Protective functions
6.5.2
Warning
Output is not shut off when a protective function activates.
Operation panel
indication
Name
Description
Check point
Corrective action
FR-F800
OL
Stall prevention (overcurrent)
When the output current of the inverter increases, the stall prevention (overcurrent)
function activates.
The following section explains about the stall prevention (overcurrent) function.
When the output current of the inverter exceeds the stall prevention
level (Pr. 22 "Stall prevention operation level", etc.), this function stops
During
the increase in frequency until the overload current decreases to
acceleration
prevent the inverter from resulting in overcurrent trip. When the
overload current has reduced below stall prevention operation level,
this function increases the frequency again.
When the output current of the inverter exceeds the stall prevention
level (Pr. 22 "Stall prevention operation level", etc.), this function reduces
During
frequency until the overload current decreases to prevent the inverter
constant-speed
from resulting in overcurrent trip. When the overload current has
operation
reduced below stall prevention operation level, this function increases
the frequency up to the set value.
When the output current of the inverter exceeds the stall prevention
level (Pr. 22 "Stall prevention operation level", etc.), this function stops
During
the decrease in frequency until the overload current decreases to
deceleration
prevent the inverter from resulting in overcurrent trip. When the
overload current has decreased below stall prevention operation level,
this function decreases the frequency again.
Check that the Pr. 0 "Torque boost" setting is not too large.
The Pr. 7 "Acceleration time" and Pr. 8 "Deceleration time" settings may be too short.
Check that the load is not too heavy.
Check for any failures in peripheral devices.
Check that the Pr. 13 "Starting frequency" is not too large.
Check that Pr. 22 "Stall prevention operation level" is appropriate.
Gradually increase or decrease the Pr. 0 setting by 1% at a time and check the motor
status.(Refer to page 5-535.)
Set a larger value in Pr. 7 "Acceleration time" and Pr. 8 "Deceleration time".
(Refer to page 5-102.)
Reduce the load.
Try Advanced magnetic flux vector control.
Change the Pr. 14 "Load pattern selection" setting.
The stall prevention operation current can be set in Pr. 22 "Stall prevention operation level".
The acceleration/deceleration time may change. Increase the stall prevention operation
level with Pr. 22 "Stall prevention operation level", or disable stall prevention with Pr. 156
"Stall prevention operation selection". (Use Pr. 156 to set either operation continued or not
at OL operation.)
Causes and corrective actions
FR-LU08
OL
6 - 13