Mitsubishi Electric FR-F820-00077 Instruction Manual page 802

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Ethernet communication (FR-F800-E)
Programming example for parameter reading
The following program reads Pr. 7 "Acceleration time" of the station 1 inverter to output to D1.
● Pr. 7 "Acceleration time" reading instruction code: H07 (hexadecimal)
● Refer to page A-5 for details of the parameter instruction code.
● The reply code at the time of instruction code execution is set to D2. (Refer to page 5-621.).
SM1536
SD1536.0
SD1540.0
(0)
M0
X20
(4)
M300
(8)
M301
X100F
(10)
M302
X100F
(17)
(25)
Fig. 5-294:
Programming example 5
NOTE
For the parameter assigned the number of 100 or higher, change the link parameter extended set-
ting (set it to other than H00). Refer to page A-5 for the settings.
5 - 630
M0
Check the data link status of the station 1.
PLS
M300
SET
M301
Write the Pr. 7 read code (H07) to RWw2.
MOV
H7
W102
Turn ON the instruction code execution request
SET
Y100F
(RY0F).
RST
M301
SET
M302
Read the acceleration time (RWr3) and the reply
MOV
W3
D1
code (RWr2) to output to D1 and D2 when the
instruction code execution completion (RX0F)
MOV
W2
D2
turns ON.
Turn OFF the instruction code execution
RST
Y100F
request (RY0F).
RST
M302
END
Parameters
I003134E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents