Mitsubishi Electric FR-F820-00077 Instruction Manual page 77

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Installation and wiring
Communication
Terminal
symbol
Tab. 2-20:
Ethernet connector (FR-F800-E)
For information regarding the communication signals of the Ethernet connector refer to page 2-83.
Safety stop signal
Terminal
symbol
S1
S2
SIC
SO
SOC
Tab. 2-21:
FR-F800
Terminal name
PU connector
TXD+ Inverter transmission
terminal
TXD-
RXD+
Inverter reception terminal
RXD-
GND
Earthing (grounding)
(SG)
USB A connector
USB B connector
Communication signals (RS-485 and USB)
Terminal name
Terminal function description
The terminals S1 and S2 are used for the safety stop
input signal for the safety relay module. The terminals S1
Safety stop input
and S2 are used at the same time (dual channel).
(Channel 1)
Inverter output is shutoff by shortening/opening
between terminals S1 and SIC, or between S2 and SIC.
In the initial status, terminals S1 and S2 are shorted with
the terminal PC by shorting wires. The terminal SIC is
Safety stop input
shorted with the terminal SD. Remove the shorting wires
(Channel 2)
and connect the safety relay module when using the
safety stop function.
Safety stop input
Common terminal for terminals S1 and S2.
terminal common
Indicates the safety stop input signal status.
Switched to LOW when the status is other than the
internal safety circuit failure. Switched to HIGH during
the internal safety circuit failure status.
Safety monitor output
(LOW is when the open collector output transistor is ON
(open collector
(conducted). HIGH is when the transistor is OFF (not
output)
conducted).)
Refer to the Safety stop function instruction manual
when the signal is switched to HIGH while both
terminals S1 and S2 are open. (Please contact your sales
representative for the manual.)
Safety monitor output
Common terminal for terminal SO.
common
Safety stop signal
Terminal function description
With the PU connector, communication can be made through
RS-485. (For connection on a 1:1 basis only)
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 4800 to 115200 bps
Overall length: 500 m
The RS-485 terminals enables the communication by RS-485.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 300 to 115200 bps
Overall length: 500 m
A connector (receptacle)
A USB memory device enables
parameter copies and the trace
function.
Mini B connector (receptacle)
Connected to a personal computer
via USB to enable setting,
monitoring, test operations of the
inverter by FR Configurator2.
Control circuit
Refer
to
page
5-453
5-455
2-68
Interface:
Conforms to USB1.1
(USB2.0 full-speed
compatible)
Transmission speed:
2-68
12 Mbps
Refer
Rated
to
specification
page
Input resistance
4.7 kΩ
Input current
4 to 6 mA DC
(with 24 V DC
input)
2-64
Permissible load
24 V DC (27 V DC at
maximum), 0.1 A
(The voltage drop
is 3.4 V at
maximum while
the signal is ON.)
2 - 49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents