Peripheral Devices - Mitsubishi Electric FR-F820-00077 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Peripheral devices

2.1.2
Peripheral devices
Check the model of the inverter you purchased. Appropriate peripheral devices must be selected ac-
cording to the capacity.
Refer to the table below to prepare appropriate peripheral devices.
LD rating (Pr. 570 "Multiple rating setting" = "1")
● 200 V class
Motor
output
[kW]
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
Tab. 2-2:
Assumes the use of an IPM motor MM-EFS/MM-THE4 or a Mitsubishi 4-pole standard motor with
the power supply voltage of 200 V AC 50 Hz.
Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, provide the appropriate UL and cUL listed fuse or UL489
molded case circuit breaker (MCCB) that is suitable for branch circuit protection. (Refer to the
Installation Guideline.)
The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic
contactor is 500,000 times. When the magnetic contactor is used for emergency stops during
motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input
side current as JEM1038-AC-3 class rated current. When using an MC on the inverter output side
for commercial-power supply operation switching using a general-purpose motor, select an MC
regarding the rated motor current as JEM1038-AC-3 class rated current.
2 - 4
Molded case circuit breaker (MCCB) or
Earth leakage circuit breaker (ELB)
Applicable inverter
model
Power factor improving (AC or DC)
FR-F820-00046(0.75K)
FR-F820-00077(1.5K)
FR-F820-00105(2.2K)
FR-F820-00167(3.7K)
FR-F820-00250(5.5K)
FR-F820-00340(7.5K)
FR-F820-004900(11K)
FR-F820-00630(15K)
FR-F820-00770(18.5K)
FR-F820-00930(22K)
FR-F820-01250(30K)
FR-F820-01540(37K)
FR-F820-01870(45K)
FR-F820-02330(55K)
FR-F820-03160(75K)
FR-F820-03800(90K)
FR-F820-04750(110K)
Breakers and contactors (LD rating, 200 V class)
MCCB
INV
MCCB
INV
(NF, NV type)
reactor
Without
With
10A
10A
15A
15A
20A
15A
30A
30A
50A
40A
60A
50A
75A
75A
125A
100A
150A
125A
175A
125A
225A
150A
250A
200A
300A
225A
400A
300A
400A
400A
500A
Fig. 2-2:
M
Installation of the breakers
M
Installation and wiring
Input-side magnetic contactor
Power factor improving (AC or DC)
reactor
Without
With
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T21
S-T10
S-T25
S-T21
S-N35
S-T25
S-N35
S-N35
S-N50
S-N50
S-N65
S-N50
S-N80
S-N65
S-N95
S-N80
S-N150
S-N125
S-N180
S-N150
S-N220
S-N180
S-N300
S-N300
S-N400
I002770E

Hide quick links:

Advertisement

Table of Contents
loading