(N) Operation via communication and its settings
5.12.6
MODBUS® RTU communication specification
Operation by MODBUS® RTU communication or parameter setting is possible by using the MODBUS®
RTU communication protocol from the RS-485 terminals of the inverter.
Pr.
331
N030
332
N031
334
N034
343
N080
539
N002
549
N000
NOTES
To use the MODBUS® RTU protocol, set "1" to Pr. 549 "Protocol selection".
If MODBUS® RTU communication is performed from the master to the address 0 (station number
0), the data is broadcasted, and the inverter does not send any reply to the master. To obtain
replies from the inverter, set Pr. 331 "RS-485 communication station number" ≠ "0 (initial value)".
Some functions are disabled in broadcast communication. (Refer to page 5-491.)
If a communication option is mounted with Pr. 550 "NET mode operation command source selec-
tion" = "9999 (initial value)", commands (operation commands) transmitted via RS-485 terminals
become invalid. (Refer to page 5-130.)
Upon delivery the FR-F800-E inverter models are not equipped with the RS-485 terminal block.
5 - 488
Name
RS-485 communication
station number
RS-485 communication
speed
RS-485 communication
parity check selection
Communication error
count
MODBUS® RTU
communication check
time interval
Protocol selection
Initial
Setting
Description
value
range
0
Broadcast communication
0
Inverter station number specification
1 to 247
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
Set the communication speed.
3, 6, 12, 24,
The setting value × 100 equals the communication
48, 96, 192,
96
speed.
384, 576,
For example, if 96 is set, the communication speed is
768, 1152
9600 bps.
Without parity check
0
Stop bit length 2 bits
With parity check at odd numbers
2
1
Stop bit length 1 bit
With parity check at even numbers
2
Stop bit length 1 bit
Displays the communication error count during
0
MODBUS® RTU communication. Read-only.
MODBUS® RTU communication, but the inverter trips
0
in the NET operation mode.
Set the interval of the communication check (signal
9999
0.1 to 999.8 s
loss detection) time. (same specifications as Pr. 122)
9999
No communication check (signal loss detection)
0
Mitsubishi inverter protocol (computer link)
0
1
MODBUS® RTU protocol
2
BACnet MS/TP protocol
Parameters