Torque Detection Filter - Mitsubishi Electric FR-F820-00077 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Parameters
5.3.4

Torque detection filter

Set the time constant of primary delay filter for torque feedback signal.
Speed loop response is reduced. Under ordinary circumstances, therefore, use the initial value as it is.
Pr.
827
G216
837
G316
Stabilizing torque detection (Pr. 827, Pr. 837)
Current loop response is reduced. Under ordinary circumstances, therefore, use the initial value as it is.
If there is torque ripple due to high frequency disturbance, adjust until speed stabilizes by gradually
raising the setting. Speed is oppositely destabilized if the setting value is too large.
Employing multiple primary delay filters
Use Pr. 837 if changing filter according to application. Pr. 837: Second function selection (RT) signal
NOTES
The RT signal is a second function selection signal. The RT signal also enables other second func-
tions. (Refer to page 5-291.)
The RT signal is assigned to the terminal RT in the initial setting. Set "3" in any of Pr. 178 to Pr. 189
(input terminal function selection) to assign the RT signal to another terminal.
FR-F800
PM
PM
PM
Name
Torque detection filter 1
Torque detection filter 2
Initial
Setting
Description
value
range
0
Without filter
0 s
Set the time constant of primary delay filter torque
0.001 to 0.1 s
feedback signal.
Second function of Pr. 827 (enabled when RT signal
0 to 0.1 s
ON)
9999
9999
Same as Pr. 827 setting
Speed control under PM motor control
5 - 59