(A) Application parameters
5.11.10
PID control enhanced functions
PID control enhanced functions can be used to perform PID control according to applications.
(For the details of the PID control, refer to page 5-353.)
Pr.
1361
A440
1362
A441
1363
A447
1364
A448
1365
A449
1366
A627
1367
A628
1368
A629
111
F031
1369
A446
1370
A442
1371
A443
1372
A444
1373
A445
1374
A450
1375
A451
1376
A414
1377
A452
1378
A453
1379
A454
5 - 404
Name
Detection time for PID
output hold
PID output hold range
PID Priming time
Stirring time during sleep
Stirring interval time
Sleep boost level
Sleep boost waiting time
Output interruption
cancel time
Check valve deceleration
time
Check valve closing
completion frequency
Detection time for PID
limiting operation
PID upper/lower limit pre-
warning level range
PID measured value
control set point change
amount
PID measured value
control set point change
rate
Auxiliary pressure pump
1000%
operation starting level
Auxiliary pressure pump
1000%
operation stopping level
Auxiliary motor stopping
level
PID input pressure
selection
PID input pressure
warning level
PID input pressure fault
level
Initial
Setting range
Description
value
Set the time from when the deviation falls within the
5 s
0 to 900 s
PID output hold range until the PID output is held.
0 to 50%
Set the range in which the PID output is held.
9999
9999
The PID output holding is disabled.
Set the time from when the priming operation starts
0 to 360 s
until the main pump starts.
9999
9999
The PID priming pump function is disabled.
15 s
0 to 3600 s
Set the stirring time.
0 h
0 to 1000 h
Set the interval time for the stirring operation.
Increase the set point before the PID output
0 to 100%
suspension function is activated.
9999
9999
The PID sleep boost function is disabled.
0 s
0 to 360 s
Set the waiting time for the sleep boost operation.
Set the time from when the deviation reaches the
0 s
0 to 360 s
output interruption cancel level until the output is
started.
Set the deceleration time for the check valve
0 to 3600 s
deceleration function.
9999
9999
The check valve deceleration function is disabled.
Set the frequency at which the check valve
0 to 120 Hz
deceleration stops.
9999
9999
The check valve deceleration function is disabled.
Set the time from when the measured value input
0 s
0 to 900 s
exceeds the Pr.131 or Pr.132 setting until the FUP or
FDN signal is output.
Set the operation range for the PID upper/lower limit
0 to 50%
pre-warning function.
9999
The PID upper/lower limit pre-warning function is
9999
disabled.
Set the set point change amount for the PID upper/
5%
0 to 50%
lower limit pre-warning operation.
Set the set point change rate for the PID upper/lower
0%
0 to 100%
limit pre-warning operation.
Set the deviation level for operating the auxiliary
900 to 1100%
pressure pump.
Set the deviation level for stopping the auxiliary
900 to 1100%
pressure pump.
Set the level for stopping the auxiliary motor by the
0 to 100%
PID overpressure control function.
9999
9999
The PID overpressure control function is disabled.
1
Terminal 1 pressure input
2
Terminal 2 pressure input
9999
3
Terminal 4 pressure input
9999
The PID input pressure control function is disabled.
20%
0 to 100%
Set the input pressure warning level.
0 to 100%
Set the input pressure fault level.
9999
9999
The input pressure fault detection is disabled.
Parameters