Description
3.5 Components for the Power Modules
3.5.4
Output reactor
Output reactors reduce the voltage stress on the motor windings and
the load placed on the inverter as a result of capacitive recharging
currents in the cables. An output reactor is required for shielded motor
cables longer than 50 m or unshielded motor cables longer than 100 m.
The figure on the right-hand side shows as example the output reactors
for PM240-2 Power Modules, FSB and FSC.
NOTICE
The output reactor is damaged if the inverter pulse frequency is too high
The output reactors are designed for pulse frequencies of 4 kHz. The output reactor can
overheat if the inverter is operated with pulse frequencies > 4 KHz. Excessively high
temperatures damage the output reactor.
● Operate the inverter with an output reactor with a maximum pulse frequency of 4 kHz.
Output reactors for PM240-2 Power Modules, 380 V ... 480 V
Power Module
FSA
FSB
FSC
FSD ... FSF: An output reactor is not required.
Output reactors for PM240-2 Power Modules, 500 V ... 690 V
An output reactor is not required.
42
6SL3210-1PE11-8 . L1,
6SL3210-1PE12-3 . L1,
6SL3210-1PE13-2 . L1,
6SL3210-1PE14-3 . L1,
6SL3210-1PE16-1 . L1
6SL321 . -1PE18-0UL1
6SL3210-1PE21-1 . L0,
6SL3210-1PE21-4 . L0,
6SL321 . -1PE21-8 . L0
6SL3210-1PE22-7 . L0,
6SL321 . -1PE23-3 . L0
Power
0.55 kW ... 2.2 kW
3 kW
4 kW ... 7.5 kW
11 kW ... 15 kW
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
Output reactor
6SL3202-0AE16-1CA0
6SL3202-0AE18-8CA0
6SL3202-0AE21-8CA0
6SL3202-0AE23-8CA0