Parameters
When each of Pr. 131, Pr. 132 and Pr. 553 corresponding to each of the FUP, FDN and Y48 signals is
set to "9999" (function not activated), signal output and protective function are disabled.
At the same time with the signal output, the protective function (E.PID) is activated.
At the same time with the signal output, deceleration is performed using the normal deceleration
time. After the deceleration stop, the protective function (E.PID) is activated.
At the same time with the signal output, deceleration is performed using the normal deceleration
time. When the measured value returns to normal, operation can be restarted.
● Example chart
Protective function (E.PID) activation at the same time with the signal output (Pr. 554 = "1, 3, 11,
or 13") / Protective function activation after the deceleration stop (Pr. 554 = "4, 6, 14, or 16") (reverse
action)
Measured value
Upper limit level
Pr.131 (Pr.1143)
Lower limit level
Pr.132 (Pr.1144)
frequency [Hz]
Fig. 5-169:
● Example chart:
Deceleration stop (restart) at the signal output (Pr. 554 = "5, 7, 15, or 17") (reverse action)
Measured value
Upper limit level
Pr.131 (Pr.1143)
Lower limit level
Pr.132 (Pr.1144)
Output
frequency [Hz]
Fig. 5-170:
FR-F800
Measured
Pr.1370
Pr.1370
value
Pr. 1370
FUP
FDN
Output
Example chart of protective function activation
Pr.1370
Pr.1370
Pr. 1370
FUP
FDN
Operation is continued when
the measured value reaches or
falls below the lower limit.
Example chart of deceleration stop (restart)
Pr. 1370
Pr.1370
Pr.1370
Output shutoff
(Pr. 554 = "1, 3, 11, 13")
Measured value
Pr.1370
Pr.1370
Pr. 1370
Deceleration stop when the
Deceleration stop when the
Deceleration stop when the
measured value reaches or
measured value reaches or
measured value reaches or
exceeds the upper limit.
exceeds the upper limit.
exceeds the upper limit.
(A) Application parameters
Pr.1370
Pr.1370
Pr. 1370
Time
ON
Deceleration stop
(Pr. 554 = "4, 6, 14, 16")
E.PID
E.PID
Pr.1370
Pr.1370
Pr. 1370
Time
ON
Operation can be
restarted when the
measured value exceeds
the upper limit.
I003041
I003042E
5 - 365