Output Reactor - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Description
3.5 Components for the Power Modules
3.5.4

Output reactor

Output reactors reduce the voltage stress on the motor windings and
the load placed on the inverter as a result of capacitive recharging
currents in the cables. An output reactor is required for shielded motor
cables longer than 50 m or unshielded motor cables longer than 100 m.
The figure on the right-hand side shows as example the output reactors
for PM240-2 Power Modules, FSB and FSC.
NOTICE
The output reactor is damaged if the inverter pulse frequency is too high
The output reactors are designed for pulse frequencies of 4 kHz. The output reactor can
overheat if the inverter is operated with pulse frequencies > 4 KHz. Excessively high
temperatures damage the output reactor.
● Operate the inverter with an output reactor with a maximum pulse frequency of 4 kHz.
Output reactors for PM240-2 Power Modules, 380 V ... 480 V
Power Module
FSA
FSB
FSC
FSD ... FSF: An output reactor is not required.
Output reactors for PM240-2 Power Modules, 500 V ... 690 V
An output reactor is not required.
42
6SL3210-1PE11-8 . L1,
6SL3210-1PE12-3 . L1,
6SL3210-1PE13-2 . L1,
6SL3210-1PE14-3 . L1,
6SL3210-1PE16-1 . L1
6SL321 . -1PE18-0UL1
6SL3210-1PE21-1 . L0,
6SL3210-1PE21-4 . L0,
6SL321 . -1PE21-8 . L0
6SL3210-1PE22-7 . L0,
6SL321 . -1PE23-3 . L0
Power
0.55 kW ... 2.2 kW
3 kW
4 kW ... 7.5 kW
11 kW ... 15 kW
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
Output reactor
6SL3202-0AE16-1CA0
6SL3202-0AE18-8CA0
6SL3202-0AE21-8CA0
6SL3202-0AE23-8CA0