Parameters
Parameters referred to
Pr. 3
Pr. 52
Pr. 54
Pr. 158
5.8.6

Output terminal function selection

Use the following parameters to change the functions of the open collector output terminals, relay
output terminals, or virtual terminals of CC-Link IE Field Network Basic (for FR-F800-E).
Pr.
190
M400
191
M401
192
M402
193
M403
194
M404
195
M405
196
M406
313
M410
314
M411
315
M412
The initial value is for standard models.
The initial value is for separated converter types.
The setting is available for FR-F800-E only.
The parameter is used when the CC-Link IE Field Network Basic is selected (for FR-F800-E).
(Refer to page 5-618.)
Pr.
289
M431
FR-F800
Base frequency
Operation panel main monitor selection
FM/CA terminal function selection
AM terminal function selection
Name
RUN terminal function
selection
SU terminal function
selection
Open
IPF terminal function
collector
selection
output
terminal
OL terminal function
selection
FU terminal function
selection
ABC1 terminal function
selection
Relay
output
terminal
ABC2 terminal function
selection
DO0 output selection
Option
DO1 output selection
terminal
DO2 output selection
Initial
Name
value
Inverter output terminal
filter
(M) Monitor display and monitor output signal
Initial
Initial set signal
value
0
RUN (Inverter running)
1
SU (Up to frequency)
IPF (Instantaneous
2
power failure/
9999
undervoltage)
3
OL (Overload warning)
FU (Output frequency
4
detection)
99
ALM (Fault)
9999
No function
9999
9999
No function
9999
Setting range
Description
Set the time delay for the output terminal
5 to 50 ms
response.
9999
9999
No output terminal filter.
=>
page 5-537
=>
page 5-198
=>
page 5-211
=>
page 5-211
Setting range
0 to 5, 7, 8, 10 to 19, 25, 26, 35,
39 to 42, 45 to 54, 57, 64 to 68,
70 to 80, 82, 85, 90 to 96, 98 to 105,
107, 108, 110 to 116, 125, 126, 135,
139 to 142, 145 to 154, 157,
164 to 168, 170 to 180, 182, 185,
190 to 196, 198 to 208, 211 to 213,
215, 217 to 220, 226, 228 to 230,
242 , 300 to 308, 311 to 313, 315,
317 to 320, 326, 328 to 330, 342
0 to 5, 7, 8, 10 to 19, 25, 26, 35,
39 to 42, 45 to 54, 57, 64 to 68,
70 to 80, 82, 85, 90, 91, 94 to 96,
98 to 105, 107, 108, 110 to 116, 125,
126, 135, 139 to 142, 145 to 154,
157, 164 to 168, 170 to 180, 182,
185, 190, 191, 194 to 196,
198 to 208, 211 to 213, 215,
217 to 220, 226, 228 to 230, 242 ,
300 to 308, 311 to 313, 315,
317 to 320, 326, 328 to 330, 342
0 to 5, 7, 8, 10 to 19, 25, 26, 35,
39 to 42, 45 to 54, 57, 64 to 66, 68,
70 to 80, 85 to 96, 98 to 105, 107,
108, 110 to 116, 125, 126, 135,
139 to 142, 145 to 154, 157,
164 to 166, 168, 170 to 180,
185 to 196, 198 to 208, 211 to 213,
215, 217 to 220, 226, 228 to 230,
242, 300 to 308, 311 to 313, 315,
317 to 320, 326, 328 to 330, 342,
9999