Connection Of The Brake Unit (Bu Type) - Mitsubishi Electric FR-F820-00077 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Installation and wiring
2.8.3

Connection of the brake unit (BU type)

Connect the brake unit (BU type) correctly as shown below. Incorrect connection will damage the in-
verter. Remove the jumpers across terminals HB and PC and terminals TB and HC of the brake unit and
fit one across terminals PC and TB.
The BU type is compatible with FR-F820-02330(55K) or lower and FR-F840-01160(55K) and lower.
Three-
phase AC
power
supply
Fig. 2-52:
When the power supply is 400 V class, install a stepdown transformer.
NOTES
The wiring distance between the inverter and brake unit (BU type), and between the brake unit
(BU type) and discharging resistor must be within 2 m each. Even when the cable is twisted, the
wiring length must be within 5 m.
If the transistors in the brake unit should becomes faulty, the resistor will overheat and result in a
fire. Install a magnetic contactor on the inverter's input side and configure a circuit that shut off
the current in case of a fault.
Remove the jumper across terminals P/+ and P1 only when connecting a DC reactor (FR-HEL).
FR-F800
MC
MCCB
Connection with the brake unit BU
Connection of stand-alone option units
T
Inverter
Motor
U
R/L1
V
M
S/L2
W
T/L3
N/-
P/+
Discharging
resistor
ON
OFF
MC
MC
Brake unit
Remove the
(BU type)
jumper
TB
N
HC
OCR
HB
HA
OCR
PC
Fit a jumper
PR
P
I002411E_B
2 - 75