4 SETPOINTS
Õ×
PATH: SETPOINTS
S9 VOLTAGE ELEMENTS
n FREQUENCY
n [ENTER] for more
Once the frequency of the phase AN or AB voltage (depending on wye or delta connection) is out of range of the overfre-
quency and underfrequency setpoints, a trip or alarm will occur.
This feature may be useful for load shedding applications on large motors. It could also be used to load shed an entire
feeder if the trip was assigned to an upstream breaker.
GE Multilin
Courtesy of NationalSwitchgear.com
Õ×

FREQUENCY

ð
FREQUENCY
ENTER
ESCAPE
ALARM: Off
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
OVER FREQUENCY
ESCAPE
MESSAGE
ALARM LEVEL: 60.50 Hz
UNDER FREQUENCY
ESCAPE
ALARM LEVEL: 59.50 Hz
MESSAGE
FREQUENCY ALARM
ESCAPE
DELAY: 1.0 s
MESSAGE
FREQUENCY ALARM
ESCAPE
EVENTS: Off
MESSAGE
FREQUENCY
ESCAPE
TRIP: Off
MESSAGE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
OVER FREQUENCY
ESCAPE
TRIP LEVEL: 60.50 Hz
MESSAGE
UNDER FREQUENCY
ESCAPE
MESSAGE
TRIP LEVEL: 59.50 Hz
FREQUENCY
ESCAPE
TRIP DELAY: 1.0 s
MESSAGE
469 Motor Management Relay
4.10 S9 VOLTAGE ELEMENTS
4.10.4 FREQUENCY
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3,
Auxiliary3
Range: 25.01 to 70.00 Hz in steps of 0.01
Range: 20.00 to 60.00 Hz in steps of 0.01
Range: 0.0 to 60.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3,
Trip & Auxiliary3
Range: 25.01 to 70.00 Hz in steps of 0.01
Range: 20.00 to 60.00 Hz in steps of 0.01
Range: 0.0 to 60.0 s in steps of 0.1
4
4-59