(H) Protective function parameter
5.7.5

Initiating a protective function

A fault (protective function) is initiated by setting the parameter.
This function can be used to check how the system operates at activation of a protective function.
Pr.
997
H103
● To initiate a fault (protective function), set the assigned number of the protective function you
want to initiate in Pr. 997.
● The value set in Pr. 997 is not stored in EEPROM.
● When a protective function activates, the inverter trips, a fault is displayed, and a fault signal (ALM,
ALM2) is output.
● The latest fault in the faults history is displayed while the fault initiation function is in operation.
After a reset, the faults history goes back to the previous status. (The protective function gener-
ated by the fault is not saved in the faults history.)
● Perform inverter reset to cancel the protective function.
● For the selectable parameter by Pr. 997 and the corresponding protective functions, refer to page 6-9.
NOTES
If a protective function is already operating, no fault can be activated by Pr. 997.
The retry function is disabled when a protective function has been initiated by the fault initiation
function.
If a fault occurs after a protective function has been activated, the protective function indication
does not change. The fault is not saved in the faults history either.
5 - 162
Name
Fault initiation
Initial
Setting
Description
value
range
The setting range is same with the one for fault data
codes of the inverter (which can be read through
16 to 253
communication).
Written data is not stored in EEPROM.
9999
The read value is always "9999".
9999
With this setting, the protective function does not
activate.