Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
5.4.3

Start quick commissioning and select the application class

Starting quick commissioning
Preconditions
● The power supply is switched on.
● The operator panel displays setpoints and actual values.
Procedure
Proceed as follows to carry out quick commissioning:
Press the ESC key.
Press one of the arrow keys until the BOP-2 displays the "SETUP" menu.
To start quick commissioning, in the "SETUP" menu, press the OK key.
If you wish to restore all of the parameters to the factory setting before the quick commissioning,
proceed as follows:
1. Press the OK key.
2. Switchover the display using an arrow key: nO → YES
3. Press the OK key.
When selecting an application class, the inverter assigns the motor control with the appropriate
default settings:
Depending on the Power Module, the inverter may not offer any application class. Also in
this case, continue the commissioning as described for "Expert".
136
Standard Drive Control (Page 138)
Dynamic Drive Control (Page 140)
Expert (Page 142)
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD