBR5.ST.Pos.stVal XSWI3.ST.Pos.stVal 1007 XCBR6.ST.Loc.stVal XSWI4.ST.Loc.stVal 1008 XCBR6.ST.Pos.stVal XSWI4.ST.Pos.stVal XSWI5.ST.Loc.stVal XSWI5.ST.Pos.stVal XSWI6.ST.Loc.stVal XSWI6.ST.Pos.stVal XSWI7.ST.Loc.stVal B-92 B30 Bus Differential System GE Multilin...
  • Page 493: Iec 61850

    System Specification Description (SSD) file. The entire substation con- figuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individ- ual ICD files and the SSD file. GE Multilin B30 Bus Differential System...
  • Page 494: File Transfer By Iec 61850

    With the Copy option active, select a file to transfer and click the Go button. The file is copied and displays in the Local list on the left side of the window. Repeat the process to transfer any other files. Figure 0–1: FILE TRANSFER BY IEC 61850 B30 Bus Differential System GE Multilin...
  • Page 495: Server Data Organization

    GGIO4 (4 to 32) and the choice of the FlexAnalog™ values that determine the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available from GGIO4 in order to obtain the analog values provided by GGIO4. GE Multilin B30 Bus Differential System...
  • Page 496: Mmxu: Analog Measured Values

    The following list describes the protection elements for all UR-series relays. The B30 relay will contain a subset of protec- tion elements from this list. • PDIF: bus differential, transformer instantaneous differential, transformer percent differential, current differential B30 Bus Differential System GE Multilin...
  • Page 497 IEC 61850 control model. • XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control with normal security is the only supported IEC 61850 control model. GE Multilin B30 Bus Differential System...
  • Page 498: Server Features And Configuration

    B30. This attribute is programmed through the setting and its LOCATION default value is “Location”. This value should be changed to describe the actual physical location of the B30. B30 Bus Differential System GE Multilin...
  • Page 499: Logical Node Name Prefixes

    The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a B30 relay with an MMS browser, such as the “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc. GE Multilin B30 Bus Differential System...
  • Page 500: Generic Substation Event Services: Gsse And Goose

    The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the B30. The B30 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data transfer between devices. B30 Bus Differential System GE Multilin...
  • Page 501 Configure the GOOSE service settings by making the following changes in the  PRODUCT SETUP COMMUNICATION      IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGU- settings menu: RABLE GOOSE 1 GE Multilin B30 Bus Differential System...
  • Page 502: C.4.5 Ethernet Mac Address For Gsse/Goose

    (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as the ‘source’ address of the frame. Each Ethernet frame also contains a destination address. The destination address can be different for each Ethernet frame depending on the intended destination of the frame. C-10 B30 Bus Differential System GE Multilin...
  • Page 503: C.4.6 Gsse Id And Goose Id Settings

    DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block. These strings are automatically populated and interpreted by the B30; no settings are required. GE Multilin B30 Bus Differential System...
  • Page 504: C.5.1 Overview

    An ICD file is generated for the B30 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 505: Configuring Iec 61850 Settings

    It can also import a system SCL file (SCD) to set communication configuration parame- ters (that is, required addresses, reception GOOSE datasets, IDs of incoming GOOSE datasets, etc.) for the IED. The IED configurator functionality is implemented in the GE Multilin EnerVista UR Setup software. C.5.2 CONFIGURING IEC 61850 SETTINGS Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED.
  • Page 506: About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 507 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. GE Multilin B30 Bus Differential System C-15...
  • Page 508 RptEnabled Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure C–4: ICD FILE STRUCTURE, IED NODE C-16 B30 Bus Differential System GE Multilin...
  • Page 509 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure C–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE GE Multilin B30 Bus Differential System C-17...
  • Page 510: Creating An Icd File With Enervista Ur Setup

    C.5.5 ABOUT SCD FILES System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI version 4.6 or above and ASE Visual SCL Beta 0.12).
  • Page 511 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE GE Multilin B30 Bus Differential System C-19...
  • Page 512 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. C-20 B30 Bus Differential System GE Multilin...
  • Page 513: Importing An Scd File With Enervista Ur Setup

    The following procedure describes how to update the B30 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item. Select the saved SCD file and click Open. GE Multilin B30 Bus Differential System C-21...
  • Page 514 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 515: Acsi Conformance

    Setting group control REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion GE Multilin B30 Bus Differential System C-23...
  • Page 516: Acsi Services Conformance Statement

    SERVER/ UR FAMILY PUBLISHER SERVER (CLAUSE 6) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 7) Associate Abort Release LOGICAL DEVICE (CLAUSE 8) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 9) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 10) GetDataValues SetDataValues GetDataDirectory GetDataDefinition C-24 B30 Bus Differential System GE Multilin...
  • Page 517 (qchg) S27-3 data-update (dupd) GetURCBValues SetURCBValues LOGGING (CLAUSE 14) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4) GOOSE-CONTROL-BLOCK SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK SendGSSEMessage GetReference GE Multilin B30 Bus Differential System C-25...
  • Page 518 (QueryLogByTime or QueryLogAfter) NOTE c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) C-26 B30 Bus Differential System GE Multilin...
  • Page 519: C.7.1 Logical Nodes Table

    RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing GE Multilin B30 Bus Differential System C-27...
  • Page 520 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer C-28 B30 Bus Differential System GE Multilin...
  • Page 521 ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component GE Multilin B30 Bus Differential System C-29...
  • Page 522 C.7 LOGICAL NODES APPENDIX C C-30 B30 Bus Differential System GE Multilin...
  • Page 523: Interoperability Document

    Balanced Transmission Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin B30 Bus Differential System...
  • Page 524  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 B30 Bus Differential System GE Multilin...
  • Page 525  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin B30 Bus Differential System...
  • Page 526 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 B30 Bus Differential System GE Multilin...
  • Page 527 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin B30 Bus Differential System...
  • Page 528 <120> F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure B30 Bus Differential System GE Multilin...
  • Page 529  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin B30 Bus Differential System...
  • Page 530 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs B30 Bus Differential System GE Multilin...
  • Page 531: Iec 60870-5-104 Points

    D.1.2 IEC 60870-5-104 POINTS The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin B30 Bus Differential System...
  • Page 532 D.1 IEC 60870-5-104 APPENDIX D D-10 B30 Bus Differential System GE Multilin...
  • Page 533: Device Profile Document

    2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin B30 Bus Differential System...
  • Page 534 FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. B30 Bus Differential System GE Multilin...
  • Page 535  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin B30 Bus Differential System...
  • Page 536: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B30 is not restarted, but the DNP process is restarted. B30 Bus Differential System GE Multilin...
  • Page 537 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B30 is not restarted, but the DNP process is restarted. GE Multilin B30 Bus Differential System...
  • Page 538 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B30 is not restarted, but the DNP process is restarted. B30 Bus Differential System GE Multilin...
  • Page 539 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B30 is not restarted, but the DNP process is restarted. GE Multilin B30 Bus Differential System...
  • Page 540: Dnp Point Lists

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 B30 Bus Differential System GE Multilin...
  • Page 541: Binary And Control Relay Output

    Virtual Input 27 Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin B30 Bus Differential System...
  • Page 542: Counters

    A counter freeze command has no meaning for counters 8 and 9. B30 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values. E-10 B30 Bus Differential System GE Multilin...
  • Page 543: Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin B30 Bus Differential System E-11...
  • Page 544 E.2 DNP POINT LISTS APPENDIX E E-12 B30 Bus Differential System GE Multilin...
  • Page 545: Change Notes

    29 May 2009 09-0938 1601-0109-U2 5.7x 30 September 2009 09-1165 1601-0109-V1 5.8x 28 May 2010 09-1457 1601-0109-V2 5.8x 04 January 2011 11-2237 1601-0109-W1 5.9x 12 January 2011 11-2227 1601-0109-W2 5.9x 31 August 2015 12-0025 GE Multilin B30 Bus Differential System...
  • Page 546: Changes To The B30 Manual

    Updated USER-DEFINABLE DISPLAYS section 5-68 5-70 Update Updated BREAKERS section 5-72 5-74 Update Updated DISCONNECT SWITCHES section 5-85 5-87 Update Updated FLEXLOGIC™ OPERANDS table 5-157 Added THERMAL OVERLOAD PROTECTION section 5-161 5-167 Update Updated REMOTE INPUTS section B30 Bus Differential System GE Multilin...
  • Page 547 Updated ENVIRONMENTAL specifications section 2-16 2-17 Update Updated TYPE TESTS specifications section 2-17 2-18 Update Updated APPROVALS specifications section 4-14 4-14 Update Updated LED INDICATORS section 5-20 5-20 Update Updated IEC 61850 PROTOCOL section GE Multilin B30 Bus Differential System...
  • Page 548 Table F–8: MAJOR UPDATES FOR B30 MANUAL REVISION T1 (Sheet 1 of 2) PAGE PAGE CHANGE DESCRIPTION (S3) (T1) Title Title Update Manual part number to 1601-0109-T1 Update Updated ORDERING section 3-13 Added PROCESS BUS MODULES section B30 Bus Differential System GE Multilin...
  • Page 549 DESCRIPTION (R3) (S1) Title Title Update Manual part number to 1601-0109-S1 Update Updated ORDERING section Update Updated REPLACEMENT MODULES section 2-12 2-12 Update Updated OUTPUTS specifications section 2-13 2-13 Update Updated COMMUNICATIONS specifications section GE Multilin B30 Bus Differential System...
  • Page 550 4-12 4-19 Update Updated ENTERING INITIAL PASSWORDS section Update Updated PASSWORD SECURITY section 5-30 5-32 Update Updated USER-PROGRAMMABLE LEDS section 5-35 5-36 Update Updated CONTROL PUSHBUTTONS section 5-36 5-37 Update Updated USER-PROGRAMMABLE PUSHBUTTONS section B30 Bus Differential System GE Multilin...
  • Page 551 Updated REMOTE INPUTS section to reflect correct values Update Updated MODBUS MEMORY MAP section Update Updated Appendix C: IEC 61850 COMMUNICATIONS Update Updated DNP V3.00 DEVICE PROFILE section Update Updated DNP IMPLEMENTATION TABLE section Update Updated BINARY INPUT POINTS section GE Multilin B30 Bus Differential System...
  • Page 552 PAGE PAGE CHANGE DESCRIPTION (M1) (M2) Title Title Update Manual part number to 1601-0109-M2 3-28 3-28 Update Updated RS422 INTERFACE section 4-13 4-13 Update Updated INVALID PASSWORD ENTRY sub-section Update Updated PASSWORD SECURITY section B30 Bus Differential System GE Multilin...
  • Page 553 Update Updated SETTING GROUPS section 5-88 5-98 Update Updated SELECTOR SWITCH section 5-106 5-117 Update Updated REMOTE INPUTS section 5-108 5-119 Update Updated DIRECT INPUTS/OUTPUTS section Update Updated MODBUS MEMORY MAP for revision 4.8x GE Multilin B30 Bus Differential System...
  • Page 554 DESCRIPTION (K1) (L1) Update Updated IEC 60870-5-104 POINT LIST sub-section Update Updated BINARY INPUT POINTS section E-13 Update Updated BINARY AND CONTROL RELAY OUTPUT POINTS section E-15 E-11 Update Updated ANALOG INPUTS section F-10 B30 Bus Differential System GE Multilin...
  • Page 555: Abbreviations

    FxE ....FlexElement™ AMP ....Ampere FWD....Forward ANG ....Angle ANSI....American National Standards Institute G .....Generator AR ....Automatic Reclosure GE....General Electric ASDU ..... Application-layer Service Data Unit GND....Ground ASYM ..... Asymmetry GNTR....Generator AUTO ..... Automatic GOOSE...General Object Oriented Substation Event AUX....
  • Page 556 ROCOF ..Rate of Change of Frequency ROD ....Remote Open Detector RST ....Reset RSTR ..... Restrained RTD ....Resistance Temperature Detector RTU ....Remote Terminal Unit RX (Rx) ..Receive, Receiver s ..... second S..... Sensitive F-12 B30 Bus Differential System GE Multilin...
  • Page 557 VTLOS ... Voltage Transformer Loss Of Signal WDG ....Winding WH ....Watt-hour w/ opt....With Option WRT ....With Respect To X..... Reactance XDUCER ..Transducer XFMR ..... Transformer Z ..... Impedance, Zone GE Multilin B30 Bus Differential System F-13...
  • Page 558: Warranty

    F.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at https://www.gedigitalenergy.com/multilin/warranty.htm...
  • Page 559: Index

    ............7-2 control of 2 breakers ............4-24 settings ................. 5-41 description ..............4-23 COMMANDS MENU ............7-1 dual breaker logic ..........5-76, 5-77 FlexLogic™ operands ............ 5-92 Modbus registers ............B-26 settings ................. 5-74 GE Multilin B30 Bus Differential System...
  • Page 560 CT RATIO MATCHING ............9-3 DIRECT DEVICES CT TROUBLE actual values ..............6-7 FlexLogic operands ............5-92 Modbus registers ............B-17 logic ................5-161 settings ................ 5-175 Modbus registers ............B-31 settings ............... 5-160 specifications..............2-10 B30 Bus Differential System GE Multilin...
  • Page 561 ..............6-15 overview ................. 4-1 direction ..............5-106 requirements ..............1-5 FlexLogic™ operands ............. 5-93 hysteresis ..............5-106 pickup ................. 5-106 scheme logic ............... 5-105 settings ..........5-104, 5-105, 5-107 specifications ..............2-11 GE Multilin B30 Bus Differential System...
  • Page 562 INSPECTION CHECKLIST .......... 2-xi, 1-1 G.703 ............ 3-32, 3-33, 3-34, 3-37 INSTALLATION G.703 WIRE SIZE ............3-32 communications .............3-25 GE TYPE IAC CURVES ..........5-118 CT inputs .............. 3-12, 3-13 GROUND CURRENT METERING ........6-13 RS485 ................3-26 GROUND IOC settings ................5-67 FlexLogic™...
  • Page 563 MODEL INFORMATION ........... 6-19 specifications ..............2-12 MODIFICATION FILE NUMBER ........6-19 via COMTRADE .............. B-7 MODULE FAILURE ERROR ..........7-5 via EnerVista software ............. 4-2 OSI NETWORK ADDRESS ..........5-16 OUT OF SERVICE ............5-9, 8-2 GE Multilin B30 Bus Differential System...
  • Page 564 2-10 REVISION HISTORY ............F-1 PHASE UNDERVOLTAGE RF IMMUNITY ..............2-17 FlexLogic™ operands ............ 5-94 RFI, CONDUCTED ............2-17 logic ................5-139 RMS CURRENT ..............2-12 Modbus registers ............B-32 RMS VOLTAGE ..............2-12 settings ............... 5-138 specifications..............2-10 B30 Bus Differential System GE Multilin...
  • Page 565 SETTINGS, CHANGING ........... 4-26 specifications ..............2-11 SIGNAL SOURCES TIME .................. 7-2 description ..............5-5 TIME OVERCURRENT metering ................ 6-13 see PHASE, NEUTRAL, and GROUND TOC entries SIGNAL TYPES ..............1-3 TIMERS ................. 5-103 GE Multilin B30 Bus Differential System...
  • Page 566 ..............5-14, 7-2 Modbus registers ............B-15 settings ................. 5-41 ZERO SEQUENCE CORE BALANCE .........3-13 USER-PROGRAMMABLE LEDs ZONING ................10-3 defaults ................. 4-18 description............4-16, 4-17 Modbus registers ............B-24 settings ................. 5-47 specifications ..............2-11 viii B30 Bus Differential System GE Multilin...

Table of Contents