Installing
4.4 Connecting the line supply, motor, and inverter components
4.4.7

Connecting the inverter with the PM240P-2 Power Module

Figure 4-9
PM240P-2 Power Module connection overview
Table 4-18
Connection, cross-section and tightening torque for PM240P-2 Power Modules
Inverters
Connection
FSD
Line supply,
motor
FSE
FSF
Line supply,
motor
Connections, frame sizes FSD ... FSF
You must remove the covers from the connections in order to connect the line supply and
motor cables to the inverter.
Figure 4-10
80
Screw-type termi‐
10 ... 35 mm
nal
25 ... 70 mm
35 ... 2 × 120 mm
22 ... 25 Nm
Cable lug accord‐
ing to SN71322
2
1
Remove the connection covers
Cross-section, tightening torque
Metric
, 2.5 ... 4.5 Nm
20 ... 10 AWG, 22 lbf in
2
8 ... 2 AWG, 40 lbf in
, 8 ... 10 Nm
6 ... 3/0 AWG, 88.5 lbf in
2
,
1 ... 2 × 4/0 AWG, 210 lbf in --
2
3
1
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD